Installation, use and maintenance instructions

Kerosene burner

One stage operation

CODE

MODEL

20157841

RDB 3.2 BT 58/70

GB

Содержание RDB 3.2 BT 58/70

Страница 1: ...20158125 1 10 2018 Installation use and maintenance instructions Kerosene burner One stage operation CODE MODEL 20157841 RDB 3 2 BT 58 70 GB...

Страница 2: ...Original instructions...

Страница 3: ...er equipment 10 4 5 Burner dimensions 10 5 Installation 11 5 1 Notes on safety for the installation 11 5 2 Handling 11 5 3 Preliminary checks 11 5 4 Installer Servicer notes for the use of Gas oil wit...

Страница 4: ...8 8 Combustion head setting 22 8 9 Normal operation burner start up cycle 22 9 Maintenance 23 9 1 Notes on safety for the maintenance 23 9 2 Maintenance programme 23 9 2 1 Maintenance frequency 23 9 2...

Страница 5: ...owing Technical Standard EN 12100 EN 267 and according to the European Directives MD 2006 42 CE Machine Directive LVD 2014 35 EU Low Voltage Directive EMC 2014 30 EU Electromagnetic Compatibility The...

Страница 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Страница 7: ...onents most likely to be subject to wear and tear use of non original components including spare parts kits accessories and optional force majeure The manufacturer furthermore declines any and every r...

Страница 8: ...ilter of 60 Microns protecting the burner from con tamination If an existing oil storage tank is to be used then in addition to the materials checks as detailed above it will be essential that the tan...

Страница 9: ...burner components is not allowed apart from the parts requiring maintenance Only those parts envisaged by the manufacturer can be replaced 3 2 Safety warnings The dimension of the boiler s combustion...

Страница 10: ...nel must not carry out on their own initiative opera tions or interventions that are not within their province Personnel must inform their superiors of every problem or dangerous situation that may ar...

Страница 11: ...w 7 Pressure gauge port 8 Pump 9 Flange 10 Air damper adjustment screw 4 Technical description of the burner Designation Voltage Code RDB 3 2 BT 58 70 1 230V 50Hz 20157841 Model RDB 3 2 BT 58 70 Deliv...

Страница 12: ...Tab C Tab D WARNING The hoses supplied with this burner set for Kerosene use are not suitable for use with Gas oil containing a Bio blend Please refer to the spare part list for the specific hoses sui...

Страница 13: ...e WARNING The handling operations for the burner can be highly dangerous if not carried out with the great est attention keep any unauthorised people at a distance check the integrity and suitableness...

Страница 14: ...at the tank and a secondary 60 micron filter are used to protect the burner pump and nozzle from con tamination The burner hydraulic components and flexible oil lines must be suitable for bio fuel use...

Страница 15: ...ry the insulating gasket holes 5 see Fig 7 Fix the flange 1 Fig 8 to the boiler door 4 using screws 2 and if necessary the nuts 3 interposing the insulating gas ket 5 Prepare a suitable lifting system...

Страница 16: ...Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by foreign matter and where nec essary use suitable screens The inside diameter of the hose must be at lea...

Страница 17: ...ated fuel is returned to the tank If this cannot be avoided make sure that the return pipe is normally below the surface of the fuel level within the storage tank See Fig 14 WARNING The suction plug 1...

Страница 18: ...length of the suction line I D internal diameter of the oil pipes NOTE The Tab E and Tab F show the maximum approximate lengths for the supply line depending on the difference in level length and the...

Страница 19: ...L max length of the suction line I D internal diameter of the oil pipes NOTE The Tab G shows the maximum approximate lengths for the sup ply line depending on the difference in level length and the d...

Страница 20: ...sary to apply in series with L N a timer switch that turns off the burner at least once every twenty four hours Refer to the wiring diagrams The electrical safety of the device is obtained only when i...

Страница 21: ...ase over follow the diagram shown carefully and carry out a good earth connection The electrical wiring carried out by the installer must be in compliance with the rules in force in the country The se...

Страница 22: ...ualified personnel as indicated in this manual and in compliance with the standards and regula tions of the laws in force WARNING Check the correct working of the adjustment com mand and safety device...

Страница 23: ...n chamber with zero depression This regulation is purely indicative Each installation however has its own unpredictable working conditions actual nozzle output positive or negative pressure in the com...

Страница 24: ...lame to the air diffuser disc improves Setting advisable for ignitions at low temperatures Turn in an anticlockwise direction in order to reduce the volume of air entering the combustion chamber and t...

Страница 25: ...f a pump vacuum gauge will assist in this This measure permits the cause of the anomaly to be traced to either the suction line or the pump If the problem lies in the suction line check to make sure t...

Страница 26: ...nents The safety components must be replaced at the end of their life cycle indicated in Tab I The specified life cycles do not refer to the warranty terms indicated in the delivery or payment conditi...

Страница 27: ...heck that safety thermostat limit is not lock out The flame sensor sees false light Eliminate the light The connections in the control box are wrongly inserted Check and connect completely all the plu...

Страница 28: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...