SIEMENS

COMBIMASTER &
MICROMASTER Integrated

Operating Instructions

Summary of Contents for COMBIMASTER CM110/3

Page 1: ...SIEMENS COMBIMASTER MICROMASTER Integrated Operating Instructions ...

Page 2: ...ASTER and MICROMASTER Integrated 6 Mains Cable Connections 6 Control Cable Connections 9 Drive Operation 10 General 10 Basic Operation 11 Operation External Analogue Control 11 Operation Digital Control 12 Stopping the Motor 12 If the Motor Does Not Start Up 12 Options Accessories 13 Electrical Data COMBIMASTER 13 Electrical Data MICROMASTER Integrated 16 Parameter Summary List 17 Technical Data s...

Page 3: ...ations as well as regulations covering correct use of tools and personal protective equipment Note that the following terminals can carry dangerous voltages even when the inverter is inoperative Power supply terminals L1 L2 and L3 Motor terminals U V and W When using the analogue input the jumpers must be correctly set and the analogue input type selected P023 before enabling the analogue input wi...

Page 4: ...commutated converters EUROPEAN MACHINERY DIRECTIVE The MICROMASTER Integrated COMBIMASTER products are suitable for incorporation into machinery The MICROMASTER Integrated COMBIMASTER must not be put into service until the machinery into which it is incorporated has been certified to be in compliance with the provisions of the European Directive 89 392 EEC Note Only valid for machinery to be opera...

Page 5: ...referred as they have lower impedance at high frequencies 2 Use screened leads for connections to the control circuitry Terminate the ends of the cable neatly ensuring that long strands of unscreened wire are not left visible 3 Separate the control cables from the power connections as much as possible using separate trunking etc If control and power cables cross arrange the cables so that they cro...

Page 6: ...oving and live parts The maximum speed see motor rating plate is not exceeded The maximum speed is the highest operating speed permitted Remember that motor noise and vibration are worse at this speed and bearing life is reduced The above list is not meant to be exhaustive additional checks may also be required Mechanical Installation MICROMASTER Integrated The motor MICROMASTER Integrated combina...

Page 7: ...the mains and control cables see Fig 6 CAUTION The printed circuit boards contain CMOS components that are particularly sensitive to static electricity For this reason avoid touching the boards or components with hands or metal objects Mains Cable Connections Ensure that the power source supplies the correct voltage and is designed for the rated current Use the appropriate circuit breakers with th...

Page 8: ...ault V JP 300 V I Mains connection Control cable connector PL800 OPm2 connector SK200 LED green LED yellow Control Potentiometer R314 Figure 2 Electrical Connection CS B IMPORTANT Ensure that the following tightening torques are used Access cover retaining screws 4 0Nm Gland hole covers 1 0Nm Mains connector screws 1 0Nm Earth Connection 1 5Nm Check that the supply voltage is correct for the inver...

Page 9: ...umper in I position current input Control cable connector PL700 OPm2 connector SK200 LED green LED yellow Control Potentiometer R314 Figure 3 Electrical Connection CS A IMPORTANT Ensure that the following tightening torques are used Access cover retaining screws 4 0Nm Gland hole covers 1 0Nm Mains connector screws 1 0Nm PL700 Screws 0 5Nm Earth Connection 1 5Nm Check that the supply voltage is cor...

Page 10: ...e optional potentiometer fitted as an analogue set point shown in Figure 4 assumes that jumper JP304 is connecting 0V pin 2 to AIN pin 4 Also 15V can be used as an alternative to P10 for the digital inputs Plug the connector block back into the PCB CS B only refit the cover and tighten the four securing screws COMBIMASTER Control Terminals Cabling Information CS A PL700 CS B PL800 Cable AWG 22 18 ...

Page 11: ...me has elapsed All settings must be only entered by qualified personnel paying particular attention to the safety precautions and warnings General For basic operation of COMBIMASTER no additional equipment is required However for more complex operation OPm2 Clear Text Display is required OPm2 is available as an option but must be ordered separately The inverter does not have a mains power switch a...

Page 12: ...itch a Connect a run stop switch between DIN1 pin 5 and P10 pin 1 on PL800 see Fig 4 if forward rotation is required If reverse rotation is required instead connect the switch to DIN2 pin 6 instead of DIN1 IMPORTANT Remove the link if fitted between pins 5 and 1 before the run stop switch is fitted b Apply mains power The green and yellow LEDs will illuminate to show that power is applied c Set th...

Page 13: ...rnal on off switch Setting the switch to OFF overrides the setting on the potentiometer and causes the motor to come to a controlled stop Via the potentiometer Turning the potentiometer counter clockwise until the input voltage drops below 2 V causes the motor to slow to a stop If an external potentiometer is applied the input voltage must also be below 2V to stop If the Motor Does Not Start Up Ch...

Page 14: ... PROFIBUS Cable 1m 6SE9996 0XA23 PROFIBUS Cable 5m 6SE9996 0XA24 PROFIBUS Cable 10m 6SE9996 0XA25 PROFIBUS Cable Link 6SE9996 0XA26 CS A Inverter Fan Option MICROMASTER Integrated only 6SE9996 0XA01 M41 CS B Inverter Fan Option MICROMASTER Integrated only 6SE9996 0XA02 M41 CS A Electro mechanical Brake Control Unit Note Expected Product release August 1999 6SE9996 0XA07 CS B Electro mechanical Bra...

Page 15: ...on U Unfiltered A Class A filter B Class B filter Position 12 shown as is for the construction type from the Siemens M11 catalogue ref E2002 K1711 A201 A2 7600 CS A Low Voltage Three Phase Units Model CM12 2 CM25 2 CM37 2 CM55 2 CM75 2 Order Number 2 pole 4 pole 1UA7053 2BU1 1UA7060 4BU1 1UA7063 2BU1 1UA7070 4BU1 1UA7070 2BU1 1UA7073 4BU1 1UA7073 2BU1 1UA7080 4BU1 1UA7080 2BU1 1UA7083 4BU1 Frame s...

Page 16: ...onstruction type from the Siemens M11 catalogue Ref see above CS B High Voltage Three Phase Units Model CM150 3 CM220 3 CM300 3 CM400 3 CM550 3 CM750 3 Order Number 2 pole 4 pole 1UA7090 2B zz 1UA7096 4B zz 1UA7096 2B zz 1UA7106 4B zz 1UA7106 2B zz 1UA7107 4B zz 1UA7113 2B zz 1UA7113 4B zz 1UA7130 2B zz 1UA7130 4B zz 1UA7131 2B zz 1UA7133 2B zz Frame size 2 pole 4 pole 90S 90L 90L 100L 100L 100L 1...

Page 17: ...4 6 A rms 6 2 A rms 8 2 A rms Mains fuse 10 A 16 A Mains Lead cross section 1mm 2 1 5mm 2 y filter option 1 Unfiltered 5 Class A filter 6 Class B filter CS A Low Voltage Three Phase Units Model MI12 2 MI25 2 MI37 2 MI55 2 MI75 2 Order Number 6SE9610 7CF10 Z C87 6SE9611 5CF10 Z C87 6SE9612 0CF10 Z C87 6SE9612 6CF10 Z C87 6SE9613 4CF10 Z C87 Motor Output Rating 0 12kW 0 16hp 0 25kW 0 33hp 0 37kW 0 4...

Page 18: ... Voltage Three Phase Units Model MI150 3 MI220 3 MI300 3 MI400 3 MI550 3 MI750 3 Order Number 6SE9613 7DD y 0 Z C87 6SE9615 8DD y 0 Z C87 6SE9617 3DD y 0 Z C87 6SE9621 1DD y 0 Z C87 6SE9621 3DD y 0 Z C87 6SE9621 7DD y 0 Z C87 Motor Output Rating 1 5kW 2 0hp 2 2kW 2 9hp 3 0kW 4 0hp 4 0kW 5 3hp 5 5kW 7 3hp 7 5kW 10 0hp Operating Input Voltage 3 AC 380 500 Vrms 10 all units 3 AC 380 480 Vrms 10 filte...

Page 19: ...on 0 P041 Fixed frequency 1 Hz 5 00 P042 Fixed frequency 2 Hz 10 00 Parameter Function Default P043 Fixed frequency 3 Hz 15 00 P044 Fixed frequency 4 Hz 20 00 P045 Inversion fixed setpoints for fixed frequencies 1 4 0 P046 Fixed frequency 5 Hz 25 00 P047 Fixed frequency 6 Hz 30 00 P048 Fixed frequency 7 Hz 35 00 P050 Inversion fixed setpoints for fixed frequencies 5 7 0 P051 Selection control func...

Page 20: ...torque P134 DC link voltage V P135 Motor RPM P137 Output voltage V P140 Most recent fault code P141 Most recent fault code 1 P142 Most recent fault code 2 P143 Most recent fault code 3 P151 Green LED function 4 Parameter Function Default P152 Yellow LED function 5 P201 PI closed loop mode 0 P202 P gain 1 0 P203 I gain 0 00 P205 Sample interval x 25 ms 1 P206 Transducer filtering 0 P207 Integral ca...

Page 21: ...out prior notice Herausgegeben vom Bereich Automatisierungs und Antriebstechnik A D Geschäftsgebiet Standard Drives Postfach 3269 D 91050 Erlangen Siemens plc Automation Drives Standard Drives Division Siemens House Varey Road Congleton CW12 1PH For Technical Support Information and to submit your suggestions for improvements see our Web Site http www con siemens co uk ...