background image

 

 

www.piigab.com 

 

PiiGAB Processinformation i Göteborg AB •  Anders Carlssons gata 7 • S-417 55  Göteborg • Sweden 

Tel: +46(0)31 559977 •  Fax: +46(0)31 227071 • email: [email protected] 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Getting started PiiGAB 810 

 
 

 

 

 

 

 
 
 
 

Summary of Contents for 810

Page 1: ...www piigab com PiiGAB Processinformation i Göteborg AB Anders Carlssons gata 7 S 417 55 Göteborg Sweden Tel 46 0 31 559977 Fax 46 0 31 227071 email info piigab se Getting started PiiGAB 810 ...

Page 2: ...FIND YOUR PIIGAB 810 ON YOUR NETWORK 8 7 CONFIGURE THE PIIGAB 810 9 8 PIIGAB M BUS SETUP WIZARD M BUS COMMUNICATION 11 8 1 COMMUNICATE WITH TEST AND DIAGNOSTIC ADDRESS 12 8 2 COMMUNICATE WITH THE METER S ACTUAL PRIMARY ADDRESS 13 8 3 IDENTIFY THE METER S ADDRESSES IN THE PIIGAB M BUS SETUP WIZARD 14 8 4 PARTS IN THE SECONDARY ADDRESS 14 8 5 SECONDARY ADDRESS IDENTIFICATION NUMBER AND WILD CARDS 15...

Page 3: ...sing something please contact us so we can improve this document continuously See contact information at the end of the document 1 1 Versions Version Modified by Details 1 00 00 Stefan Eriksson Initial version 1 00 01 Stefan Eriksson Edited distributor contact information 2 Requirements Object Detail One PiiGAB 810 One M Bus meter Supports EN13757 One power supply 24V AC DC A patch cable PiiGAB M ...

Page 4: ... PiiGAB M Bus Setup Wizard 2 Connect PiiGAB 810 gateway to your computer with the patch cable 3 Connect the M Bus meter to the PiiGAB 810 4 Connect PiiGAB 810 gateway to a 24V AC or DC power supply 5 Turn the power supply on 6 Wait for PiiGAB 810 s Pwr LED to go steady red M Bus meter Power supply 24V AC DC Network Patch cable ...

Page 5: ...The most common IP configuration of the PiiGAB 810 gateway is for static IP address The gateway is by default set to DHCP when delivered 5 1 DHCP network If you have a network with DHCP you can connect your PiiGAB 810 gateway to it and the gateway will receive the IP configuration automatically 5 2 Static IP If you don t have a network with DHCP you must set your PiiGAB 810 gateway to a static IP ...

Page 6: ...ct Setup IP using network UDP broadcast 6 In the MAC address field specify the PiiGAB 810 gateway s MAC address 7 Press Next to continue 8 Select Use the following IP address 9 Specify the IP configuration The PiiGAB 810 gateway should match your computer s IP address 10 Press Next to continue ...

Page 7: ... started PiiGAB 810 Rev 1 00 01 PiiGAB Processinformation i Göteborg AB Page 7 11 Press Apply to set the IP configuration 12 Wait for the PiiGAB 810 gateway to reboot 13 Press Next to continue to the main menu ...

Page 8: ...work with DHCP or static IP address configuration 1 Go to the main menu in the PiiGAB M Bus Setup Wizard 2 Select Find gateways on your network 3 Press Next to continue 4 Your PiiGAB 810 gateway should be listed 5 Find your PiiGAB 810 by the MAC address column 6 Select your PiiGAB 810 gateway and press Next Note If you placed your PiiGAB 810 gateway on a different sub network you might not find it...

Page 9: ... the PiiGAB 810 should be configured for M Bus communication for 2400 baud UDP and port 10001 1 In the PiiGAB M Bus Setup Wizard s main menu click the Change gateway parameters 2 Press Next to continue 3 Select Connect using network Note Make sure the PiiGAB 810 gateway s IP address is shown in IP address DNS field 4 Press Next to continue ...

Page 10: ... 01 PiiGAB Processinformation i Göteborg AB Page 10 5 Configure the PiiGAB 810 with these settings 6 Press the Apply button to continue 7 Wait for the program to finish the configuration of the PiiGAB 810 gateway 8 Press Next to continue ...

Page 11: ...eter respond to M Bus communication 1 In the main menu select Test search and configure meters 2 Press Next to continue 3 Select Connect using network and configure the connection as shown in the picture below Note Your PiiGAB 810 s IP address may not be 192 168 10 122 The PiiGAB M Bus Setup Wizard only fills in the IP address automatically as you selected in Find your PiiGAB 810 on your network s...

Page 12: ... should respond to This address is called Test and diagnostic and has the value 254 This address is very useful if only one M Bus meter is connected to the M Bus master and the meter s actual primary address is unknown 1 Configure as the picture shown below 2 Press the Find button to test communication with the M Bus meter For this example the M bus meter responded and its primary address is 1 ...

Page 13: ... 8 2 Communicate with the meter s actual primary address Always make sure the M Bus meter responds to the actual primary address 1 Configure as the picture shown below 2 Press the Find button to test communication with the M Bus meter As expected the meter responded to primary address 1 ...

Page 14: ...er s actual primary and secondary addresses In the previous example the meter s addresses are Address Value Primary 1 Secondary 00922082 4ECD 09 04 8 4 Parts in the secondary address The secondary address is based on four fields These fields make the meter s secondary address entirely unique These fields are Field Value Identification number 00922082 BCD Manufacturer 4ECD Hex Version 09 Hex Media ...

Page 15: ...ddress For the secondary address there is often just enough to specify the identification number 1 Configure as the picture shown below 2 Press the Find button and test the communication with the meter 8 6 Entire secondary address If the meter doesn t respond to the identification number you can enter the entire secondary address 1 Configure as the picture shown below 2 Press the Find button and t...

Page 16: ...on t support usage of primary addresses If that is the case then the meter s secondary address must be used The opposite of Test and diagnostic from primary addresses usage is wild cards in the secondary address 1 Configure as the picture shown below 2 Press the Find button to test communication with the M Bus meter As expected the meter responded ...

Page 17: ...7 www piigab com Distributors Please contact our distributors in respective countries Germany Relay GmbH Stettiner Str 38 33106 Paderborn Germany Phone 49 5251 17670 www relay de Norway Autic Systems AS Stoltenbergs gate 48 3110 Tønsberg Norway Phone 47 33 30 09 50 www autic no Czech Republic Papouch store s r o Strasnicka 3165 1b 102 00 PRAGUE 10 Czech Republic Phone 420 267 314 267 8 www papouch...

Reviews: