Siemens Building Technologies 

RDF300.2/SRL 

2016-08-22 

1/2 

 

 
 
 

Mounting locations                     

Mount the thermostat on a recessed square conduit box with fixed centers of 60.3 mm. Do not mount in niches 
or bookshelves, behind curtains, above or near heat sources and wind outlets or inlets, and exposed to direct 
radiation. Mount about 1.5 m above the floor. 

 

Application settings and removal of front panel 

    
 
 
 
 
 

2-pipe   4-pipe 

  

 

                                                         

If the unit is new, the front panel is separated from the mounting plate as shown in 

point 5

 above. Select  

applications according to the dip switch settings.  

To remove the front panel, proceed as follows: 

1.  Insert the tool into the opening to disconnect the top of the front panel from the mounting plate. 

2.  Place the tool near the center at both sides and push inward. 

3.  Swing the top of the front panel downward.  

4.  Remove the panel from the mounting plate. 

5.  Check and select the desired applications (2-/4-pipe only) according to the dip switches shown. 

 

 

A6V10944443 

 

 
 
 
 
 

 

RDF300.02/SRL 

Mounting Instructions 

for Shangri-la Hotels 
 

 

Note: please refer to the installation  
manual

 M3076 

for more details

 

 