background image

User Manual for AyAlarm

AyTerminal

V2.1

User Manual for AyAlarm

V2.1

AyTerminal

© Siemens AG Österreich 2007

Issued by
Siemens AG Österreich (Siemens Austria)
Program and System Engineering
PSE CSS MPS
Gudrunstraße 11
A-1100 Vienna

Page 1 of 52

Summary of Contents for Ay

Page 1: ...larm AyTerminal V2 1 User Manual for AyAlarm V2 1 AyTerminal Siemens AG Österreich 2007 Issued by Siemens AG Österreich Siemens Austria Program and System Engineering PSE CSS MPS Gudrunstraße 11 A 1100 Vienna Page 1 of 52 ...

Page 2: ...d 5 2 3 Configuring the AyAlarm modes 5 2 4 Activating a mode 6 2 5 Deactivating a mode or a triggered alarm 6 2 6 Turning off the AyTerminal 6 3 AyTerminal device 7 3 1 Device description 7 3 1 1 Hold switch 8 3 1 2 Status LED 8 3 1 3 Lumberg Connector 9 3 1 4 AySnapOn Connector 9 3 1 5 Navigation buttons 9 3 1 6 Speaker 10 3 1 7 Microphone 11 3 1 8 3D Ego motion sensor 11 3 1 9 Temperature senso...

Page 3: ...art 31 5 4 3 Notifiers 31 5 4 4 Triggers 34 5 4 5 Duration 39 5 4 6 Overview 39 5 5 Activating Starting a mode 41 5 6 Deactivating a mode or a triggered alarm 43 5 7 Emergency Call 43 5 8 Settings 44 5 8 1 AyServer Sync 44 5 8 2 AySnapOn 45 5 8 3 AyTerminal 45 5 8 4 Audio 48 5 8 5 Clock 49 5 8 6 Display 49 5 8 7 Security 50 5 9 Turning off the AyTerminal 51 5 10 Involved sensors in AyAlarm modes 5...

Page 4: ...erms and abbreviations Abbreviation Description APN Access Point Name AySnapOn additional device to extend the functionality of the AyTerminal device DNS Domain Name Server EW East West GPRS General Packet Radio Service GPS Global Positioning System GSM Global System for Mobile Communications GUI Graphical User Interface IMEI International Mobile Equipment Identity LED Light Emitted Diode MSISDN M...

Page 5: ...d and battery See chapter 4 Turn on the device press the central button for 2 seconds The loading screen will be displayed See chapter 4 2 1 Enter the PIN of the SIM card Select the OK option and press the Enter button right button See chapter 4 2 3 Select the AyAlarm application and press the Enter button Optional Define the deactivation code sequence of 4 buttons default up button right button d...

Page 6: ...uration see chapter 5 4 5 Voice Call Activation Time see chapter 5 4 1 Autostart see chapter 5 4 2 Notifiers see chapter 5 4 3 Phone number see 5 4 3 3 Emergency Call see chapter 4 2 2 If this mode is activated pressing the Enter button initiates an emergency call to the 112 emergency number This mode is also available if no SIM card is inserted Settings see chapter 5 8 For all the modes also an o...

Page 7: ...ion measuring sounding alarms or notifying user via web pages voice call and or SMS All this numbered features are AyApplication specific Figure 3 1 Front side of AyTerminal Figure 3 2 Lumberg connector Figure 3 3 Release button Acceptance touch button Cancel tough button Up touch button Down touch button Display and central button Loudspeaker LED Release button Lumberg connector ...

Page 8: ...10Hz Following table shows the status of the Status LED depending on the AyTerminal status Status LED color type AyTerminal status green permanent AyTerminal OFF charger connected battery charging mode red permanent AyTerminal OFF charger connected battery charging error orange permanent AyTerminal OFF charger connected battery charging finished green permanent AyTerminal ON startup phase orange g...

Page 9: ...low GREEN and current status permanent RED When the status RED is removed then the slow GREEN is again established as status of the LED Example of applying the rules In case of triggering an alarm it is defined that the status LED becomes fast blinking ORANGE In case of SMS it is defined that the status LED is blinking GREEN If SMS is sent meanwhile the alarm is triggered then the change request f...

Page 10: ...s provided On navigation button click On AyApplication specific triggering of a predefined alarm tone On AyApplication specific triggering of predefined acknowledgment tones On incoming voice calls with predefined ring tones 3 1 6 1Acknowledgement tones There are positive and negative acknowledgment tones one beep indicates a positive acknowledgment two beeps a negative acknowledgment The table be...

Page 11: ...Terminal will rise due to the charging process The AyTerminal will counterbalance this internal heating but the temperature sensor will have lower environment temperature accuracy due to the battery charging 3 1 10OLED display The AyTerminal has a white OLED display with 128x96 pixel resolution which is also the active display area used for the screen layouts In standard mode the used font is Taho...

Page 12: ... in Figure 3 6 is shown If after this screen is shown the charger is removed then AyTerminal is turned off The AyTerminal can be turned on again by pressing long the central button 3 1 11 4Connecting charger before shutting down AyTerminal If after connecting the charger Turn Off item is selected in main menu the AyTerminal is executing a turning off procedure see the chapter 5 9 While AyTerminal ...

Page 13: ...he inserted SIM card is not locked to the AyTerminal only the following menu will be available Turn OFF Emergency call Figure 4 10 AyTerminal emergency call menu structure Choosing the emergency call item by pressing the accept button it is possible to initiate an emergency call The GSM mobile phone standard includes 112 as emergency number In countries where 112 is not the standard emergency phon...

Page 14: ...d false for three times then the PUK is required see Figure 4 14 The PUK number of digits is fixed to 8 digits After entering the PUK the PIN will be set to 1234 and a message is shown to the user For changing the PIN please see chapter 5 8 7 If the PUK is incorrect then a similar message like for wrong PIN is displayed _ Enter PUK 9 2 1 0 The PIN is set to 1234 Figure 4 14 PUK input screen standa...

Page 15: ...ication Welcome Nickname to Ay AyApplication Welcome AyAppl Nickname to Ay Figure 4 16 AyTerminal boot screen standard and jumbo mode If the AyTerminal is not registered to the AyServer then the default nickname is displayed Default nickname is John Doe ...

Page 16: ...memory when the AyTerminal is turned off normally The AyTerminal is turned off normally if Turn Off item is chosen in main menu These settings can be set locally via the AyTerminal menu or can be received from AyServer synchronized via AyServer interface The modes can have defined an activation time period for which are activated e g For mode Baggage Secure the activation time is activated and set...

Page 17: ... Siren R Siren o Active Start End SMS Voice Call R AyServer o Active Phone number o Active Phone number R Siren Temperature Ego motion Activation delay Threshold o Active Greater than Lower than Threshold o Active o Active Start End SMS Voice Call R AyServer o Active Phone number o Active Phone number R Siren Temperature Activation delay Threshold Greater than Lower than o Active Start End SMS R A...

Page 18: ... number and to listen in If no listen in number is defined the listen in feature can t be used For user configurable values and notifiers refer to the chapter 5 4 3 5 2 4Car Alarm This mode can be used in cars to trigger alarm when the default or the defined ego motion or temperature threshold is reached The Car Alarm mode is used to protect a car against theft or for alarming if the temperature i...

Page 19: ...atically start up Boolean false disabled true enabled false Activation time active flag if mode is enabled to automatically be activated Boolean false disabled true enabled false Activation start time time that activates the mode Time format is 24h hh mm ss 00 00 00 Activation end time time that deactivates the mode Time format is 24h hh mm ss 12 00 00 Table 5 4 AyAlarm settings available for all ...

Page 20: ... 00 00 Siren active flag if siren enabled Boolean false disabled true enabled true SMS notifier active flag if SMS notifier enabled Boolean false disabled true enabled false SMS phone number target phone number for SMS Max 15 characters If not defined SMS is not send out none SMS text Text to be sent via SMS in case of alarm Max 160 characters Alarm Clock Alarm Voice Call notifier active flag if V...

Page 21: ...ed false SMS phone number target phone number for SMS Max 15 characters If not defined SMS is not send out none SMS text Text to be sent via SMS in case of alarm Max 160 characters Baggage Secure Alarm Voice Call notifier active flag if Voice Call notifier enabled Boolean false disabled true enabled false Voice call phone number target phone number for voice call Max 15 characters If not defined v...

Page 22: ...ed in case of Listen In flag if Voice Call notifier enabled Boolean false disabled true enabled false Voice call phone number ignored in case of Listen In target phone number for voice call Max 15 characters If not defined voice call is not started none AyServer active flag if AyServer notifier enabled Boolean false disabled true enabled true Ego motion active flag if ego motion sensor enabled Boo...

Page 23: ...otifier active flag if Voice Call notifier enabled Boolean false disabled true enabled false Voice call phone number target phone number for voice call Max 15 characters If not defined voice call is not started none AyServer active flag if AyServer notifier enabled Boolean false disabled true enabled true Ego motion active flag if ego motion sensor enabled Boolean false disabled true enabled true ...

Page 24: ...x 15 characters If not defined SMS is not send out none SMS text Text to be sent via SMS in case of alarm Max 160 characters Tempera ture Watchdo g Alarm Voice Call notifier active flag if Voice Call notifier enabled Boolean false disabled true enabled false Voice call phone number target phone number for voice call Max 15 characters If not defined voice call is not started none AyServer active fl...

Page 25: ...alse disabled true enabled false SMS phone number target phone number for SMS Max 15 characters If not defined SMS is not send out none SMS text Text to be sent via SMS in case of alarm Max 160 characters Voice Call Alarm AyServer active flag if AyServer notifier enabled Boolean false disabled true enabled true Phone number Phone number that will be dialled Table 5 5 AyAlarm mode specific settings...

Page 26: ...erature watchdog Temperature triggered if temperature sensor activated Siren SMS Voice Call AyServer Siren AyServer Voice call Voice call1 triggered if a voice call is triggered SMS AyServer AyServer Table 5 6 AyAlarm alarms and notifiers 5 3Selecting a mode When turning on the AyTerminal and starting the AyAlarm application and if no mode is set to auto start the main menu see Figure 5 19 is disp...

Page 27: ... the next screen enter next In this main menu screen the left button action is not applicable In the main menu the status icons are displayed No title is available for this screen Switching between the modes is possible without restarting the AyTerminal Note By switching between the AyApplications the AyTerminal must be restarted In the main menu Alarm Clock Baggage Secure Room Monitor Car alarm T...

Page 28: ... to start a mode at least one trigger must be activated The notifiers of a mode can be deactivated In this case before the mode is started a warning message will be displayed 5 4 1Activation Time From the Activation time menu it is possible to enable the activation time This means that the mode will be active only for the defined period of time e g 1 hour between 10 30 and 11 30 In this case when ...

Page 29: ...screen The activation time is applied to the mode as long as the Active check box is checked To disable the activation time uncheck the Active check box in the Activation time menu see Figure 5 21 Activation time menu Note Only one mode can have the activation time active The other modes will have activation time option disabled automatically ...

Page 30: ...tive Figure 5 24 Activation time example 1 2 Start and end time for the Car Alarm mode 11 00 and 15 00 The Active item in the menu is checked which activates the defined activation time activated At 9 00 the mode Car Alarm mode is started Because of the activated activation time the status of Car Alarm is idle At 11 00 the mode becomes active and the status on the display is updated The mode becom...

Page 31: ... of notifiers and each one of them is configurable independently Almost all modes except Voice Call have Siren SMS Voice Call and AyServer as common notifiers When an alarm is triggered activated notifiers are going to be the only ones informed The notifiers are informed in the following sequence 1 The SMS is send to the defined phone number 2 A Voice Call to the defined phone number is establishe...

Page 32: ...hone num OK 0 Figure 5 29 Set phone number screen The available characters are and 0 9 Using the up or down navigation buttons the user can browse the displayed characters or select OK To add a new characters press the Enter OK navigation button after highlighting the desired character To delete the last inserted character use the left navigation button When no character is available in the input ...

Page 33: ...elect OK option and after that press the right button The only validation that is made for the inserted phone number is to be in international format to start with Only one phone number can be defined for SMS notification No acknowledgment tone will be played in previous described screen An established Voice Call can be ended by pressing long on the central button If also voice call and siren are ...

Page 34: ...l and Alarm Clock have no triggers menu instead of Triggers the Phone number menu item is displayed in case of Voice Call and alarm time in case of Alarm Clock Each mode has a different list of triggers see next figures Possible actions in each screen are Navigating through the items using the up or and down buttons Selecting the highlighted item using the OK button Going back to the previous scre...

Page 35: ...tifiers Overview Start Figure 5 37 Settings menu in Voice Call mode Also the overview screen contains different data than for the other modes see 5 4 6 Each trigger can be activated deactivated if it is not the only one defined for that mode Each trigger has its own list of parameters to be set At least one alarm trigger has to be activated when the mode is started It is defined that if there is o...

Page 36: ...5_ Phone num OK 0 Figure 5 40 Set phone number screen The available characters are and 0 9 Using the Up Down navigation buttons the displayed characters can be browsed or OK selected For adding new characters press the right navigation button The selected character will be added For deleting the last inserted character use the left navigation button When no digit is available in the input area pre...

Page 37: ...d to all three axes of the ego motion sensor It is not possible to define a threshold on a combination of different axes e g alarm triggering on a resulting vector of one or two axes The alarm is triggered on ego motion detection if the default or defined threshold value of the ego motion sensor is exceeded The scale for the axis is 0g to 3 6g in 26 steps 0 100 One step is 4 72 curr 10 Ego motion ...

Page 38: ... saving any changes using left button No validations are made when leaving this screen If any problem occurred while saving the noise threshold a message box containing a proper message is displayed The message text is The value could not be saved Please try again Otherwise the previous screen is shown without notification 5 4 4 5Temperature The following menu is provided for setting temperature p...

Page 39: ...et time is applied to all sensors used and activated for the selected mode This option is useful when some time is needed to place the AyTerminal in the desired place e g baggage after activating a mode The activation delay is set in seconds up to 255 seconds 00 01 00 Activation delay OK 01 00 00 Activation d OK Figure 5 48 Set activation delay screen Enter a new Activation delay value To leave th...

Page 40: ...ber will be displayed in brackets also Alarm duration in seconds Example of displayed data in case of Alarm clock menu with Siren and AyServer as notifiers active and with defined time Alarm clock Current 19 54 Timer 21 30 Notifiers Siren AyServer Duration 00 00 30 The text will be wrapped and the user will be able to see screen s content by scrolling it using the up and down navigation buttons In...

Page 41: ...e entered Alarm Alarm triggered Alarm Duration Time passed Deactivation sequence entered Mode activated activation time disabled Or Start time met activation time enabled Figure 5 50 Mode states With the Start option the selected mode of the AyApplication can be started When a mode is started this takes the control over the display and the user input If no alarm trigger is active the mode is not s...

Page 42: ...own in this screen AyTerminal Status bar Mode s name Active Idle status While a mode is started the green LED will blink In these screens only the deactivation code is available If an alarm is triggered a message will be displayed informing the user about the triggered alarm see Figure 5 55 In case that the alarm was triggered because the current value of a sensor exceeded the set threshold the fi...

Page 43: ...lay 09 23 Alarm triggered Mode paused 09 00 09 05 Trigger activation delay Alarm duration 9 23 9 25 Figure 5 56 Mode active and alarm triggered timeline 5 6Deactivating a mode or a triggered alarm To stop the triggered alarm the mode has to be deactivated For deactivating a mode the deactivation code needs to be introduced by pressing the buttons that form the deactivation code After deactivating ...

Page 44: ... AyServer is in progress on display the following screen will be visible Sync In Progress Sync In Progress Figure 5 59 Sync in progress When the synchronization process is finished a message box is displayed informing about the result of the synchronization In case the synchronization failed the message box with the proper message is displayed until right or left button is pressed In case of succe...

Page 45: ...ication supports this AySnapOn It is forbidden to plug or unplug AySnapOn modules to from AyTerminal while AyTerminal is powered on It needs to be powered off first 5 8 3AyTerminal This menu provides the common settings for all AyApplications that has impact on the AyApplication itself Info option allows the user to see FW and AyTerminal useful information See 5 8 3 3 Default settings option allow...

Page 46: ...ngs like time and date are not influenced by this action Setting to default Please wait Setting to default Ple ase wait New settings saved Rebooting New settings saved Rebooting Figure 5 67 AyApplication warning message standard and jumbo mode The settings which are influenced by this reset to default are Setting Default value Application version Current AyApplication version All AySnapOns deactiv...

Page 47: ...he firmware is downloaded on the AyTerminal and a positive acknowledgment is sounded During the download a message screen is shown Before AyTerminal reboots a notifying message box is shown If the left button is pressed in confirmation screen then the firmware update is canceled and negative acknowledgment is sounded New FW available Confirm update Downloading FW 29 FW downloaded successfully from...

Page 48: ...ates or deactivates the connected headset The user has the possibility to set up the volume for alarm siren button clicks voice calls ring tone or to mute all sound feedback The volume can be defined in 5 steps where the first step always means mute 0 20 40 60 80 and 100 By default volume settings for call siren and ring tone are set to 100 and for button to 40 If the user activates the Mute all i...

Page 49: ... is hh mm ss and the date input format is DD MM YYYY European format Clock Time Date Change Time Auto time Change Date Time 23 59 15 Date 31 12 2006 23 59_ Set Time 9 2 1 0 10 12 2006 Set Date OK Figure 5 74 Clock menu normal mode Clock Change Da Change Ti Time Date Time 23 59 15 Date 31 12 2006 23 59_ OK 1 0 Set Time 2006_ OK 1 0 Set Date Figure 5 75 Clock menu jumbo mode 5 8 6Display Display Jum...

Page 50: ...d using the right or left button Code setup Code setup Figure 5 78 Code setup editor standard and jumbo mode The deactivation Code is up right Down left Confirm The deactivation code is up right Figure 5 79 Confirmation request If confirmation is rejected then the new deactivation code is not saved 5 8 7 2PIN control Using this menu item it is possible to activate or deactivate the SIM PIN request...

Page 51: ...user will have to enter PUK number 5 9Turning off the AyTerminal If a mode is activated and has control over the device then first deactivate the mode After deactivating the mode by entering the deactivation code the AyApplication menu will be displayed As soon as 4th key is entered deactivation code is completed After the main menu is displayed select Turn Off item in order to turn off the Ay Mes...

Page 52: ...ion to AyServer 5 10Involved sensors in AyAlarm modes Mode Involved sensors Alarm Clock Baggage Secure acceleration Room Monitor Noise acceleration Car Alarm Temperature acceleration Temperature Watchdog temperature Voice Call Table 5 8 Involved sensors in AyAlarm s modes 5 11Symbols on AyTerminal SYMBOL Description Hold switch ON Phone call in progress Dialing Incoming call Connection established...

Reviews: