manualshive.com logo in svg
background image

11

www.shieldglobal.com

MODEL: SD1133, SD1121

DESCRIPTION

The  SD1133,  SD1121, 

½

”  orifice,  standard  horizontal  sidewall 

sprinkler  is  designed  for  standard  or  recessed  installation.  The 
design provides a crescent-shaped water discharge pattern for 
installation  along  a  wall  or  under  a  beam  or  ceiling.  The  design  
incorporates state-of-the-art, heat responsive, frangible glass 
bulb  design  (standard  or  quick  response)  for  prompt,  precise  
operation. The die cast frame is more streamlined and attractive 
than traditional sand cast frames.

It is cast with a hex-shaped wrench boss to allow easy tightening 
from  many  angles,  reducing  assembly  effort.  This  sprinkler  is 
available  in  various  temperature  ratings  and  finishes  to  meet 
many  design  requirements.  The  recessed  pendent  should  be  
utilized  with  a  recessed  escutcheon  which  provides  up 

” of  

adjustments.

SPRINKLER OPERATION

The operating mechanism is a frangible glass bulb which contains 
a  heat  responsive  liquid.  During  a  fire,  the  ambient  temperature 
rises causing the liquid in the bulb to expand. 

When the ambient temperature reaches the rated temperature of 
the sprinkler, the bulb shatters. As a result, the waterway is cleared 
of all sealing parts and water is discharged towards the deflector. 
The deflector is designed to distribute the water in a pattern that is 
most effective in controlling the fire.

 MAXIMUM COVERAGE

Standard  spray  coverage  is  up  to:  Light  Hazard  =  196  square 
feet(18,2  sq.m);  Ordinary  Hazard  =  100  square  feet(9,3  sq.m)per 
NFPA 13.

TECHNICAL SPECIFICATION

SPRINKLER HEAD

Horizontal Sidewall Sprinkler

Sprinkler Identification 
Number

Standard SD1133 (bulb 
5mm),  Quick Response 
SD1121 (bulb 3mm)

Style

Horizontal Sidewall

K Factor

5.6gpm/psi

½

. (80lpm/bar

½

)

Response Time Index 
(RTI)

Standard 50
Quick Response 30

Nominal Thread Size

½

”NPT(15mm)

Orfice Size

13mm

Max. Working Pressure 175PSI(1200kPa)

Factory Hydrostatic Test  100%@500PSI(3450 kPa)

Min. Operation Pressure 7 PSI(48 kPa)

RATINGS

Sprinkler Temperature

Classification

Norminal Sprinkler

Temperature Rating

N.F.P.A Maximum Ambient

(Ceiling) Temp.(Allowed)

Glass Bulb Color

Ordinary

155ºF/57ºC

100ºF/38ºC

Orange

Ordinary

155ºF/68ºC

100ºF/38ºC

Red

Intermediate**

175ºF/79ºC

150ºF/65ºC

Yellow

Intermediate**

200ºF/93ºC

150ºF/65ºC

Green

High*

286ºF/141ºC

225ºF/107ºC

Blue

Extra High*

360ºF/182ºC

300ºF/149ºC

Mauve

Open*

Open

-

No Bulb

* Non-Approved

** FM Approved only

Отзывы: