Page 1: ...he transportation company immediately and file a concealed damage claim LOCATION Check local codes for regulations concerning zoning noise platforms and other issues Locate unit away from fresh air intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the unit L...

Page 2: ...mm J 18 457mm 18 457mm 152mm 18 152mm 4 102mml 102mm wide fence 18 457mm 24 610mm Service 18 457mm 152mm 1 1 Im 8 152mm Post 18 457mm 18 457mm 24 610mm Service f 18 457mm 24 610mm Service J Fig 1 Clearances 18 457mm 24 J 610mm Service I 18 457mm ...

Page 3: ... Place the unit over one or more load bearing walls If there are several units mount them on platforms that are self supporting and span several load bearing walls These suggestions are to minimize noise and vibration transmission through the structure If the structure is a home or apartment avoid locating the unit over bedrooms or study NOTE When unit is to be installed on a bonded guaranteed roo...

Page 4: ...ade Be extra careful when bending refrigeration tubing Tubing can kink easily and if this occurs the entire length of tubing must be replaced PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury and or death Relieve pressure and recover all refrigerant before servicing existing equipment and before final unit disposal Use all service ports and open all flow control...

Page 5: ...rier be installed in the liquid line Leave the plugs in the tube ends until the filter drier is installed The optimal location for the filter drier is close to the indoor coil Install the filter drier with the arrow pointing towards the indoor coil Refer to Fig 5 A05178 Fig 5 Liquid Line Filter Drier Installed at Indoor Unit Failure to follow this warning could result in personal iniury death and ...

Page 6: ...s vacuum level The deep vacuum method is the most positive way of assuring a system is free of air and water Watch the vacuum gauge as the system is pulling down The response of the gauge is an indicator of the condition of the system refer to Fig 7 With no leaks in the system allow the vacuum pump to run for 30 minutes minimum at the deep vacuum level 5000 4500 4000 3500 g3000 _2500 m 2000 1500 V...

Page 7: ...pply Line Voltage connections with rain tight conduit and fittings Most codes require a disconnect switch outdoors within sight of the unit Consult local codes for special requirements Route electrical supply Line Voltage wiring through knockout hole in bottom of Control Box Connect wires to Contactor and Ground Lug according to Wiring Diagram on unit Also refer to Fig 9 Route thermostat wiring th...

Page 8: ... fan motor motor will operate in low speed when outdoor ambient temperature is below 82 F 28 C Pull one of the yellow low voltage wires off the fan control and the unit will default to high speed fan for servicing Reconnect wire after servicing 2 Measure liquid service valve pressure by attaching an accurate gauge to service port 3 Measure liquid line temperature by attaching an accurate thernfist...

Page 9: ...drainage and clean if necessary Cleanliness These tips will help keep the air conditioner looking better and working more efficiently 1 Free flow of air is essential Keep fences shrubs trash cans and other obstructions at least 18 inches 0 5 m from all coil inlets 2 Keep the coil free of grass clippings leaves weeds and other debris NOTE Coil may occasionally require cleaning with a liquid solutio...

Page 10: ...W Morris St Indianapolis IN 46231 Printed in Mexico edition date 11 10 Manufacturer reserves the right to change at any time specification8 and design8 without notice and without obligations Catalog No IM PA13NR 05 Replaces New 10 ...