background image

RCI-15                                                                                                                                                         

ZSME300000050 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Summary of Contents for RCI-15

Page 1: ...RCI 15 ZSME300000050 ...

Page 2: ......

Page 3: ...ing and calibration flow chart 18 3 3 Specification calibration 20 3 4 General Calibration 22 3 5 Linearity calibration 23 3 6 Digital calibration 25 3 7 Calibration Error Messages 26 CHAPTER 4 WEIGHT COMPARISON PROCEDURES 27 4 1 Function configuration menu 27 4 2 Check weighing configuration 30 4 3 Batching signal outputs 33 4 4 Normal batching flow chart SQ 01 1 34 4 5 Loss in Weight flow chart ...

Page 4: ... 1 Restore the function parameter back to its default value 59 6 2 2 Clear zero compensation and TARE values 59 6 2 3 Clear batch setting 59 6 2 4 Display zero voltage mV V 59 6 2 5 Clear batch setting 60 6 3 Test mode 61 6 3 1 7 segment display testing 62 6 3 2 Keypad and calibration SW testing 62 6 3 3 Display A D internal value display 62 6 3 4 RS 232 serial loop back testing 62 6 3 5 EEPROM me...

Page 5: ...ble battery Before open the stainless case please make sure the indicator is dry if necessary the liquid should be wiped off The assembling notice should be accurately followed to assure the waterproof performance We also strongly suggest that these procedures should be operated by the technical staff of your supplier ASSEMBLING NOTICE After the desired steps are done screw the case with 12 kgf cm...

Page 6: ...ide 2 To install the optional interface cards it is necessary to disconnect the mains power supply and fit a yellow green earth bonding cable to the rear panel 2 Before turning the power on ensure the supply voltage is within the acceptable range AC100V AC240V 2 The operating ambient temperature range is 10o C 40o C 14 F 104 F 2 The indicator is IP67 waterproof design Only the cables with ψ4 ψ7mm ...

Page 7: ...otalise weight and number of cycles Key in the signal voltage value mV V directly via the keyboard no need to apply any weight to the bottom work to calibrate the weigher Display load cell output voltage mV V for future maintenance Adjustable filter RS232C bi directional and current loop one way serial interface Interface options OP 01 RS422 485 232 serial interface OP 03 16 Bit Analogue current v...

Page 8: ... Weight Net Weight Totalised Weight Number of transactions in the total Indication icons ZERO Zero Indication MD Unstable weight Indication GROSS Gross weight Indication NET Net weight Indication The indicator is supplied with suitable labels to customise the icon displays Refer to FNC 07 FNC 10 for the various options available 2 Weighing Units Weighing Units kg g t lb F2 F F1 Tare Zero G N RCI 1...

Page 9: ...m In the normal mode it accesses the FNC 05 setting When parameter setting it move flashing to left In the normal mode it accesses the FNC 04 setting Confirm enter key 4 Function FNC 03 can be used to selectively disable individual keys 4 Zero operation will be limited by functions CSP 05 and CSP 10 4 Zero operation will be limited by functions CSP 10 and CSP 11 When entering data or reference set...

Page 10: ...n Max Sampling Speed Application Range Load Cell Excitation Voltage Up to 0 12 uV D 1 1 000 000 120 times sec 0 1 mV V 4 0 mV V 5 VDC 5 120mA Up to eight 8 350 Ω load cells can be connected 1 5 Power supply AC 100V 240V 50 60Hz Power consumption is about 10VA 正面 背面 OP 01 OP 03 OP 05 OP 04 Back Front ...

Page 11: ...ame Ground CN6 OFF ON ON 校正開關 開關方向往上 為 ON 亦即進入 校正模式 開關方 向往下為 OFF 亦 即一般使用模式 OFF SW1 CN1 CN5與OP 03 CN2 OP 04 CN3 OP 05 CN3相連接 EXC SHLD SIG SIG EXC SEN SEN J5 1 2 3 CN4 422 1 2 3 J1 J2 J3 J4 1 6 Circuit board description CN OP 03 CN2 OP 04 CN3 and OP 05 CN3 are connected On is the calibration mode status Off is the normal mode status 100V 240V ...

Page 12: ...RCI 15 10 ZSME300000050 1 7 Indicator appearance Front view Up view Back view Side view ...

Page 13: ...o default Turn the power on and Press and keys during self testing sequence See 6 2 1 for details Clear zero point compensation and tare value Turn the power on and press and keys during self testing sequence and then press See 6 2 2 for details Clear setpoint parameter setting Turn the power on and press and keys during self testing sequence and then press two times See 6 2 3 for details Value of...

Page 14: ...of FUNC 4 to 1 in the normal mode or See 4 2 for details 4 Key actions in function set up mode Increases the number of the flashing digit Decreases the number of the flashing digit Moves the flashing digit one space to the left Moves the flashing digit one space to the right Saves the configuration Quits set up mode Escape F2 F ƒ G N F1 F ƒ ...

Page 15: ...input interface External parallel trip output interface 4 Function Setting Procedures With weight displayed press and hold the key Then press See 5 1 for details See 5 2 for details See 5 3 for details See 5 1 for details See Function Setting 2 2 for details See Chapter 4 for details See 5 4 for details See 5 4 for details Set Point Procedure F1 F1 F1 F1 F1 F1 F1 F1 F1 G N G N G N G N G N G N G N ...

Page 16: ... digit Move flashing point left Move flashing point right Store data in memory Exit Escape Function Parameter code Digital Filter I Digital Filter II Lock keypad function F function setting F1 function setting F2 function setting Front panel indication S1 setting status Front panel indication S2 setting status Front panel indication S3 setting status Front panel indication S4 setting status Terms ...

Page 17: ...ble FNC 03 Key Locked 000000 111111 1 Close lock enable 0 0 0 0 0 0 Tare G N Zero F2 F1 F 000000 FNC 04 F function setting 0 FNC 05 F1 function setting 1 FNC 06 F2 function setting Parameter Description 0 Setpoint parameter setting 1 Tare reset 2 Manually output of serial parallel print 3 Start load 4 Stop load 5 Start comparison 6 Unload command 7 Totalise weight and counts command 8 Clear totali...

Page 18: ...0 Accu V 1 Accu C 2 SP1 3 SP2 4 SP3 5 Hi 6 OK 7 Lo 8 Under 9 Over 10 Unloading 11 Running 12 Hold 0 0 5 d 1 10 d 2 20 d 3 40 d 4 60 d 5 80 d 6 100 d 7 150 d 8 200 d FNC 11 Return to zero band 9 250 d 0 0 Hold 1 Peak hold positive 2 Peak hold negative FNC 12 Hold 3 Peak hold absolute value 0 0 No limitation 1 20 times sec 2 10 times sec 3 5 times sec FNC 13 Rate for display rewrite 4 1 time sec 0 4...

Page 19: ...050 SEN SHLD SIG EXC SIG SEN EXC SEN SEN EXC EXC Shield SIG SIG CHAPTER 3 CALIBRATION 3 1 Load cell connection 2 When using a 6 wire cable to connect the load cell the SEN and SEN can be left unconnected see below diagram ...

Page 20: ...on Calibration General Calibration Linearity Calibration Digital Calibration Calibration Switch ON Zero Point Voltage Calibration Span Voltage Calibration Select 1 Point for Weight Calibration 1P 5P Calibration Switch OFF Calibration Completed Zero point Calibration Weight Calibration ...

Page 21: ...g the General calibration see 3 4 for details Entering the specification calibration see 3 3 for details 2 Calibration process 4 Before the Linearity Calibration the General Calibration should be completed Spec Calibration General Calibration Linearity Calibration Digital calibration Calibration Switch set to ON G N G N G N F1 F1 F1 F1 G N ...

Page 22: ...t flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape Calibration parameter code Unit Decimal Point Min Division Max Capacity Zero Range Time of Zero tracking Range of Zero tracking Investigate period of unstable Investigate range of unstable Function Zero and Tare when the weight is unstable Tare function availability when gr...

Page 23: ... set to 0 0 the zero tracking function is disabled 1 0 CSP 07 Range of zero tracking 0 9 Range of zero tracking setting value D D min division Range and time of zero tracking should be use at the same time If the range is set to 0 the zero tracking function is disabled 2 CSP 08 Investigate time in stable 0 0 5 0 sec Investigate time and range should be use at the same time If the time is set to 0 ...

Page 24: ...e hopper After the weight is stable Press the key Five sec later Calibration complete set calibration switch to the OFF position 4 Zero calibration only press key to escape after the display shows 4 Span calibration only press key entering directly to span calibration after the display shows 4 Please refer to error message during calibration of the display show X Increment flashing digit Decrement...

Page 25: ...e 4 Please refer to the error message list if the display shows X Increment flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape Use to select one of calibration points 1P 5P no setting value with setting value Press key Press key Key in the correct weight value Press key Press key Finish the 1st calibration point setting Eithe...

Page 26: ...t Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape Either continue to display the second point value or press key to exit the linearity calibration mode Use to select one of calibration points 1P 5P no setting value with setting value Display the setting value of this calibration point Either continue to clear the second point value or pr...

Page 27: ...e refer to the error message list if the display shows X Example Zero Voltage 0 00036 mV V incl dead load Span Voltage 2 90000 mV V Span Capacity 30000 Increment flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape Zero voltage calibration Weight mV V Zero voltage ZERO Span voltage SPAN CAP Capacity Span voltage calibration Met...

Page 28: ...output voltage 0 1mV V or 4mV V Weight value previous weight value Actual measured weight value previous weight value Setting value 0 mV V value entered measuring range mV V value entered is too small SPAN Zero 0 mV V Displayed resolution is less than 0 12µV division ...

Page 29: ...leted value in Zero band Hi OK Lo action mode Auto totalise weight counts The parameter source for weight comparison Weight comparison delay time Tare auto Discharge auto CHAPTER 4 WEIGHT COMPARISON PROCEDURES 4 1 Function configuration menu Item code Press the key Select the desired menu code Press the key Display shows the existing parameter code Input a new code as required Press the key Contin...

Page 30: ...5 sec Output the batch finished signal after this delay time 0 5 0 Wait until the weight is stabilized SQ 05 Batch finish Condition 1 No need to wait until the weight has stabilized 0 SQ 06 Batch finish Output signal time 0 0 25 5 sec Batch finished output signal time If set to 0 the output signal will be off until the next batch start 1 0 Batch finish signal ON SQ 04 OFF SQ 06 Batch finish SQ 07 ...

Page 31: ...Batching counts 0 255 times Number of batch runs 0 one batch only 0 0 No setting SQ 15 Set the zero band in to final weighing value 1 Setting 0 0 Comparison anytime 1 To compare at batch finish 2 To compare at external input signal 3 To compare at batching finish and external input signal SQ 16 Hi OK Lo 4 Comparison auto 0 0 Disabled SQ 17 Auto totalise weight counts 1 Enabled 0 0 Key in directly ...

Page 32: ...t new value as required Press Display shows the existing Free Fall value setting Input new value as required Press Display shows the existing Over value setting Input new value as required Press Increment flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape Display shows the existing Under value setting Input new value as requi...

Page 33: ...equired Press Display shows the existing Lo value setting Input new value as required Press Display shows the existing Zero Band setting Input new value as required Press Increment flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape F ƒ G N F1 F ƒ F2 ...

Page 34: ...o value setting Input new value as required Press Display shows the existing Zero Band setting Input new value as required Press Display show the existing Peak Ready value setting Input new value as required Press Increment flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit Escape F ƒ G N F1 F ƒ F2 ...

Page 35: ...Final SP1 SP2 Net Final SP2 SP3 Net Final Free Fall in flight Under Net Final Under Over Net Final Over Zero Band Gross Zero Band 2 Loss in weight signal outputs Signal Output condition SP1 Gross SP1 SP2 Net Final SP2 SP3 Net Final Free Fall in flight Under Net Final Under Over Net Final Over Zero Band Gross Zero Band ...

Page 36: ... hing finis h S Q 4 S e tting Delay time arrived after batching finish output signal N Batch finish signal output Batch finish output signal time SQ6 Batch finish condition stabilized or not SQ5 Weight stabilized or not SQ5 1 instable SQ5 0 Stabilized N Y Batch finish output signal reach time Closed batch finish signal SQ6 0 SQ6 1 25 5 N Y over Y SP1 SP2 SP3 Receiving bin Weighing hopper Supplying...

Page 37: ...gate open Weight of supplying bin reach to zero range SQ15 1 Setting N Y Y Set the zero band in to final weighing value SQ15 GROSS SP1 Supplying hopper gate closed TARE SP1 output Y N Batch finish signal output Batch finish output signal time start SQ6 Batch finish condition stabilized or not SQ5 Weight stabilized or not SQ5 1 instable SQ5 0 stabilized N Y Batch finish output signal reach time Clo...

Page 38: ...JUDGING Signal input delay time arrived JUDGING Signal input delay tim e start SQ19 N Y N Y Y Y N ET transmit range FU N10 N W eight is stabilized or not N Y Y N ET LO LO NET HIG H NET HIGH LO UND ER output OK FINAL output HI OVER output Y Y Y N N Y NET LO LO NET HIGH N ET HIG H LO UNDER output OK FINAL output HI OVER output Y Y Y N N Y N ET LO LO NET H IG H NET HIGH LO U NDER output OK FINAL outp...

Page 39: ...gate arrived To reach times of supplementary loading B N N Y Y N Y Y N B Reach batch finish output signal delay time Batch finish output signal Batch finish output signal time start SQ6 Batch finish condition stabilized or not SQ5 Weight stabilized SQ5 1 not stabilized SQ5 0 stabilized N Y Doscharge setting auto SQ21 To activate discharge on delay time SQ10 Discharge delay time arrived Discharge s...

Page 40: ...R To activate supplementar y loading SQ7 SQ7 1 255 To activate supplem entary loading Supplementar y loading gate open time start SQ 8 Supplementary loading gate open time arrived NET UNDER SP3 signal output O N A SP3 signal output OFF Supplementar y gate closed tim e start SQ9 Supplementary loading gate closed time arrived Times of supplementary loading arrived B N N Y Y N Y Y N B SQ7 0 not suppl...

Page 41: ...ak hold mode FNC 12 1 2 Peak hold mode with four different states FNC 12 1 2 3 4 positive peak weight 1 negative peak weight absolute value of peak weight 3 and positive peak weight 2 The peak holds of absolute value and positive peak weight 2 both have no peak ready signal output ...

Page 42: ... K R E A D Y o u tp u t O N Y Y N N N Y H O L D sig n a l in p u t D i s p l a y k e e p s h o w m a x o f a b s o l u te w e i g h t N Y N E T L O L O N E T H IG H N E T H IG H L O U N D E R o u tp u t O K F IN A L o u tp u t H I O V E R o u tp u t Y Y Y N N F N C 1 1 0 D i s p la y k e e p s h o w w e i g h t v a l u e i n H O L D s i g n a l i n p u t F N C 1 1 1 D i s p l a y k e e p s h o w m...

Page 43: ...he comparison 4 10 Totalizing ACCU Auto Transmit With automatic totalising active SQ 17 or RS232 RS485 or BCD output set to auto transmit 1 SQ 01 1 2 4 or 5 batch loss in weight a When the weight reaches the Final weight and the batch finish signal is ON the net weight will be added to the totaliser and number of additions is incremented The RS232 RS485 and BCD outputs transmit data b When the net...

Page 44: ...00050 CN4 J1 J4 RS232 422 short 12 RS422 short 23 RS232 J5 4Wire Wire RS short 12 4Wire short 23 2Wire 422 1 2 3 J1 J2 J3 J4 J5 1 2 3 CHAPTER 5 INTERFACE 5 1 Serial input output interface OP 01 2 Pin location and setting ...

Page 45: ... 02 RCI 15 RS2 7 10 TRM 5 SG 6 RDB 4 RDA 3 SDB 2 SDA 1 TRM 5 SG 6 RDB 4 RDA 3 SDB 2 SDA 1 HOST COMPUTER HOST COMPUTER 2 Connection type RS 422 RS 485 Notice l The maximum connection is 10 sets of RCI 15 l When the Host computer has the built in terminal resist it is not necessary to have the external one l On the last set of RCI 15 the TRM RDB can be connected depends on the situation l When the h...

Page 46: ...he existing Display shows the existing parameter code Input parameter code Input a new code as required a new code as required Press the key Press the key Continue to the next function setting Continue to the next function setting or or press to escape or press to escape Increment flashing digit Decrement flashing digit Move flashing point left Move flashing point right Store data in memory Exit E...

Page 47: ...it command mode RS1 02 RS2 02 Transmit mode 3 Command mode 0 0 600 1 1200 2 2400 3 4800 4 9600 RS1 03 RS2 03 Transmit speed 5 19200 2 0 N 8 1 No parity 8 data bits 1 Stop bit 1 O 7 1 Odd parity 7 data bits 1 Stop bit RS1 04 RS2 04 Parity Bit length Stop Bit 2 E 7 1 Even parity 7 data bits 1 Stop bit 2 0 Open 1 1 time sec 2 2 time sec 3 5 time sec RS1 05 RS2 05 Transmit times 4 10 time sec 0 RS1 06...

Page 48: ...SP SP SP SP SP SP SP SP SP Accu Wt Over T W SP SP SP SP SP SP SP SP SP SP SP SP Accu Count T N 0 1 2 3 4 5 6 7 8 9 SP SP Accu Count over T N SP SP SP SP SP SP SP SP SP SP SP SP CR LF 3 Sample Format Gross Net or as display 1 2 3 4 5 6 Over load positive SP SP SP SP SP SP Over load negative SP SP SP SP SP SP CR LF 4 Setpoint 1 Simple Format Gross Net or as display 1 2 3 4 5 6 CR LF bit 7 bit 6 bit ...

Page 49: ...T 53H 54H Weight stable Status 1 US 55H 53H Weight unstable GS 47H 53H Gross Weight NT 45H 54H Net Weight TR 54H 52H TARE TW 54H 57H Totalised Weight Status 2 TN 54H 4EH Number of transactions in total 0 9 30H 39H Figure of weight 2BH 2DH Symbol or of weight Space 20H Over load Data of Weight 2EH Decimal Space Space 20H 20H None kg 6BH 67H kg Space t 20H 74H tonne Units lb 6CH 62H lb Ending code C...

Page 50: ... Command Format B Host Command CR LF Slave Data CR LF RW Read current weight RT Read TARE RG Read Gross Weight RN Read Net weight RB Read current display of wt simple RH Read Gross simple RI Read Net simple RJ Read comparison situation current display of weight simple RK Read comparison situation Gross simple RL Read comparison situation Net simple RO Read comparison situation 2 RF Read prior comp...

Page 51: ...Under LO Write LO ZB Write Zero Band HI Write HI PR Write Peak value OV Write Over 2 Error messages E1 Format command fault E2 Setting parameters over range E3 Command not recognised 2 Indicator poling address If the indicator has an address configured in RS1 2 07 it will only respond to messages prefixed with its address For example The indicator poling address is set to 02 it would send the weig...

Page 52: ...tment Current voltage Span adjustment to increase value turn clockwise decrease value turn anticlockwise C ZERO adjustment Current voltage Zero adjustment to increase value turn clockwise decrease value turn anticlockwise 2 Analogue output interface specification Resolution 16 bits Current output 0 20mA 0 550 Ω load Voltage output 0 10V CN2於連接至電路 板之插座CN5 CN1 FG I_Output V_Output GND SPAN ADJ ZERO ...

Page 53: ... AnL 03 Weight in Lo 000000 999999 0 AnL 04 Current Voltage in Lo 0 0 mA 20 0 mA or 0 0 V 10 0 V When the weight reaches the value of that in AnL 03 the current voltage output is changed to that configured in AnL 04 4 0 AnL 05 Weight in Hi 000000 999999 300000 AnL 06 Current Voltage in Hi 0 0 mA 20 0 mA or 0 0 V 10 0 V When the weight reaches the value of that in AnL 05 the current voltage output ...

Page 54: ...th a low temperature coefficient and a power rating above 0 2 W be used 2 Avoid short circuits between the positive and negative analogue output terminals as the interface this may cause damage 3 It is recommended that a screened cable is used to connect the analogue output to its load and that the screen is earthed to avoid noise interference ...

Page 55: ...300000050 5 3 External parallel input output interface OP 04 OP 05 2 OP 04 2 OP 05 CN3於連接至電路 板之插座CN5 CN2 CN3 on CN5 socket connected with current PCB CN3於連接至電路 板之插座CN5 CN2 CN3 on CN5 socket connected with current PCB ...

Page 56: ...nput 2 2 IN 03 Input 3 3 IN 04 Input 4 4 IN 05 Input 5 5 IN 06 Input 6 6 IN 07 Input 7 7 IN 08 Input 8 0 None 1 Zero 2 Tare 3 Tare reset 4 Start batching 5 Stop batching 6 Discharge Command 7 Hold 8 Hold display I O reset 9 Totalise Accu Command 10 Clear totaliser Accu 11 Clear previous total Accu Value 12 Start to compare 13 Serial and parallel printer manual output 14 Net Gross 8 Increment flash...

Page 57: ...ut 4 4 OUT 05 Output 5 5 OUT 06 Output 6 6 OUT 07 Output 7 7 OUT 08 Output 8 0 None 1 Zero band 2 SP1 3 SP2 4 SP3 5 Batching completed 6 Discharge 7 Peak ready 8 Stable 9 Internal batching process running 10 Under 11 Over 12 Hi 13 OK 14 Lo 8 OUT 09 The output logic of OUT 04 OUT 01 0000 à positive logic 1111 à negative logic 0000 OUT 10 The output logic of OUT 08 OUT 05 0000 à positive logic 1111 ...

Page 58: ...al Open OFF Short ON 4 Warning Don t use external power AC or DC to connect to the input terminals Output inside Vs Spark killer Photo coupler COM2 Vex OUT 1 8 Vex Vex 30V max Load Varistor Load Diode RCI 15 AC IN DC IN Relay 30mA max Input COM 1 IN 1 IN 8 RCI 15 inside Ic 5mA VS ...

Page 59: ...wheel switches or a PLC to input various parameters depending on the configuration of SQ 01 The input variables are Final 5 digits SP2 4 digits Free Fall 3 digits or Hi 6 digits Lo 6 digits When using external thumbwheel Switches SQ 18 should be set to 1 Connection data SQ 01 1 2 4 or 5 SQ 01 3 or 6 Hi Lo 8 4 1 2 5 C 1 4 8 4 2 C 3 8 4 1 2 C 2 8 4 1 2 C 1 8 4 1 2 C 1 36 2 18 4 37 8 19 7 10 10 10 10...

Page 60: ...and return the calibration SW to OFF 3 2 To abort set the calibration SW to OFF directly 6 2 Maintenance function parameters Power on the machine Press keys while the display counts back to zero Restore all parameters to their default factory values See for details 6 2 1 Clear zero compensation and tare value See for details 6 2 2 Clear batch setting value See for details 6 2 3 Display zero voltag...

Page 61: ...isplay shows flashing 4 Confirm abort 4 1 To confirm press the key don t release it The display will then show 4 2 To abort press the key or switch the power off 6 2 3 Clear batch setting 1 During the indicator count back to zero press 2 The display shows press the F1 key to display 3 Press key the display shows flashing 4 Confirm abort 4 1 To confirm press the key don t release it The display wil...

Page 62: ...0 6 2 5 Clear batch setting 1 During the indicator count back to zero press 2 The display shows press the F1 key to display 3 Press the key the display shows the span voltage mV V e g 4 Press key or switch the power off F ƒ ...

Page 63: ...ails 6 3 2 Display A D internal value display See for details 6 3 3 RS 232 serial loop back testing See for details 6 3 4 EEPROM memory testing See for details 6 3 5 Production testing use only OP 01 interface testing If OP 03 display If OP 04 display If OP 05 display See for details 6 3 6 If install interface testing continuous G N F1 G N F1 G N F1 G N F1 G N F1 G N F1 G N F1 ...

Page 64: ... 2 Terminal pin1 and pin 3 pin 2 and pin 4 must be separately connected together at the rear of the indicator If display shows the interface is working normally If display shows the interface is not working correctly 6 3 5 EEPROM memory testing If the display shows it means normal If the display shows the memory is not working correctly 6 3 6 Option interface card testing 2 OP 01 RS232 RS422 RS485...

Page 65: ...r to measure the voltage between pin 2 pin 3 of the interface Use the keys to select the output voltage level desired 1V 5V 10V 2 OP 04 Control I O 4I 4O testing 1 2 Press key to switch to the control input value 2 OP 05 Control I O 8I 8O testing Input 1 4 signal ON OFF related to display Press key in sequence represents Output 1 8 4 Warning To avoid damage to components use only a voltmeter Press...

Page 66: ... ZSME300000050 APPENDIX I Description of 7 segment characters Digit 7 segments letter Alphabet 7 segments letter Alphabet 7 segments letter 0 A N 1 B O 2 C P 3 D Q 4 E R 5 F S 6 G T 7 H U 8 I V 9 J W K X L Y M Z ...

Page 67: ...same time If the time is set to 0 0 the zero tracking function is disabled 1 0 CSP 07 Range of zero tracking 0 9 Range of zero tracking setting value D D min division Range and time of zero tracking should be use at the same time If the range is set to 0 the zero tracking function is disabled 2 CSP 08 Investigate time in stable 0 0 5 0 sec Investigate time and range should be use at the same time ...

Page 68: ...ble FNC 03 Key Locked 000000 111111 1 Close lock enable 0 0 0 0 0 0 Tare G N Zero F2 F1 F 000000 FNC 04 F function setting 1 FNC 05 F1 function setting 0 FNC 06 F2 function setting Parameter Description 0 Setpoint parameter setting 1 Tare reset 2 Manually output of serial parallel print 3 Start load 4 Stop load 5 Start comparison 6 Unload command 7 Totalise weight and counts command 8 Clear totali...

Page 69: ...ation S4 setting Parameter Description 0 Accu V 1 Accu C 2 SP1 3 SP2 4 SP3 5 Hi 6 OK 7 Lo 8 Under 9 Over 10 Unloading 11 Running 12 Hold 0 0 5 d 1 10 d 2 20 d 3 40 d 4 60 d 5 80 d 6 100 d 7 150 d 8 200 d FNC 11 Return to zero band 9 250 d 0 0 Hold 1 Peak hold positive 2 Peak hold negative FNC 12 Hold 3 Peak hold absolute value 0 0 No limitation 1 20 times sec 2 10 times sec 3 5 times sec FNC 13 Ra...

Page 70: ... mode 2 Manual transmit command mode RS1 02 RS2 02 Transmit mode 3 Command mode 0 0 600 1 1200 2 2400 3 4800 4 9600 RS1 03 RS2 03 Transmit speed 5 19200 2 0 N 8 1 No parity 8 data bits 1 Stop bit 1 O 7 1 Odd parity 7 data bits 1 Stop bit RS1 04 RS2 04 Parity Bit length Stop Bit 2 E 7 1 Even parity 7 data bits 1 Stop bit 2 0 Open 1 1 time sec 2 2 times sec 3 5 times sec RS1 05 RS2 05 Transmit times...

Page 71: ...03 Weight in Lo 000000 999999 0 AnL 04 Current Voltage in Lo 0 0 mA 20 0 mA or 0 0 V 10 0 V When the weight reaches the value of that in AnL 03 the current voltage output is changed to that configured in AnL 04 4 0 AnL 05 Weight in Hi 000000 999999 300000 AnL 06 Current Voltage in Hi 0 0 mA 20 0 mA or 0 0 V 10 0 V When the weight reaches the value of that in AnL 05 the current voltage output is ch...

Page 72: ...s total Accu Value 12 Start to compare 13 Serial and parallel printer manual output 14 Net Gross 8 Setting value Item Function Parameter Description Default OUT 01 Output 1 1 OUT 02 Output 2 2 OUT 03 Output 3 3 OUT 04 Output 4 4 OUT 05 Output 5 5 OUT 06 Output 6 6 OUT 07 Output 7 7 OUT 08 Output 8 0 None 1 Zero band 2 SP1 3 SP2 4 SP3 5 Batching completed 6 Discharge 7 Peak ready 8 Stable 9 Interna...

Page 73: ... batch finished signal after this delay time 0 5 0 Wait until the weight is stabilized SQ 05 Batch finish Condition 1 No need to wait until the weight has stabilized 0 SQ 06 Batch finish Output signal time 0 0 25 5 sec Batch finished output signal time If set to 0 the output signal will be off until the next batch start 1 0 Batch finish signal ON SQ 04 OFF SQ 06 Batch finish SQ 07 Number of Times ...

Page 74: ...is ON 1 0 SQ 14 Batching counts 0 255 times Number of batch runs 0 one batch only 0 0 No setting SQ 15 Set the zero band in to final weighing value 1 Setting 0 0 Comparison anytime 1 To compare at batch finish 2 To compare at external input signal 3 To compare at batching finish and external input signal SQ 16 Hi OK Lo 4 Comparison auto 0 0 Disabled SQ 17 Auto accu weight counts 1 Enabled 0 0 Key ...

Reviews: