background image

 

 

 

 

 

 

AC MOTOR DRIVE 

Operation manual 

 
 
 
 

 
 
 
 
 

 
 
 

RM6F2 series 

 

Summary of Contents for RM6F2 Series

Page 1: ...AC MOTOR DRIVE Operation manual RM6F2 series...

Page 2: ...Quality Satisfaction Improvement Innovation http www rhymebus com tw 2020 11 16 Revised XB200179...

Page 3: ...poses please do read and follow specific instructions contained in this manual before using the product The manual shall be placed on the top of the machine and all the setup parameters and reference...

Page 4: ...execute the tasks Although the mark may indicate minor damages serious damages or injuries may be possibly incurred if the caution is not under user s attention Installation CAUTION 1 The installation...

Page 5: ...ll the thermal relay between the individual motor and the drive when using one drive to propel several motors j Do Not connect power factor leading capacitor surge absorber or non three phase motor to...

Page 6: ...rations d The drive can produce high frequency outputs Before adjusting the frequency please check the specifications of motor carefully to prevent the motor from unexpected damages e If any of the pr...

Page 7: ...ve for any paint chipped off smearing deformation of shape etc 3 Check up the nameplate as below example by RM6F2 2001B3 of the drive to verify the product descriptions with the order specification Rh...

Page 8: ...plicable motor HP kW 0 5 0 4 1 0 75 2 1 5 3 2 2 Rated output capability kVA 1 0 1 6 2 9 3 8 Rated output current A 2 5 4 2 7 5 10 Rated output voltage V Three phase 200 240V Range of output frequency...

Page 9: ...an cooling Applicable safety standards Protective structure IP20 Weight Mass kg 1 1 1 2 1 2 2 5 1 This model is batch production 1 2 3 Three Phase 200V Series Model name RM6F2 B3 20P5 2001 21P5 2002 M...

Page 10: ...s kg 1 2 2 5 2 5 1 This model is batch production 1 2 4 Three Phase 400V Series Model name RM6F2 B3 4001 4002 4003 4005 1 4007 1 Maximum applicable motor HP kW 1 0 75 2 1 5 3 2 2 5 3 7 7 5 5 5 Rated o...

Page 11: ...Braking Resistor option Induction Motor Multi function Input 5 Multi function Input 6 Shielded Wire Twisted Pair Shielded Wire JP1 I V Selection I position AI GND terminal is inputted with the curren...

Page 12: ...s Motor U T1 V T2 W T3 Drive outputs to motor terminals The terminals output three phase variable frequency and voltage to motor Power and Brake P N Dynamic braking unit connecting terminal The termin...

Page 13: ...P2 10P5 1001 20P2 20P5 2001 2002 M3 5 8 5 9 8 M4 15 6 18 RM6F2 _______B1 1002 1003 2003 M4 15 6 18 M4 15 6 18 2 200 400V Three phase AC power Model number Screw size of main circuit terminal except fo...

Page 14: ...2V position Output DC 12V Maximum supplied current is 20mA Select 24V position while connecting to the pressure transducer GND Common terminal for analog input control Common terminal for control powe...

Page 15: ...A 2 10V or DC 0 20mA 0 10V The function is set by F126 Output Terminal FM Note3 Analog signal output terminal Output signal selection JP3 FMI position current signal JP3 FMV position voltage signal In...

Page 16: ...Differential input of RS 485 Note 1 Modbus RS 485 communication only uses pin1 2 2 Communication transmission terminal DX 3 Power terminal of KP 15V Only for KP linking 4 Auto detect terminal of KP O...

Page 17: ...arameter setting Drive 0 Setting Description Content Func F015 Selection of Parallel Control Mode 1 Single pump F016 Set Drive s No in Parallel Control 0 Drive 0 F126 Select the range of AI 0 4 20mA J...

Page 18: ...nge of AI 0 4 20mA JP1 JP4 Selection JP1 Input signal type selection of AI Voltage Current I position JP4 Seclect output Voltage V 24V output DC 24V 12V output DC 12V 24V Terminal Resistor Switch DSW1...

Page 19: ...F016 Set Drive s No for Parallel Cntrol 0 Drive F126 Select the range of AI 0 4 20mA JP1 JP4 Selection JP1 Input signal type selection of AI Voltage Current I position JP4 Seclect output Voltage V 24...

Page 20: ...JP4 Selection JP1 Input signal type selection of AI Voltage Current I position JP4 Seclect output Voltage V 24V output DC 24V 12V output DC 12V 24V Terminal Resistor Switch DSW1 ON position Auxiliary...

Page 21: ...indicator ON Pressure transducer is at disconnected or cut off status OFF Pressure transducer is at normal status Priority operation parallel multiple drive indicator ON Indicate the drive which is pr...

Page 22: ...r mode FUNC DATA Function Data key 1 Enter the parameter setting mode 2 Back to the function setting mode 3 Switch monitor mode Up key Change functions and parameters Down key ON Start key Start the d...

Page 23: ...nute The operation steps are shown as below table by default setting Operation Steps Display 1 Start the drive and enter the monitor mode RUN CRG MAIN SV PV 2 Press PROG key and enter the function set...

Page 24: ...FUNC DATA FUNC DATA FUNC DATA FUNC DATA FUNC DATA FUNC DATA RUN CRG MAIN SV PV RUN CRG MAIN SV PV RUN CRG MAIN SV PV RUN CRG MAIN SV PV RUN CRG MAIN SV PV RUN CRG MAIN SV PV RUN CRG MAIN SV PV FUNC D...

Page 25: ...re is shown as below figure RUN CRG MAIN SV PV X1 X6 X3 Ta1 Tb1 X2 Drive temperature Left Display Right Display X4 X5 Right display The temperature of heat sink Left display Horizontal line of seven s...

Page 26: ...DATA key to enter parameter setting mode RUN CRG MAIN SV PV 3 Press key to decrease the value of F001 from 3 default value to 2 RUN CRG MAIN SV PV 4 Press FUN DATA key and return to function setting m...

Page 27: ...and then display the copy process on keypad RUN CRG MAIN SV PV 5 After completing the copy the keypad will display message and automatically back to function setting mode RUN CRG MAIN SV PV a 2 Parame...

Page 28: ...to select and then press FUNC DATA key to copy the parameters RUN CRG MAIN SV PV 5 After completing the copy the keypad will display message and automatically back to function setting mode RUN CRG MA...

Page 29: ...DATA key to enter parameter setting mode RUN CRG MAIN SV PV 2 Press key to select parameter and then press FUN DATA key to execute the saving RUN CRG MAIN SV PV 3 After completing the saving the keyp...

Page 30: ...004 Setting Value SV Change Selection Under F002 1 0 In the monitor mode setting value cannot be changed 1 In the monitor mode setting value can be changeable 0 1 1 F005 Selection of Setting Value Aut...

Page 31: ...al number for every drive 0 is the host drive to command others 0 7 0 F017 Maximum Output Frequency The maximum output frequency of drive 0 1 400 0 0 1Hz 60 0 F018 Reference Frequency of Accel Decel T...

Page 32: ...ec 0 0 F030 V F Pattern Selection 0 Linear 1 Square curve 2 1 7th power curve 3 1 5th power curve 0 3 1 F031 Primary Speed Jog command Multi speed level 3 command Multi speed level 2 command Multi spe...

Page 33: ...atus of drive before power off 0 Enable F001 2 3 4 1 Disable 0 1 0 F052 Multi function Input Terminal X1 0 Manual control command 1 of M mode F015 4 1 Jog command 2 Switch to secondary accel decel tim...

Page 34: ...load condition adjust the output voltage of the V F Pattern 0 0 Off 0 0 25 5 0 1 1 0 F065 System Overload Detection OLO 0 Disable 1 Enable OLO 0 1 0 F066 System Overload Detecting Selection 0 Detectio...

Page 35: ...after drive stopped 0 0 20 0 0 1 sec 0 2 F077 Time of DC Braking before Start Set the time for DC braking before drive starts 0 0 20 0 0 1 sec 0 0 F078 Operation Selection at Instantane ous Power Fai...

Page 36: ...frequency will trace downward 0 200 of drive rated current 1 150 F089 Delay Time for Speed Tracing Set the output delay time before the speed tracing 0 0 5 0 0 1 sec 0 5 F090 The V F Pattern of Speed...

Page 37: ...3 0 F106 Integration Time I Set the integration time for deviation adjustment 0 0 I control disabled 0 0 25 0 0 1 sec 1 2 F107 Derivative Time D Set the derivative time for deviation adjustment 0 00 D...

Page 38: ...19 and F120 to detect if a pump suffers from water shortage 0 250 1sec 60 F122 Drive Shutdown Time for Water Shortage Drive will automatically restart after the time setting when a pump suffers from w...

Page 39: ...tting the number of drives standing by 0 3 0 F136 Noise Prevention 0 Disable 1 Enable 0 1 0 F137 Delay Time at Pump Exchange Operation The delay time setting is to remain the stable pressure of the sy...

Page 40: ...n In parallel control system set the least quantity of pumps during operation 1 4 1 F154 Default Setting 0 Disable 0 CLF Clear error records dEF60 Restore the default value of drive for 60Hz dEF50 Res...

Page 41: ...e fault EEPROM component defected Please reset all parameters to default value and restart the drive Return the drive to repair when the fault can t be eliminated Fot RUN CRG MAIN SV PV IGBT module er...

Page 42: ...over loading condition at the motor Check if the the acceleration time is too short GF RUN CRG MAIN SV PV Grounding fault The three phase output current is unbalance and exceeding the detection level...

Page 43: ...lean the dust on the heat sink Return the drive to replace the cooling fan OL RUN CRG MAIN SV PV Motor overload Operation current exceeds 150 of motor s rated current and reaches the motor overload pr...

Page 44: ...ction time F069 Check the usage of mechanical equipment thr RUN CRG MAIN SV PV External fault The multi function terminal receives the external fault signal Clear the external fault and then press OFF...

Page 45: ...propriate Check whether the pressure of water pipe is normal Check whether the pressure sensor is normal FbLo RUN CRG MAIN SV PV Water shortage Water Shortage Detection by Pressure Level F119 Water Sh...

Page 46: ...op command is activated Clear coast to stop command db RUN CRG MAIN SV PV Braking transistor is active The internal DC bus voltage of drive is over the protection level DC bus voltage is too high Chec...

Page 47: ...RUN CRG MAIN SV PV Over pressure Over pressure Level F148 Over Pressure Detection Time F149 The setting value of F148 is not appropriate Pump oulet pressure is too high The water valve shut down immed...

Page 48: ...20P5B1 RM6F2 2002B1 RM6F2 20P5B3 RM6F2 2003B3 RM6F2 4001B3 RM6F2 4003B3 2 M4 146 76 88 158 5 2 138 47 5 70 81 123 5 Unit mm Model Number RM6F2 1002B1 RM6F2 1003B1 RM6F2 2003B1 RM6F2 2004B3 RM6F2 2005B...

Page 49: ...LE1 RUN CRG MAIN SV PV Under voltage during operation thr RUN CRG MAIN SV PV External fault OC RUN CRG MAIN SV PV Drive over current ntCF RUN CRG MAIN SV PV NTC Thermistor sensor fault GF RUN CRG MAI...

Page 50: ...PV Running Err_00 Keypad cable trip before connecting Err_01 Keypad cable trip during operation bb RUN CRG MAIN SV PV Drive output interruption dtF RUN CRG MAIN SV PV Direction command error Fr RUN CR...

Reviews: