PAD100-SB
Addressable Sounder Base
8830104 - REV B
•
12/17
PAGE 1 OF 2
Description
The Addressable Sounder Base 6” (PAD100-SB) is a sounder base that
may be utilized in a variety of applications. The base has a locking
feature for the sensor that may be used or removed in the field. Once
the head is removed, the sounder is accessible in the bottom of the unit.
The base has an independent sounder module that may be programmed
as a single station, zone or all call sounder. The PAD100-SB passes
through the sound pattern sent to the sounder, therefore it may
reproduce in any pattern the power supply provides.
The panel will support any combination of sensors or modules on
the SLC. The PAD100-SB does not consume an address on the loop
and is fully programmable to operate with any input. Once activated
the sounder will also follow the input from the power source and de-
activate accordingly.
Technical Specifications
Working Range for SLC
24 VDC
Working voltage range for
PWR
16 - 33 VDC
Active current for PWR
30 ma
Sound pressure level
75dB/10ft (min.) as per UL464
Installation temperature
range
32°F to 120°F (0°C to 49°C)
Operating relative
humidity range
0% to 93% (Non-condensing)
Start-up time
Max. 1 sec.
Maximum number of
devices per zone
127
Color
Eggshell White
Dimensions (without
detector)
Height: 0.75 in (19mm)
Diameter: 6.3 in (166 mm)
Features
•
Integrated Sounder in base
•
75 dB (UL 464 Listed) sounder output
•
Sounder independent of sensor, allows for a single station,
grouped or all-call
•
May be mapped to any device connected to the control panel
•
Terminals accept 22 to 12 AWG wire sizes
•
Supports Class A, Class X and Class B wiring
•
Does not require SLC Loop address
DWG • 516-