Installation and Power Limited Wiring Instructions

Models EB-32, EB-33 and EB-35
System 3 Control Panel Enclosures

(For indoor use only in dry environments)

INTRODUCTION

The EB-32, EB-33 and EB-35 Enclosures (See Figure
1) from Siemens Industry, Inc. are designed to accom-
modate System 3 control panels, input and output
modules, and all power supplies utilized in the system.
They can be either surface or semi-flush mounted.

Each enclosure consists of a back box and door cover
assembly fabricated of heavy gauge sheet steel. The
back box, which is finished in a black enamel, is
designed for mounting the "Z" brackets and "U"
channel supports on which are mounted the controls,
modules, and power supplies.

INSTALLATION

Securely fasten the control panel enclosure to a shock
and vibration-free surface in a clean, dry area. It
should be mounted with the top of the enclosure
approximately 6 feet above the floor. The location
should ensure that the control panel is easily visible
and readily accessible for maintenance. Leave
sufficient room to open the enclosure door.

Wiring should be in accordance with national and local
codes for fire alarm circuits. For AC supply power, use
No. 14 or larger AWG, 600V insulation wire.

1.

Remove knockouts in the backbox where field
wiring is required. (Refer to Table 1, Table 2 and
Figure 1.)

2.

Hold the empty enclosure against the wall at the
designated height.

3.

Mark drill points on the wall in the center of  the
two slots on the upper rear of the box (Refer to
Figure 1).

4.

Drill the two holes and screw in the top bolts,
leaving a small gap between the wall and each
top bolt.

5.

Mount the enclosure on the two bolts and then
install the bottom bolts.

6.

Tighten all bolts securely against the back wall of
the enclosure.

7.

Pick up the module/frame assembly by the straps
provided at the end of the wiring channels. Do not
place hands behind the modules, as the circuitry
may be damaged.

8.

Install the module/frame assembly in the enclo-
sure, securing it to the studs with the 5/16 inch
nuts provided.

CAUTION:

Do not overtighten nuts (do not use
ratchet type wrench), as the studs can be
broken if excessive force is applied.

WIRING

In compliance with UL-864, all power limited fire
protective signaling conductors must be separated a
minimum of ¼ inch from all of the following items
located within a control panel:

• electric light
• power
• Class 1 or non-power limited signaling conductors

To meet these requirements, the following guidelines

must be observed

 when installing modules and

wiring to a System 3 control panel.

When installing power limited field wiring, the installer
must comply with NEC article 760-54, which states:

The fire alarm power-limited circuits are installed
using Types FPL, FPLR, FPLP or permitted
substitute cable, provided these power-limited
cable conductors extending beyond the jacket are
separated by a minimum of 0.25 in. (6.35 mm) or
by a nonconductive sleeve or nonconductive
barrier from all other conductors.

P/N 315-093680-9

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

Summary of Contents for EB-32

Page 1: ...e box Refer to Figure 1 4 Drill the two holes and screw in the top bolts leaving a small gap between the wall and each top bolt 5 Mount the enclosure on the two bolts and then install the bottom bolts 6 Tighten all bolts securely against the back wall of the enclosure 7 Pick up the module frame assembly by the straps provided at the end of the wiring channels Do not place hands behind the modules ...

Page 2: ... 3 5 3 3 3 1 3 4 1 s n o i t i s o P l l A s n o i t i s o P l l A 8 6 n o i t i s o P B T WIRING IN THE ENCLOSURE Non power Limited Wiring Wiring from the batteries to the BC 37 is considered non power limited To maintain the required separa tion the wiring must be routed in the right side of the enclosure All wiring within the enclosure must be routed as shown in Figure 2 To maintain the require...

Page 3: ...ing Dimensions Enclosure A B C D EB 32 201 2 in 52 07 cm 223 8 in 56 83 cm 241 2 in 62 23 cm EB 33 31 in 78 74 cm 327 8 in 83 50 cm 35 in 88 95 cm 151 2 in 39 37 cm EB 35 52 in 132 08 cm 53 7 8 in 136 84 cm 56 in 142 24 cm 26 in 66 04 cm ...

Page 4: ...U AA 30U AA 30U TRI R TRI S TRI R TRI D PLM 35 PLM 35 ZU 35DS ZU 35 ZN 31U ZN 34U2 1 2 3 4 5 8 7 6 1 2 3 4 5 8 7 6 1 2 3 4 5 8 7 6 1 2 3 4 5 8 7 6 Figure 2 System 3 Power Limited Wiring P N 315 093680 9 Siemens Industry Inc Building Technologies Division Florham Park NJ Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Reviews: