manualshive.com logo in svg
background image

3.60 (91.4)

(96.5)

3.80

1.95

(49.5)

(2.5)

.10

(104.1)

4.10

(44.5)

1.75

PAR

9

1

3

2

4 5

6 7 8

10

13

11 12

14 15

SEL

RST

P

S 1

P

S 2

A

B

GENERAL DESCRIPTION

The PAXLCR is a versatile meter that provides a single or dual counter with 

rate indication, scaling and dual relay outputs. The 6-digit display has 0.56" high 
digits with adjustable display intensity. The display can be toggled manually or 
automatically between the selected counter and rate values.

The meter has two signal inputs and a choice of eight different count modes. 

These include bi-directional, quadrature and anti-coincidence counting, as well 
as a dual counter mode. When programmed as a Dual Counter, each counter has 
separate scaling and decimal point selection.

Rate indication is available in all count modes. The Rate Indicator has 

separate scaling and decimal point selection, along with programmable display 
update times. In addition to the signal inputs, the User Input can be programmed 
to perform a variety of meter control functions.

Two setpoint outputs are provided, each with a Form C relay. The outputs can 

activate based on either counter or rate setpoint values. An internal batch counter 
can be used to count setpoint output activations.

The PAXLCR can be powered from a wide range of AC or DC voltages. The 

meter has been specifically designed for harsh industrial environments. With a 
NEMA 4X/IP65 sealed bezel and extensive testing to meet CE requirements, the 
meter provides a tough yet reliable application solution.

MODEL NO.

DESCRIPTION

PART NUMBER

PAXLCR

Dual Counter & Rate Meter with Dual Relay Output

PAXLCR00

PAXLCRU

UL Listed Dual Counter & Rate Meter with Dual 
Relay Output

PAXLCRU0

SAFETY SUMMARY

All safety regulations, local codes and instructions that appear in this and 

corresponding literature, or on equipment, must be observed to ensure personal 
safety and to prevent damage to either the instrument or equipment connected to 
it. If equipment is used in a manner not specified by the manufacturer, the 
protection provided by the equipment may be impaired.  Do not use this meter 
to directly command motors, valves, or other actuators not equipped with 
safeguards. To do so can be potentially harmful to persons or equipment in the 
event of a fault to the meter

SPECIFICATIONS

1.

DISPLAY

: 6 digit, 0.56" (14.2 mm) intensity adjustable Red LED

2.

POWER REQUIREMENTS

:

AC POWER

: 50 to 250 VAC 50/60 Hz, 12 VA

Isolation

: 2300 Vrms for 1 min. to all inputs and outputs

DC POWER

: 21.6 to 250 VDC, 6 W

DC Out

: +24 VDC @ 100 mA if input voltage is greater than 50 VAC/VDC

  +24 VDC @ 50 mA if input voltage is less than 50 VDC

3.

COUNTER DISPLAYS

:

Counter A

: 6-digits, enabled in all count modes

Display Designator: “A” to the left side of the display
Display Range: -99999 to 999999

Counter B

: 6-digits, enabled in Dual Count mode or Batch Counter

Display Designator: “B” to the left side of the display
Display Range: 0 to 999999 (positive count only)

Overflow Indication

: Display “



” alternates with overflowed count value

Maximum Count Rates

: 50% duty cycle, count mode dependent.

With setpoints disabled: 25 KHz, all modes except Quadrature x4 (23 KHz).
With setpoint(s) enabled: 20 KHz, all modes except Dual Counter (14 KHz), 

Quadrature x2 (13 KHz) and Quadrature x4 (12 KHz).

  6 DIGIT, 0.56" HIGH RED LED DISPLAY

  PROGRAMMABLE SCALING FOR COUNT AND RATE

  BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL

  QUADRATURE SENSING (UP TO 4 TIMES RESOLUTION)

  BUILT-IN BATCH COUNTING CAPABILITY

  PROGRAMMABLE USER INPUT

  DUAL 5 AMP FORM C RELAYS

  UNIVERSALLY POWERED

  NEMA 4X/IP65 SEALED FRONT BEZEL

MODEL PAXLCR - PAX LITE DUAL COUNTER AND RATE METER

DIMENSIONS  In inches (mm)

Bulletin No.  PAXLCR- B
Drawing No.  LP0749
Released  04/09

CAUTION: Risk of Danger.

Read complete instructions prior to 

installation and operation of the unit.

CAUTION:

Risk of electric shock.

ORDERING INFORMATION

Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
 

 2.1" (53.4) H x 5.0" (127) W.

C

US LISTED

UL

R

IND. CONT. EQ.

51EB

For Model No. PAXLCRU0 Only

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание PAX LITE PAXLCR00

Страница 1: ...t If equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired Do not use this meter to directly command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event of a fault to the meter SPECIFICATIONS 1 DISPLAY 6 digit 0 56 14 2 mm intensity adjustable Red LE...

Страница 2: ...ents for electrical equipment for measurement control and laboratory use Part 1 IP65 Enclosure rating Face only IEC 529 IP20 Enclosure rating Rear of unit IEC 529 For Model No PAXLCRU0 Only UL Listed File E137808 UL508 CSA C22 2 No 14 M95 LISTED by Und Lab Inc to U S and Canadian safety standards ELECTROMAGNETIC COMPATIBILITY Emissions and Immunity to EN 61326 Electrical Equipment for Measurement ...

Страница 3: ...xternal EMI suppression devices such as ferrite suppression cores is effective Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of t...

Страница 4: ... A COMMON 4 5 6 7 5 24V EXC 3 t 2 5 A MAX Resistor to Limit Current ON 1 2 3 4 AC 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 ON 3 4 2 2 kΩ 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 2 1 ON 3 4 O C NPN 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 3 ON 4 O C PNP 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 3 4 ON COMMON 5 V 5 INPUT A INPUT B COMMON 7 6 5 24V EXC C...

Страница 5: ...the display alternates between the present parameter and the selections value for that parameter The SEL and RST buttons are used to move through the selections values for that parameter Pressing the PAR button stores and activates the displayed selection value This also advances the meter to the next parameter For numeric values the value is displayed with one digit flashing initially the right m...

Страница 6: ...g applications it is recommended to use Count with Direction for the count mode Simply leave the direction input unconnected Shaded area selections only apply when Counter B is enabled Dual Count mode or batch counter Counter A Subtract Counter A Add Counter A Add Counter A Add Quad A Count A Quad A Count A Quad A Count A Counter B Add Counter A Add Counter A Add Rate only Counter A Direction Coun...

Страница 7: ...osition Number of Pulses Given that 128 pulses are equal to 1 foot display total feet with a one hundredth resolution Scale Factor 1 00 x 100 128 Scale Factor 0 007812 x 100 Scale Factor 0 7812 EXAMPLE 2 A manufacturer wants to count the total number of bricks molded in a process yielding 12 bricks per mold The counter receives 1 pulse per mold and should increase by 12 for each pulse received Sin...

Страница 8: ...otted to a Display value of 0 and Input value of 0 0 Hz A linear relationship is formed between these points to yield a rate display value that corresponds to the incoming input signal rate The meter is capable of showing a rate display value for any positive slope linear process SCALING CALCULATION FOR KEY IN STYLE If a display value versus input signal in pulses per second is known then those va...

Страница 9: ...s this code to be entered at the prompt in order to access Full Programming mode Quick Programming mode if enabled is accessed before the prompt appears PROGRAMMING SECURITY CODE to to USER INPUT FUNCTION USER INPUT STATE SECURITY CODE MODE WHEN PAR KEY IS PRESSED FULL PROGRAMMING MODE ACCESS 0 Full Programming Immediate Access not ______ 1 99 Quick Programming After Quick Programming with correct...

Страница 10: ...ns to Press the PAR button to exit the module VIEW MODEL AND VERSION DISPLAY Select the display to which the Setpoint is assigned SETPOINT ASSIGNMENT Entering Code 66 will overwrite all user settings with the factory default settings The meter will display and then return to Press the PAR button to exit the module RESTORE FACTORY DEFAULT SETTINGS Some Setpoint parameters will not appear depending ...

Страница 11: ...ction is programmed for timed output SETPOINT 2 OUTPUT OFF AT SETPOINT 1 SP2 Only High Acting Boundary Type activates the output when the assigned display value equals or exceeds the Setpoint value Low Acting activates the output when the assigned display value is less than or equal to the Setpoint SETPOINT BOUNDARY TYPE This parameter only applies to Low Acting Boundary Type setpoints Select to d...

Страница 12: ...oint Annunciator SP1 Only Setpoint Value Setpoint Output Time out Setpoint Output Logic Exit Programming Counter Auto Reset Setpoint Boundary Type Setpoint Output Power up State Setpoint Standby Operation SP2 Output Off at SP1 Output SP1 Output Off at SP2 Output SEL SEL SEL SEL SEL PAR PAR PAR PAR PAR Counter B Scale Factor Counter B Decimal Point User Input Function Dual Count or Batch Only Count...

Отзывы: