background image

Powerware

®

5119 RM

User’s Guide

1000-3000 VA

www.powerware.com

02/15/01

Summary of Contents for 5119 RM

Page 1: ...Powerware 5119 RM User s Guide 1000 3000 VA www powerware com 02 15 01...

Page 2: ...UPS for Unrestricted Sales Distribution For these configurations the following applies WARNING This is a Class A UPS Product In a domestic environment this product may cause radio interference in whi...

Page 3: ...ANY INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION NOTE This equipment has been tested and found to comply with the limits for a Class B device pursuant to Part 15 of FCC Rules These limits are desi...

Page 4: ...fer servicing to the factory RISK OF ELECTRIC SHOCK Indicates that a risk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERATOR S MANUAL Refer to your op...

Page 5: ...PS On 13 Starting the UPS on Battery 13 Turning the UPS Off 13 Standby Mode 13 UPS Front Panel 14 AC Input LEDs 15 Battery Charge LEDs 15 Load Level LEDs 16 Initiating the Self Test 16 4 Configuration...

Page 6: ...UPS Features 25 Communication Port Configurations 25 Communication Indicator 25 Pin Out 26 Remote Emergency Power Off REPO 27 Load Segments 27 Option Modules 28 7 Specifications 29 8 Troubleshooting 3...

Page 7: ...pect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expen...

Page 8: ...ers disk arrays and servers Advanced Battery Management ABMZ doubles battery service life optimizes recharge time and provides a warning up to 60 days before the end of useful battery life Buck and Do...

Page 9: ...after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damag...

Page 10: ...s in a 19 inch rack Follow the steps below to install the UPS in the rack CAUTION The UPS is heavy 132 lb 60 kg A minimum of two people are required to lift the UPS into the rack NOTE Disconnect all c...

Page 11: ...Installation 5 Powerware 5119 Rack Mount User s Guide www powerware com Figure 2 Attaching the Mounting Bracket 1000 1500 VA Figure 3 Attaching the Mounting Handle 2000 3000 VA...

Page 12: ...UPS 2 For 230V models and 1000 1500 VA 120V models plug the UPS power cord into the input connector on the UPS rear panel Customer supplied power cords must correctly rated for the UPS see Specificat...

Page 13: ...The installation is complete To learn how to operate the UPS see Operation on page 13 To change the factory set defaults see Configuration on page 17 NOTE The UPS charges to 90 in approximately 4 hou...

Page 14: ...ad Segment 1 Three 5 15 Receptacles 15A IEC 320 Input Connector with Power Cord Load Segment 2 Three 5 15 Receptacles Figure 6 1000 1500 VA 120V Rear Panel Communication Port Option Slot Load Segment...

Page 15: ...0 Receptacles REPO Port Output Circuit Breaker Reset Buttons Power Cord with 5 20 Plug Figure 8 2000 VA 5 20R 120V Rear Panel Communication Port Load Segment 2 Three 5 15 Receptacles Load Segment 3 On...

Page 16: ...Option Slot REPO Port Load Segment 3 One 5 20 Receptacle and Three 5 15 Receptacles Output Circuit Breaker Reset Buttons Figure 10 3000 VA 5 20R 120V Rear Panel Communication Port Option Slot REPO Por...

Page 17: ...320 Input Connector Input Output Circuit Breaker Reset Buttons Option Slot REPO Port Figure 12 2000 2400 VA 230V Rear Panel Communication Port Load Segment 1 Three 10A IEC 320 Receptacles Load Segment...

Page 18: ...Installation 12 Powerware 5119 Rack Mount User s Guide www powerware com...

Page 19: ...ailable from the rear receptacles Starting the UPS on Battery To turn on the UPS without using utility power press and hold the On button for three seconds When the UPS starts on battery it does not c...

Page 20: ...trols Site Wiring Fault Indicator On Button Off Button Test Alarm Reset Button AC Input LEDs Load Level LEDs Communication Indicator Battery Charge LEDs Battery Service Indicator Power On Indicator Fi...

Page 21: ...is using the Double Boost feature to automatically correct voltage fluctuations If any AC Input LEDs are red see page 34 for more information Battery Charge LEDs The Battery Charge LEDs show informat...

Page 22: ...UPS capacity the third and fourth LED illuminate The last LED illuminates if the load is between 5 and 33 If any Load Level LEDs are red see page 35 for more information Initiating the Self Test Pres...

Page 23: ...inal input voltage by selecting a different input voltage or extending the input voltage range See Table 1 on page 19 for a list of available options Other Settings You can change the UPS default conf...

Page 24: ...Repeat Step 1 for one beep ONLY to enter Configuration mode and then perform Step 2 3 Press the button ONCE to toggle the selected option on or off The Power On indicator corresponds with the current...

Page 25: ...lecting this option changes the nominal input voltage on low voltage models to 127V and to 240V for high voltage models OFF default 127 240V is disabled one of the other input voltage options is selec...

Page 26: ...current the UPS shuts down the load This feature conserves battery power OFF Select this option if you want a load less than 5 of the current to be protected by battery power 100 208V Nominal Input V...

Page 27: ...r For full battery life keep the UPS at an ambient temperature of 25 C 77 F Storing the UPS and Batteries If you store the UPS for a long period recharge the battery every 12 months by plugging the UP...

Page 28: ...uit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries ELECTRIC...

Page 29: ...odels 2000 3000 VA Models Remove the face plate 1 2 3 4 Black Red Figure 19 Replacing Batteries Testing New Batteries Press and hold the button for three seconds to initiate a self test After the test...

Page 30: ...a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements Do not open or mutilate the battery or batteries Released electrolyte is harmf...

Page 31: ...d cable or a cable built to factory specifications see Table 2 to the communication port A standard serial cable may damage your computer When the communication cable is installed power management sof...

Page 32: ...conds Remote UPS off In absence of AC power output is turned off until normal AC power returns Serial Data Mode Input RS 232 data RS 232 serial communication input 1200 baud 8 bits No parity 1 stop bi...

Page 33: ...e equipment NOTE The REPO function activates when the dry isolated normally open REPO contacts close 1 Remove the REPO connector from the REPO port on the rear panel of the UPS 2 Connect dry isolated...

Page 34: ...uide www powerware com Option Modules Option modules help your UPS communicate in a variety of networking environments and are installed in the UPS option slot See the manual that accompanies each mod...

Page 35: ...5119 1 5Ki RM PW5119 2Ki RM PW5119 2 4Ki RM PW5119 3Ki RM Table 4 Electrical Input 120V Models 230V Models Nominal Voltage 120V default 100 110 120 127V selectable 230V default 208 220 230 240V select...

Page 36: ...n Battery Nominal Voltage 5 120V for 110 120 127V 100V for 100V 230V for 220 230 240V 208V for 208V Voltage Waveform Sine wave 3 distortion with linear load Overcurrent Protection Online Branch rated...

Page 37: ...s and Controls Serial Communication Intelligent serial communication to provide alarms with history measured parameters self test and many other features contact your authorized dealer for UPS compute...

Page 38: ...in Minutes Load VA 1000 Model 1500 Model 2000 Model 2400 Model 3000 Model 300 40 67 112 187 187 500 20 32 68 112 112 700 12 23 48 80 80 1000 7 13 27 45 45 1500 7 18 30 30 2000 11 19 19 2400 14 14 3000...

Page 39: ...an input fuse on the rear panel is open Push the circuit breaker button or replace the fuse see UPS Rear Panels on page 8 start The line cord is not connected Connect the line cord The wall outlet is...

Page 40: ...the condition persists the input voltage in your area may differ from the UPS nominal Change the UPS input voltage to match your local voltage see Configuration Mode on page 17 AC input low The line...

Page 41: ...ve Battery Service The DC voltage is high the alarm does not clear Contact your service representative Overload Power requirements exceed UPS capacity or the load is defective Remove some of the equip...

Page 42: ...the Bill Of Lading if applicable Use the original packaging or request packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under war...

Reviews: