PowerLink CM 

Smart Communications, PowerLink CM Product Information 

C53000-X6040-C256-2 Edition Sept. 2021 

 

 

 

 

 

 

 

 

 

 

 

 

ENGLISH 

 

Read and understand these instructions and the relevant manual before installing, 

operating, or maintaining the device. For available software and complete documentation for 

PowerLink CM see: 
 
Siemens Industry Online Information platfor

SIOS 

Further Support 

If special problems arise, or further information are required, please contact your Siemens 

representative. Our Customer Support Center provides a 24-hour service. 
Siemens AG 

Smart Infrastructure – Digital Grid 
Customer Support Center 
●  Phone: +49 911 2155 4466 

●  E-Mail: 

[email protected]

 

Disclaimer of Liability 

Although we have carefully checked the contents of this publication for conformity with the 

hardware and software described, we cannot guarantee complete conformity since errors 

cannot be excluded. 

The information provided in this manual is checked at regular intervals and any corrections 

that might become necessary are included in the next releases. Any suggestions for 

improvement are welcome. 

Copyright 

Copyright © Siemens AG 2021 – All Rights Reserved 

The reproduction, transmission or use of this document or its contents is not permitted 

without express written authority. Offenders will be liable for damages. All rights, including 

rights created by patent grant or registration of a utility model or design, are reserved. 

OpenSSL 

This product includes software developed by the OpenSSL Project for use in OpenSSL 

Toolkit (

http://www.openssl.org/

). 

This product includes software written by Tim Hudson (

[email protected]

). 

This product includes cryptographic software written by Eric Young ([email protected]). 

Notes on Safety 

This document contains notes that must be adhered to ensure personal safety and to avoid 

damage to property during commissioning and use.  
However, it does not constitute a complete description of all safety measures required for 

installation, service, and maintenance of the device. Details are to be taken from the device 

manual; those are mandatory. Keep it safe for later usage. 

 

Warning: Danger of severe personal injury or substantial damage to property 

Hazardous voltages may occur in devices and modules during operation. Always 

observe the instructions given in “Qualified Electrical Engineering Personnel” below. 

 

 

Qualified Electrical Engineering Personnel 

Qualified electrical engineering personnel must have up to date technical qualifications 

as electrical technicians. Only these persons may commission, use, maintain, 

decommission and dispose of the device according to the state-of-the-art standards of 

engineering in the high voltage power line environment. 

 

 

Warning: Laser radiation! Danger of eye injury

 

This device may contain a class 1 laser. Do not look directly into the beam. 

 

 

Warning: Danger of damage due to static electrical charges

 

The printed circuit boards of numerical relays contain CMOS circuits. These shall not 

be withdrawn or inserted under live conditions! The modules must be so handled that 

any possibility of damage due to static electrical charges is excluded. 
During any necessary handling of individual modules, the recommendations relating to 

the handling of electrostatically endangered components (EEC) must be observed. 
In installed conditions, the modules are in no danger. 

Use as Prescribed 

The device may only be used for such applications as set out in the user instructions, and 

only in combination with equipment recommended and approved by Siemens. 
Correct and safe operation of the product requires adequate transportation, storage, 

installation and mounting in a control cabinet, as well as appropriate use and maintenance. 
Only qualified electrical engineering personnel may install, set up, commission, attach 

communication cables, power supply lines and ground to the device.  
Check and follow the electrical operating conditions, mechanics, and climatic max. ambient 

conditions for safe operation. Connect and operate the device only in conformance with the 

values as specified in the ‘Technical Data’ below. 
Commissioning must be carried out in accordance with good engineering practice and 

under consideration of local installation rules and laws (also applicable and obligatory for 

cabinet internal wiring). 
Fuses may be required on all phases in the electrical installation, depending on local 

installation conditions and requirements. 
During operation of the equipment, it is unavoidable that certain parts will carry dangerous 

voltages. Severe injury or damage to property can occur if the appropriate measures during 

use are not taken: 

  Make sure, that the equipment is properly connected to ground at all times and 

mechanically fixed in the rack. The device is connected through a coupling unit to the 

HV line. A permanent ground connection is an essential precondition to safeguard the 

user against any high voltages from the HV line. 

  Degree of protection by enclosure IP20. 

  Device may only be operated in a dry location within a temperature range of 

-10 to +55 degree Celsius. 

  This is a Class A device. It is intended to be operated in an industrial environment only. 

It may cause harmful interference if operated in residential/light industry environment. 

  Hazardous voltages can be present on all components when the device is connected 

to a power source. Before opening the device, makes sure all power sources are 

disconnected or switched off. Even after the power supply has been disconnected, 

hazardous voltages can still be present within the device (capacitor storage). 

  The limit values indicated in the manual must not be exceeded; that also applies to 

testing and commissioning. 

Statement of Conformity 

  The product is in conformity with the regulations of the following European Directives: 

  EMC Directive 2014/30/EU 

  Low Voltage Directive 2014/35/EU 

  RoHS Directive 2011/65/EU 

Used Symbols 

 

Caution, hazard. The documentation 

must be observed. 

 

Protection class I / protective 

earthing 

  CE conformity 

  Hazardous voltage 

 

Qualified Electrical Engineering 

Personnel 

  Note 

 

 

Distributor statement according to WEEE-Guideline 2012/19/EU 

Do not throw the device in the household trash! Please dispose of the device 

according to the guidelines regarding electronic waste in your country.  

Application 

PowerLink CM is a condition monitoring system for high voltage lines. 

 

 

Unpacking a Device 

  Check the package for external transport damage. A damaged packing may indicate 

that the device inside is also damaged. 

  Unpack the device carefully; do not use force. 

  Visually check the device to ensure that it is in perfect mechanical condition. 

  Return a damaged device to the manufacturer or dispose it correctly. A defect device 

may not either be used or repaired by the user. 

 

Note:

 Before commissioning the device, leave it in the final operation room for at least 

2 hours. This allows it to reach room temperature and to prevent dampness and 

condensation. 

Repacking a Device 

  If you store devices after incoming inspection, pack them in suitable storage 

packaging. 

  If devices are to be transported, pack them in transport packing. 

  Put the accessories supplied in the packing with the device. 

Storing a Device 

  Only store devices on which you have carried out an incoming inspection, thus 

ensuring that the warranty remains valid. 

  The relative humidity must be at a level where condense water and ice are prevented 

from forming. 

  If the device has been in storage for more than 2 years, connect it to the primary 

voltage source, and operate it for 1 to 2 days. This will cause the electrolytic capacitors 

to form on the printed circuit board assemblies again. 

  When the device is reshipped ensure that the transport requirements for the selected 

means of transport are met. The outer package alone is not adequate for transport 

purposes. 

Mounting 

The device is designed for horizontal mounting in a cabinet or rack. Min. distance between 

two PowerLink CM devices is one unit of height (= 1.75 inches or 44.45 mm). The climatic 

conditions have to be within the specified values (see technical data). Consider the weight 

and position of the device to avoid personal injuries. 

Commissioning 

 

Before making any connections, ground the equipment and the grounding 

terminal. 

  Connection of the Supply Voltage: The AC supply voltage is connected to the terminals 

PE-N-L1 (Protective Earth, Neutral, Line). In case of DC voltage, the (-) is connected to 

the N and (+) to the L1 terminal. The terminals are covered. The supply voltage 

connected must be within the specified limit values (see technical data). These values 

indicated in the manual must not be exceeded at any time. 

  Make sure that all front and back covers of the device are remounted upon completion 

of the installation. 

  Turn on the Supply Voltage: switch S1 located on DMB board enables/disables the 

secondary voltages of the power supply. 

  Down position: Off mode; LED "i" (red) lights up on the PSPA2 power supply unit(s). 

Up position: On mode; LEDs +48V/-48V (green) lights up on the PSPA2 power supply 

unit(s). 

  After system startup the LEDs on DMB board will light up green. 