background image

PS15v24 v3.2 EN Rev.C.doc 

 

2007-10-23 

       

Power Supply  

Type PS15v24  

v3.2 

P

RODUCT 

D

ESCRIPTION 

 

The PS15v24 is dedicated for electronic equipment  which requires 24VDC buffered 
power supply. Device consist of metal case with compartment for sealed lead-acid  
battery, mains transformer and electronic circuit. PS15v24 may deliver up to 1.5A 
current without any time limit, it utilize DC/DC “switched mode” electronic circuit which 
offer high efficiency (reduced heating of electronic components). PS15v24 employs 
internal current limiting and short circuit protection which make it essentially 
indestructible. The reserve battery is connected to output terminals trough an ultra low-
resistance MOS transistor, such a circuit architecture enables optimum performance 
during AC failure and during dynamic changes of load when excessive current 
consumption is required. PS15v24 charge battery with 

constant current-constant voltage

 

method, this method of charging guaranties relatively quick and safe charging process. 
The initial charging current is factory set to ~300mA, installer should notice that with 
battery connected to PS15v24 the output current will be reduced to 1.2A. Depending on 
battery charging phase the output voltage of PS15v24 may vary between 23.0..27.6V 
level. When battery voltage drops below ~20.0V internal circuit disconnect it from load, 
battery is automatically reconnected when AC supply returns. Battery cut off circuit 
protect battery from deep discharge but the equipment connected to power supply from 
operation below 20.0V level which in many cases might lead to undefined system 
behavior. Battery is protected with 5A fuse which reduce maximum output current 
sourced from battery and electronic circuit against battery reverse connection. PS15v24 
offers two output ports (Z1 and Z2 terminals). The nominal output voltage is factory set 
to 27.6V and should not be changed by user. PS15v24 is equipped with two LEDs, the 
red one (marked as 230VAC) indicates that the AC power supply exists where the second 
one (marked as 24VDC) signals that output voltage is available.  

O

PTIONAL 

A

LARM 

M

ODULE 

PSAM-1 

For more sophisticated installation electronic circuit of PS15v24 can be equipped with 
optional alarm module (PSAM-1). This module can be connected to PS15v24 circuit 
through dedicated connector (CON4) which is located on PS15v24 board. The main 
purpose of PSAM-1 module is to signal an alarm situation of power supply to external 
device or system. The PSAM-1 may operate in 

autonomic

 or 

networked

 mode. When 

set to autonomic mode it offers three transistors outputs which are dedicated to signal 
following situations: 

low battery 

battery failure 

AC lost 

These outputs can be connected to external system or it can trigger warning device (e.g. 
siren, buzzer etc.).  
When PSAM-1 operates in networked mode it must be connected to PR series access 
controller (type PRxx2) through Clock & Data lines. In this mode PSAM-1 module sends 
all messages about power supply condition direct to access controller. When in 

networked 

mode PSAM-1 indicates the same alarm conditions as in standalone mode 

plus additionally delivers data about actual voltage level available on PS’s output. 

Summary of Contents for PS15v24

Page 1: ...t connected to power supply from operation below 20 0V level which in many cases might lead to undefined system behavior Battery is protected with 5A fuse which reduce maximum output current sourced from battery and electronic circuit against battery reverse connection PS15v24 offers two output ports Z1 and Z2 terminals The nominal output voltage is factory set to 27 6V and should not be changed b...

Page 2: ...C frequency 50 60 Hz Nominal Output voltage 27 6 VDC Output voltage may vary from app 23 0 up to 27 6V depending on actual battery charging phase Max output current without battery 1 5A Maximum output current is guaranteed for unlimited time and for entire temp range During battery charging process output current will be reduced to 1200mA Ambient Temperature 0 55 C Max momentary output current wit...

Page 3: ......

Page 4: ......

Page 5: ......

Page 6: ......

Page 7: ... This page intentionally left blank ...

Page 8: ......

Page 9: ...solve the problem They may be reached at 48 55 2670126 or support roger pl Monday through Friday 8 00 A M to 4 00 P M GMT 1 You can also contact the Technical Support Department by fax at 48 55 2720133 If it is determined that you need to return the product the following procedure must be followed to ensure prompt service ROGER Sp j Gosciszewo 59 82 416 Gosciszewo pomorskie Poland Tel 48 55 272 01...

Page 10: ... form in order to avoid damages during transit You are advised to get proof of delivery 12 Some repairs may be chargeable and you will receive formal advice if this is the case 13 If product returned as defective is found not to be defective it will be returned back to the customer at his expenses In that case the customer will be also charged with costs which may arise after triggering the RMA pr...

Page 11: ...Notes No Fault description filled out by the customer Date of repair filled out by the service 1 2 3 4 5 ...

Page 12: ...due to the continual development of new techniques for intruding upon and attacking networks Roger does not warrant that the Product will be free of vulnerability to intrusion or attack This warranty does not cover repair or replacement where normal use has exhausted the life of a part or instrument ALL IMPLIED WARRANTIES AND CONDITIONS OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE LI...

Reviews: