background image

Catalog No.:  2000.24O 

Effective:  04-15-10 

Replaces:  12-01-07

 

Job: 

 

           

 

Engineer: 

 

           

 

Contractor: 

             

 

Prepared By: 

            

 Date:

              

 

Model: 

  

           

 

 

 

 

EFFICIENT 

 

82% efficiency – highest of any atmospheric 
boiler available today 

THERMAL SHOCK PROOF 

 

Twenty-year warranty against thermal shock damage 
up to 150°F differential 

 

Maximum operating temperature: 230°F 

LIGHTWEIGHT 

 

A floor load of 70 lbs./sq. ft. or less 

HIGH RECOVERY 

 

Cuts fuel costs substantially because the standby and 
radiation losses normal to other boilers are eliminated 

LOW WATER OPERATING TEMPERATURE 

 

Operates with inlet water temperature as low as 105°F 
without condensing 

 

Heat Exchanger 

ƒ

  ASME Inspected and Stamped 

160 PSIG 

ƒ

  National Board Listed 

ƒ

 Headers 

 Glass-lined Cast Iron – Standard  
 Bronze – Option A-1 

ƒ

 Finned 

Tubing 

 Copper – Standard  
 Cupro Nickel – Option A-3 

ƒ

  ASME Steel Tube Sheet 

ƒ

 Silicone 

O-Rings 

ƒ

  60 PSIG ASME Pressure Relief Valve 

ƒ

  Temperature and Pressure Gauge 

ƒ

 Water 

Connections 

 Left Hand – Standard  
 Right Hand – Option A-6 

ƒ

 Flow 

Configuration 

 Two-pass – Standard  
 Single-pass – Cast Iron Only 

ƒ

  Pump - Rear-mounted, 1/2 HP

,  

120 VAC, 1

,

 60 Hz – Optional 

 4.25” Impeller 
 4.7” Impeller 

Controls 

ƒ

  120V, 60Hz, 1 Ph Power Supply 

ƒ

 120/24V 

Transformer 

ƒ

  100% Pilot Shut-off/Lockout 

ƒ

  Electronic, Intermittent Ignition (IID) 

Pilot 

ƒ

  High Limit Control, Manual Reset, 

240°F 

ƒ

 On/Off 

Switch 

 

Controls (cont.) 

ƒ

 Flow 

Switch 

ƒ

  Economaster Pump Time Delay 

Gas Train 

ƒ

  Manual Main Gas Shut-off Cock 

ƒ

  Main Gas Pressure Regulator 

ƒ

  Redundant Safety Shut-off Valve 

ƒ

  Control Valve         

ƒ

 Firing 

Mode 

 On/off (H4) 
 Two-stage Firing (H3) 
 Four-stage Firing (H9) 
 Mechanical Modulation, 

110-170°F (H5) 

 Mechanical Modulation,  

150-210°F (H1) 

 Motorized Modulation (H2) 

ƒ

 Fuel 

 Natural Gas 
 Propane Gas     

ƒ

  Design Certified ANSI Z21.13/CSA 4.9  

Construction 

ƒ

  AB 1953 & VLA 193 Compliant 

ƒ

 Front 

Controls 

ƒ

  Stainless Steel Burners 

ƒ

  Polytuf Powder Coat Finish 

ƒ

 Vent 

Selection 

 Draft Diverter – Option D-10  
 Power Vent, Loose – Option D-2 

ƒ

 Base 

(Optional) 

 Combustible Floor Shield –  

Option J-1 

Temperature Controllers 

Note:  H1 and H5 do not require a 

controller 

 B-6  Two-stage 
 B-36  TempTracker Mod+ Hybrid 
 B-40  Motorized Modulation 
 B-41  Motorized Modulation, 

Outdoor Reset 

 B-     Four-stage 

Digital 

 Y-241 Electronic Sequencer,  

1-4 Stages 

 

 Y-281 Electronic Sequencer,  

1-8 Stages 

            Remote Controller 

 

 

 By others: 

Additional Safety Controls 

 F-9 

Low Water Cut-off Probe 

 I-1 

High Limit Control, Auto 
Reset, 240°F 

 S-1 

Low Gas Pressure Switch, 
Manual 

 S-2 

High Gas Pressure Switch, 
Manual 

                       

 

                       

 

Regulatory Agency Requirements 

            

 

            

 

 
 
 
 
 
 
 
 

 

Raytherm

®

 

- Type H

Hydronic Heating Boilers

Commercial

Models 962-1826 (Indoor)

INDOOR