SOC / SOH button
(State of Charge / State of Health)
LED’s
RJ45 Jacks
ON/OFF
button
January 2015
Evolion
®
Installation and operating instructions
1. Safety
Make sure to study and follow all
instructions. Misusing the Evolion
®
may cause it to overheat or ignite.
■
■
Do not short-circuit the power
terminals.
■
■
Do not reverse connect the
power cables.
■
■
Do not disassemble the unit.
■
■
Do not subject the unit to
excessive vibrations or drop the
unit.
■
■
Do not immerse the unit.
■
■
Do not expose the unit to fire or
temperature higher than 100°C
(+212°F). It may cause the
cell safety vent to open which
renders the unit inoperable.
■
■
Use only in Telecom power
systems with a maximum rated
output of 60 V.
■
■
Refer to the Battery Information
Sheet (included) for emergency
response procedures.
2. Important recommendations
If smoke is emitted from a unit, stay
clear of the smoke and evacuate
the area until the smoke clears.
Refer to the Evolion
®
Technical
Manual for functional details.
See Figure 1 for operator interface
features.
3. Unpacking and inspection
When shipped, the Evolion
®
is
packaged in accordance with
UN3480 Class 9 Group 2.
Unpack and make sure all items
were received. Table 1 summarizes
the standard kit.
If items were not received or if
anything is damaged contact your
local Saft representative.
If a long storage is planned (more
than 6 months), check and note the
SOC (State of Charge) according to
In these conditions, the Evolion
®
can
be stored for up to 1 year from the
manufacturing date. Make sure the
unit is switched OFF during storage.
When OFF, the unit is in sleep
mode. In sleep mode, no voltage is
present on the terminals and the
internal electronic consumption is
very low.
NOTE:
The Evolion
®
unit will
periodically and automatically wake-up
to record its state and to initiate cell
balancing if necessary.
IMPORTANT:
If the unit is left
ON, it may over discharge in less
than 3 weeks and render the unit
inoperable. It is mandatory to check
the SOC, every 6 months, while in
a long storage period. See Figure 3
and Table 2.
If the Evolion
®
is stored at a low SOC for
too long, it may eventually over discharge
and render the unit inoperable.
To conduct a maintenance charge:
• Connect according to Section 6
• Make sure the set-point voltage on
the rectifier is 56.0 V
• Charge for a total time according
to the available charge current
(see Table 3)
Figure 1 - Evolion
®
main front access
Figure 3 - Checking SOC (State of Charge)
• For SOC, push and hold for 3 s or less
and observe the LED’s.
Figure 2 - Accessing the unit
4. Storage
Store the battery in its original
packaging and in typical warehouse
conditions. The temperature should be
between 15°C to 30°C (59°F to 86°F).
Table 1 - Standard items in Evolion
®
kit
(771473-XX)
Figure 3 and Table 2. A hole in the
packaging allows you to access the
unit without removing it from the
box. Refer to Figure 2.
This will help to plan the next
refreshing charge.
Keep Evolion
®
in its original
packaging for continued storage or
for transportation.
Part N
o
Qty
771492-XX Evolion
®
1
771285
Fuse, spare
1
780680
Power cable for positive
terminal (1 meter length)
1
772517
(Note 1)
Power cable for negative
terminal (1 meter length)
1
772518
(Note 1)
Communication cable
(1 meter length)
1
773455
RJ45 resistor cap
1
Table 2 - SOC (State of Charge) LED legend
Amps
per unit
Charging
time
Amps
per unit
Charging
time
3
15 h 20 min
12
3 h 50 min
4
11 h 30 min
15
3 h
5
9 h 10 min
18
2 h 30 min
6
7 h 40 min
20
2 h 10 min
8
5 h 40 min
25
1 h 50 min
10
4 h 30 min
CL mode*
see Note 1
Table 3 - Maintenance charge time
-XX: refers to the parameter file variant
Note 1: The cable Part N° varies according to heat
shrink color and cable color
*Note 1: CL = current limit mode, use a charge
current less than IMR to avoid CL mode charge.
See Evolion
®
Technical Manual for more details.
SOC LED
(LED steady for 5 s)
Minimum SOC
≥75%
≥50%
≥25%
<10%
Maximum storage time
(at less than 30ºC)
20 months
13 months
7 months
schedule
maintenance
charge
immediately