Online UPS

 

PowerWalker VFI 10000CRM LCD 

 
 
 
 

 

 
 
 
 
 

Manual   

 

Uninterruptible Power Supply System

Summary of Contents for VFI 10000CRM LCD

Page 1: ...EN Online UPS PowerWalker VFI 10000CRM LCD Manual Uninterruptible Power Supply System...

Page 2: ......

Page 3: ...ing instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety i...

Page 4: ...REAR PANEL VIEW 5 2 3 SINGLE UPS INSTALLATION 6 2 4 SOFTWARE INSTALLATION 7 3 OPERATIONS 8 3 1 BUTTON OPERATION 8 3 2 LED INDICATORS AND LCD PANEL 8 3 3 AUDIBLE ALARM 10 3 4 SINGLE UPS OPERATION 11 3...

Page 5: ...nnect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not...

Page 6: ...quipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Do not use this equipment in the presen...

Page 7: ...e mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Cond...

Page 8: ...Be sure that nothing inside the package is damaged during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts Please k...

Page 9: ...ng table Model Wiring spec AWG Input Output Battery Ground PowerWalker VFI 10000CRM LCD 8 8 8 PowerWalker VFI 10000CRM LCDL 8 8 8 8 NOTE 1 It is recommended to use suitable wire in above table or thic...

Page 10: ...UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed If not please install it carefully Switch off the battery b...

Page 11: ...tton to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 1s to mute the buzzer Please refer to section 3 4 Mute the buzzer for details Down ke...

Page 12: ...is disabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level b...

Page 13: ...de Beeping once every 2 minutes Yes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Batte...

Page 14: ...on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Switch on the devices one by one and it will display total load level in LCD pane...

Page 15: ...UPS with utility power supply in AC mode 1 Turn off the inverter of the UPS by pressing OFF button for at least 1s and then the buzzer will beep once The UPS will turn into Bypass mode NOTE 1 If the...

Page 16: ...ault occurs Don t try to turn on the UPS again before solving the problems If the problems can t be fixed please contact the distributor or service people immediately 3 For emergency case please cut o...

Page 17: ...ge Y 02 Output frequency Y 03 Voltage range for bypass Y 04 Frequency range for bypass Y 05 Reserved 06 Reserved 07 Reserved 08 Bypass mode setting Y Y 09 Battery maximum discharge time setting Y Y Y...

Page 18: ...put frequency at CVCF mode or non CVCF mode You may choose following two options in parameter 3 CF Setting UPS to CVCF mode If selected the output frequency will be fixed at 50Hz or 60Hz according to...

Page 19: ...Setting reserved 06 reserved Interface Setting reserved 07 reserved Interface Setting reserved 08 Bypass mode setting Interface Setting Parameter 2 OPN Bypass allowed When selected UPS will run at Byp...

Page 20: ...990 min DIS Disable battery discharge protection and backup time will depend on battery capacity 10 reserved Interface Setting reserved 11 reserved Interface Setting reserved 12 reserved Interface Set...

Page 21: ...voltage Parameter 3 the voltage range is from 0V to 6 4V the default value is 0V 17 Constant charger voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust constant char...

Page 22: ...lated backup time x Multiplier factor The default value of multiplier factor is 1 0 and the setting range is from 0 5 to 2 3 7 Operating Mode Status Description Operating mode status AC mode Descripti...

Page 23: ...D display Battery Test Description When UPS is in AC mode or CVCF mode press Test key for more than 1s Then the UPS will beep once and start Battery Test The line between I P and inverter icons will b...

Page 24: ...None Over temperature 41 None Inverter soft start failure 11 None Overload 43 High Inverter voltage 12 None 3 9 Warning Indicator Warning Icon flashing Alarm Battery low Beeping every second Overload...

Page 25: ...overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43...

Page 26: ...e required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 27: ...recover to 90 capacity Charging Current Default 1 A 10 Max 1A 2A Adjustable Charging Voltage 218 4V 1 Long run Model Type Depending on applications Numbers 16 Charging Current Default 4 A 10 Max 1A 2...