HR SERIES

HEAT RECOVERY VENTILATOR (HRV)

INSTALLATION AND WIRING INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS

Models HR100V, HR160H, HR220H

RESIDENTIAL USE ONLY

PP0923

09/2013

Содержание HR100V

Страница 1: ...HR SERIES HEAT RECOVERY VENTILATOR HRV INSTALLATION AND WIRING INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS Models HR100V HR160H HR220H RESIDENTIAL USE ONLY PP0923 09 2013...

Страница 2: ...systems 13 16 Troubleshooting 14 17 Maintenance 15 18 Warranty 15 Before servicing or cleaning the HRV system always remove the power cord from the AC wall outlet To reduce the hazards of electric sh...

Страница 3: ...M L S CFM REQUIRED Master Bedroom x 20 cfm 10 L s With Basement x 20 cfm 10 L s Single Bedroom x 10 cfm 5 L s Living Room x 10 cfm 5 L s Dinning Room x 10 cfm 5 L s Family Room x 10 cfm 5 L s Recreati...

Страница 4: ...t length 35 ft 10 7 m Round plastic diffuser equivalent length 100 ft 30 5 m NOTE Maximum airflow assumes diffuser is in full open position Tee take off equivalent length 50 ft 15 24 m Angle boot equi...

Страница 5: ...less than 10ft 3 m upstream of the return plenum connection to the forced air system Check with your local code or the forced air system s manufacturer The HRV and forced air system must be in continu...

Страница 6: ...the forced air system s manufacturer The HRV and forced air system must be in continuous mode to achieve maximum comfort and to avoid cross contamination NOTE TO INSTALLER Dwellings with multiple for...

Страница 7: ...1 Installation of the wall bracket Secure with two 10 x 11 4 screws figure 6 2 Hang HRV to wall mounting bracket figure 6 3 When completing the procedure make sure that the HRV is leveled figure 6 4 P...

Страница 8: ...sert vinyl duct over the hooks and seal with a Tie wrap figure 7 2 Insert insulation inside the collar figure 8 1 Make a loop in condensate line not be subject to freezing temperatures figure 8 2 Use...

Страница 9: ...of intake air NOTE Outdoor air intake hoods shall be located to avoid contamination from sources such as Exhaust air openings Driveways auto exhaust Combustion appliances Gas meters oil fill pipes Gar...

Страница 10: ...otors and OFF Left Motor Step 3 Once the total cfm needed is determined you can start balancing the HRV Set your fresh air supply by selecting the OFF position on the DuotrolTM Install your magnehelic...

Страница 11: ...Outside LOW Exhaust Air from Home LOW Fresh Air from Outside HIGH Fresh Air to home HIGH Exhaust Air to Outside LOW Exhaust Air from Home Magnehelic gauge Magnehelic gauge BalancingTap Connection LOW...

Страница 12: ...G R R W B G To Casing Screw for Ground Jumper JP 4 2 Relays 1 Relay LVC Version 1 LVC Version 2 Jumper JP 4 R G B W G R B G R R W B G To Casing Screw for Ground Jumper JP 4 2 Relays 1 Relay LVC Versio...

Страница 13: ...h the Alternate Forced Air Wiring LOCATING THE WIRING DIAGRAM NOTE TO INSTALLER Wiring Diagram for the entire line of HRV Models are placed on the back of each Exhaust motor bracket CAUTION Thermostat...

Страница 14: ...all bracket is used for hanging the units Verify that flexible duct connections are use between the HRV and the rigid duct Verify that the motors are operating and are not obscured by any debris Insur...

Страница 15: ...option when returned to our factory transportation prepaid Deterioration or wear by heat abrasive ac tion chemicals improper installation or operation or lack of normal maintenance shall not constitu...

Страница 16: ......