Refrigerating Specialties Division

1

BULLETIN DN23-10

B

Type A4AL-DN

A4AL-DN

Fig 1

DIFFERENTIAL PRESSURE
RELIEF REGULATOR
TYPE A4AL-DN

Port Size 3/4"- 4" (20-100mm)
For Ammonia, R-22, R134a, R404a, R507
and other common refrigerants.

FEATURES
• Pilot operated characterized Modulating

Plug  for precise control

• Suitable for all common refrigerants and oil

  406

 psig (2

8

 bar) design pressure (PS)

• Flanges for threaded or welded steel pipe

and copper tube (copper not for ammonia)

• Unique Modular construction
• Interchangeable parts
• Easy to Service
• Close coupled strainers, optional
• Stainless Steel Diaphragm
• Manual Opening Stem
• Complies with Pressure Equipment Direc-

tive 97/23/EC

Description:
These compact, heavy duty, pilot operated,  Differential
Pressure Regulators are suitable for Ammonia, R22,
R134a, R404a, R507 and other common refrigerants and
fluids approved for use in refrigeration systems.

All A4AL Regulators are pilot operated using upstream
pressure for the opening force and require a minimum 2
psi (0.14 bar) pressure drop to fully open.

These valves are generally ordered with close coupled
upstream strainer to prevent entrance of foreign material
into the valve and the rest of the system.

Purpose:
Modulates flow of refrigerant liquid or gas to maintain a
constant set-for pressure differential between regulator
inlet and regulator outlet.

Regulator applications are as follows:  As a relief valve
from pump outlet to accumulator of a liquid recirculating
pump system to prevent pump overload or dry pumping
when evaporator liquid solenoid valves are closed.
Differential pressure will not vary despite fluctuating
accumulator pressures.  As a gas or liquid pressure
regulator whenever it is desired to maintain a set-for
pressure difference between regulator inlet and outlet.
The fluid temperature range for the A4AL Series of
Regulators is -50°F to 220°F (-45°C to 105°C).

January 2007

Installation and Service Information

I S O   9 0 0 1   C E R T I F I E D

310218

Summary of Contents for A4AL-DN

Page 1: ...s All A4AL Regulators are pilot operated using upstream pressure for the opening force and require a minimum 2 psi 0 14 bar pressure drop to fully open These valves are generally ordered with close co...

Page 2: ...r the system has been in operation for a while and make any minor corrections neces sary Installation All regulators are packed for maximum protec tion Unpack carefully check the carton to make sure a...

Page 3: ...l the flats onthestembarelyprotrudefromthestuffingbox nut Push Piston 30 down against the spring force The piston should move freely down and be returned by the spring force If the piston is jammed or...

Page 4: ...g must be replaced Check other system components for proper op eration Check hand valves in the system to make sure they are open or closed as required and the system is receiving liquid or gas as the...

Page 5: ...Spring Rest Lower 15 Diaphragm Follower 16 Gasket Bonnet 17 Diaphragm 18 Seat Pilot 19 Gasket Adapter 20 Flg Ring tube Asm 27 Gauge Port Pipe Plug 28 Adapter Body 29 Gasket Body 30 Piston Stem 31 Scre...

Page 6: ...BOTTOM A4A S4A 1 5 8 to 2 1 2 DUCTILE IRON GGG 40 3 BONNET A4W DUCTILE IRON GGG 40 3 COMPONENT DESCRIPTION MATERIAL Kv VOLUME BODY 2 A4A DN DUCTILE IRON GGG 40 3 42 4 1 61 L ADAPTER 2 A4A DN DUCTILE...

Page 7: ...A43P 414 16 3 432 17 0 485 19 1 505 19 9 620 24 4 676 26 6 C 164 6 2 203 8 0 251 9 9 252 9 9 311 12 2 359 14 1 G A4P A4L 244 9 6 248 9 8 287 11 3 302 11 9 324 12 8 361 14 2 A43P 266 10 5 270 10 7 308...

Page 8: ...me for Refrigerating Specialties any other liability in con nection with any of it products SYMPTOM PROBABLE REASON CORRECTION Regulator does not shut off flow Diaphragm or seat dirty damaged or froze...

Reviews: