TRANSFORMER SERIES : Omega Xmer, 

Operating Manual

 

Indication

Before initial operation we ask you to pay full attention to these assembling instructions in order to guarantee the 
reliability and to ensure the performance of the device.

Functional description

Current transformers of the model range Omega are inductive single conductor-current transformers operating 
according to the transformer principle. Due to the applicated measuring principle, current transformers of this type 
may only be installed in alternating current (AC) networks.

Safety instructions

 

 

 

 

In order to avoid personal and material damage the following assembling steps     

 

 

 

 

must by performed only by authorised, qualified and trained personnel.

 

 

 

 

If the secondary circuit is operated without a burden/load (open) high voltages

 

 

 

 

may appear. These voltage values are dangerous for persons as well as for the

 

 

 

 

functional reliability of the current transformer.

 

 

 

 

It is forbidden to operate the current transformer without a secondary 

 

 

 

 

circuit (open)!

Technical parameters

Primary current:    

 

30A to 6000A

Secondary current: 

  

1A or 5A

Accuracy class:   

 

0.2, 0.2s, 0.5, 0.5s & 1

Over current limiting factor:  

FS5, FS10, Fs15

Rated frequency:  

 

60Hz

Rated continuos thermal
current (standard): 

 

1,2 x In

Rated short time thermal
current Ith: 

 

 

 

60 x In, 1 s (Max 40kA)

Rated isolation level:  

 

0,72/3/-kV

Place of installation:  

 

Indoor

Altitude:  

 

 

up to 2000 m

Degree of protection:  

 

Ip20

Degree of pollution: 

 

2

Ambient temperature:  

 

-5°C 

≤ 

ϑ ≤ +40°

C

 

 

 

 

(0…95% relative humidity, non condensing!

Storage temperature: 

 

-25°C 

≤ ϑ ≤ +70°

C

Applied standards:  

 

IEC - 61869 - Part : 1 & 2 : Performance

 

 

 

 

IEC - 61010 - 2 : Safety.

Low Voltage-Current Transformer - 

Omega Xmer Series 

Omega 10, Omega 20, 

Omega 10 Series
Omega 20 Series