background image

 

 

 

 

 

 

 

Summary of Contents for SpaceWice

Page 1: ......

Page 2: ...egress mode for emergency applications 21 13 Troubleshooting 24 14 Linking a wireless switch to the SpaceWise group 25 15 Linking a wireless scene selector to the SpaceWise group 28 16 Linking an external wireless ceiling sensor to the SpaceWise group 31 17 Creating zones in a group 33 18 Altering the default scenes on the scene selector with no zones 36 19 Altering the default scenes on the scene...

Page 3: ...ccommodate partition height reflectances and light level requirements Out of the box a group of SpaceWise Technology luminaires are optimized to deliver approximately 88 of the full light output of the luminaire under the following standard application space parameters Luminaire length Celling grid Ceiling height Partition height Workstation 4 ft 8 ft x 10 ft 8 to 9 ft 4 5 ft 8 ft x 12 ft 2 5 ft 2...

Page 4: ...To limit unwanted motion detection the coverage of the luminaire can be restricted by the sensor shield The shield is a plastic circular ring located around the occupancy sensor lens To install the shield first pull out the ring completely and then reinsert it backwards so that the elongated part of the shield is facing downwards ...

Page 5: ...h the SpaceWise Remote large groups of 30 50 luminaires are recommended to maintain the lighting aesthetics of the space Smaller groups may turn off more frequently than desired Install luminaires per manufacturer installation instructions and ensure sensors from adjacent luminaires are not positioned next to one another ...

Page 6: ...settings A set of 2 AAA batteries of 1 5V each are supplied with the remote Before proceeding to the commissioning instructions make sure that the batteries are correctly installed in the remote and the luminaires are powered The angle under which the IR receiver in the sensor will receive signal is a 55 degree angle PREPLAN WHICH FIXTURES YOU LL WANT TO BE IN A GROUP AND TRY TO ANSWER QUESTIONS B...

Page 7: ...eshooting before proceeding a Point remote to any luminaire and press Open once Wait for the luminaires to dim down to 5 Make sure the button is pressed only once Pushing multiple times can create multiple networks which can cause undesired operation b Walk to the next luminaire to be added to the group point to the luminaire and press add Repeat step for adding all the luminaires in the group Add...

Page 8: ...s lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for daylight calibration Group is ready for normal operation Once the group is locked it will not accept any configuration changes To make any changes the group has to be unlocked first In order to save time you can choose to l...

Page 9: ... 25 25 25 Prolong Time2 Infinite Infinite Infinite Infinite Infinite Infinite Start up and Dim behavior Behavior of the luminaires after grouping Background Level 27 27 27 27 27 10 Fading to Switch On 1s 1s 1s 1s 1s 1s Hold Time 10 min 10 min 10 min 10 min 5 min 5 min Fading to Background Level 10s 10s 10s 10s 10s 10s Prolong Time 15 min 0 min 15 min 0 min 15 min Infinite Occupancy Mode Auto On Au...

Page 10: ...e to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point to any of the luminaires in the group and press mode While the LED is still blinking red enter the number for the preferred mode see list at step 5 Red LED on remote will start blinking Red LED on remote will...

Page 11: ... unsure about mode selection or remote blinking status then wait for the remote blinking to stop and redo step b c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation...

Page 12: ...ctances light level preference and energy goals Light output setting Percentage High 100 Medium default 88 Low 77 Minimum 66 a Point remote to any luminaire and press unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light l...

Page 13: ...e step The luminaire may or may not flash at the end of the step depending upon firmware version Note that the default setting is Medium To get to high go one step up To get to Minimum go two steps down Medium to High Will move light output setting from default of 88 to 100 Medium to low Will move light output setting from default of 88 to 77 Low to minimum Will move light output setting from 77 t...

Page 14: ...t to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation ...

Page 15: ...ait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Press pir button While the LED is still blinking red enter the numbers 10 Enable occupancy sensing 12 Disable occupancy sensing lights will stay at 100 Red LED...

Page 16: ...ght level will go to 50 Repeat step b for all the luminaires that need to be reconfigured c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation ...

Page 17: ...lock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Press daylight button While the LED is still blinking red enter the numbers 1 Disable daylight sensing 2 Enable daylight sensing Red LED on remote w...

Page 18: ...ght level will go to 50 Repeat step b for all the luminaires that need to be reconfigured c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation ...

Page 19: ...ait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point remote to any of the luminaires and adjust the group light level to the required level using the dimming up or down arrow keys When the arrow keys are pr...

Page 20: ...ght set point Red LED on remote will blink The entire group will FLASH twice and group light level will go to 50 d Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation ...

Page 21: ...seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point remote to any of the luminaires and press test To stop the test feature press the test button again Test feature is activated users can now walk in the space to estimate the occupancy cover...

Page 22: ... on the generator back up system During emergency the battery will bypass the sensors and therefore the luminaire will not shut off automatically When normal power is restored the luminaire will behave like a standard SpaceWise system The path of egress luminaire should be powered on the emergency circuit As long as the luminaire is powered an adequate light level will be delivered by the luminair...

Page 23: ...ny of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Press pir button While the LED is still blinking red enter the numbers 11 Enable path of egress feature 10 Disable path of egress feature Red LED on remote will start blinking Red LED on remote will stop blinking ...

Page 24: ...ured with the path of egress feature The luminaire will FLASH twice and group light level will go to 50 c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation ...

Page 25: ...s unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point to any of the luminaires in the group and press reset Once LED stops blinking with remote still pointing to the luminaire in the group pre...

Page 26: ...d release action on the rocker will turn on or turn off the lights A long press and hold action on the rocker will dim the lights accordingly a Point remote to any luminaire and press unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice ...

Page 27: ...p light level will go to 5 Step d is a trial and error process The 4 buttons signify 4 different wireless channels To join the switch to the luminaire group the wireless channel of the switch and the luminaire must match Since the wireless channel of the luminaire is not visible one has to try out all the 4 channels via the buttons to determine the matching channel as described in step e e If the ...

Page 28: ...the switch and test the switch by pressing the rocker pads All the luminaires in the group will turn on off based on the rocker pad action h Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ...

Page 29: ...ess message to the luminaires The factory default reactions for each button are I Activates the automatic behavior where the light levels are set by the sensor O Turns off the lights Recalls scene 2 default 20 and overrides the light levels set by the sensor Recalls scene 3 default 40 and overrides the light levels set by the sensor a Point remote to any luminaire and press unlock once Wait for LE...

Page 30: ...d group light level will go to 5 Step c is a trial and error process The 4 buttons signify 4 different wireless channels To join the scene selector to the luminaire group the wireless channel of the scene selector and the luminaire must match Since the wireless channel of the luminaire is not visible one has to try out all the 4 channels via the buttons to determine the matching channel as describ...

Page 31: ...int to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation g Test the scene selector by pressing the buttons All the luminaires in the group will react to the button action OR...

Page 32: ...r the passage way entrance an OSW ceiling sensor can be installed near the entrance to detect an incoming occupant and trigger the group lights thereby avoiding the possibility of any dark passage way for the user a Point remote to any luminaire and press unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blink...

Page 33: ...rt blinking The LED indicator on OSW sensor will turn green upon successful linking of the sensor to the group If the OSW sensor fails to join the group then red LED will turn on In case of failure repeat step c d Point to any of the luminaires in the group and press close All the luminaires in the group will go to 50 light level e Point to any of the luminaires in the group and press lock Wait fo...

Page 34: ...n a different or no zone will react on the occupancy signal by going to background level Zones can only be created within a group so a group should be created first as per the instructions in section 4 Switch and the scene selector cannot be added to the zone They can only be linked at a group level a Point remote to any luminaire and press unlock once Wait for LED to stop blinking apx 10 seconds ...

Page 35: ...e added to the zone point to the luminaire and press add Repeat step for adding all the luminaires in the zone Added luminaire will go to 50 To create new zones execute steps b and c again Note that a luminaire can only be part of one zone d To stop the zone creation process point to any of the luminaires added in the zone and press close All the luminaires in the group will go to 50 e To test the...

Page 36: ...ing The luminaire will FLASH twice and group will turn OFF and ON once for Daylight calibration Group is ready for normal operation g Alternately zones can also be re tested after locking the group Point remote to any of the luminaires in the created zone and press zone Point to the same luminaire and press on or off To stop the test process point to the same luminaire and press close The entire z...

Page 37: ...ult 40 and overrides the light levels set by the sensor a Make sure the group is locked and in the operational state Point remote to any luminaire and dim the group to the required light level by pressing the up or down arrow keys or The group will dim accordingly b Press scene once While the LED is still blinking red enter the scene number to be stored Select number 2 to store the scene on the bo...

Page 38: ...ll the luminaires in the group will react to the button action a Make sure the group is locked and in the operational state Point remote to any luminaire that is part of the zone and press Zone once The luminaire will go to 50 while the rest of the luminaires go to 5 b Point remote to the same luminaire and dim the zone to the required light level by pressing the up or down arrow keys or switch th...

Page 39: ...nter the scene number to be stored Select number 2 to store the scene on the bottom left button on the scene selector Select number 3 to store the scene on the bottom right button on the scene selector Red LED on remote will start blinking Red LED on remote will stop blinking d Point to any of the luminaires in the group and press save The luminaire will FLASH twice e Test the scene selector by pr...

Page 40: ...from a wall switch non SpaceWise switch or from the breaker panel turn the power off for 5 seconds and then turn it back on After a power cycle the luminaire will take 30 seconds to stabilize After these 30 seconds test the ON OFF commands on the luminaire Please note that if power cycle is performed or interrupted in between the grouping sequence then those luminaires that were successfully group...

Page 41: ...eived including interference that may cause undesired operation Any changes or modification not expressly approved by Philips could void the user s authority to operate this equipment This product is intended for commercial use only 22 Warranty A detailed product warranty statement can be found on the Philips website http www lighting philips com us_en connect tools_literature warranties wpd 23 Te...

Page 42: ...SpaceWise for Office Applications v 3 7 41 Philips Lighting North America ...

Reviews: