background image

(Left and right are identical)

Installation plate

Sleeve (   )

Bushing-Sleeve (   )

Bend the pipe as 
closely on the wall as 
possible, but be careful 
that it doesn’t break.

Saddle (   )

Putty (   )
(Gum Type Sealer)

Installation parts you 
should purchase (   )

50 mm 

or more

Vinyl tape (wide) (   )

 

• Apply after carrying 

out a drainage test.

 

• To carry out the 

drainage test, 
remove the air fi lters 
and pour water into 
the heat exchanger.

Power supply cord (   )

It is advisable to avoid more 

than 2 blockage directions. 

For better ventilation & 

multiple-outdoor installation, 

please consult authorized 

dealer/specialist.

Indoor/Outdoor Unit Installation Diagram

50 mm 

or more

(*)

ENGLISH

ACXF60-47740

PRINTED IN MALAYSIA

SAFETY PRECAUTIONS

 

Read the following “SAFETY PRECAUTIONS” carefully before installation.

 

This installation manual must be used together with another installation manual incorporated in applicable outdoor unit as complete full set of instructions.

 

Confi rm the type of gas used before installation.

 

Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.

 

The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation due 
to ignoring of the instruction will cause harm or damage, and the seriousness is classifi ed by the following indications.

 

 WARNING

This indication shows the possibility of causing death or serious injury.

 

 CAUTION

This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classifi ed by the symbols:

Symbol with white background denotes item that is PROHIBITED.

   

Symbol with dark background denotes item that must be carried out.

 

Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please 
remind the customer to keep the operating instructions for future reference.

PRECAUTION FOR USING R32 REFRIGERANT

 

Pay careful attention to the following precaution points and the installation work procedures.

When connecting fl are at indoor side, make sure that the fl are connection is used only once, if torqued up and released, the fl are must be remade. Once the fl are connection was torqued up 
correctly and leak test was made, thoroughly clean and dry the surface to remove oil, dirt and grease by following instructions of silicone sealant. Apply neutral cure (Alkoxy type) & ammonia-
free silicone sealant that is non-corrosive to copper & brass to the external of the fl ared connection to prevent the ingress of moisture on both the gas & liquid sides. (Moisture may cause 
freezing and premature failure of the connection)

The appliance shall be stored, installed and operated in a well ventilated room with indoor fl oor area larger than 

A

min

 (m²) [refer Table A] and without any continuously operating ignition source.

Keep away from open fl ames, any operating gas appliances or any operating electric heater. Else, it may explode and cause injury or death.

Refer to “PRECAUTION FOR USING R32 REFRIGERANT” in outdoor unit installation manual for other precautions that need to pay attention to.

Air conditioner

Installation Instruction
(Simpli

fi

 ed Version)

MODEL NO. :-

CS-TZ60, TZ71ZKE Series.

A

CXF60-47740

Applicable piping kit

Piping size

Gas

Liquid

CZ-3F5, 7BP

9.52 mm (3/8")

6.35 mm (1/4")

CZ-4F5, 7, 10BP

12.7 mm (1/2")

6.35 mm (1/4")

CZ-52F5, 7, 10BP

15.88 mm (5/8")

6.35 mm (1/4")

 

Pipe Size Reducer (CZ-MA3PA) and Expander (CZ-MA2PA) for Outdoor Multi Connection
CS-TZ60***,
CS-TZ71***

 

Please refer to “CONNECT THE PIPING” section

SELECT THE BEST LOCATION

INDOOR UNIT

Do not install the unit in excessive oil fume area such as kitchen, workshop 
and etc.

There should not be any heat source or steam near the unit.

There should not be any obstacles blocking the air circulation.

A place where air circulation in the room is good.

A place where drainage can be easily done.

A place where noise prevention is taken into consideration.

Do not install the unit near the door way.

Ensure the spaces indicated by arrows from the wall, ceiling, fence or other 
obstacles.

Indoor unit of this air conditioner shall be installed in a height of at least 1.8 m.

Table A

Model

Capacity W 

(HP)

Max. Refrigerant

Charge (k

g

)

Indoor 

A

min (m²)

TZ60***,

2.25HP

1.52

Not applicable (*)

TZ71***

2.5HP

1.85

4.46

(*)  Systems with total refrigerant charge, m

c

 , lower than

1.84 k

g

 are not subjected to any room area requirements.

*  Table “A” only applicable for single split connection.
*  In case of connection to outdoor multi inverter,

refer to installation manual at outdoor unit.

 

This illustration is for 
explanation purposes only.
The indoor unit will actually 
face a different way.

A

min

 = (

m

c

 / (2.5 x (

LFL

)

(5/4)

 x 

h

0

)) 

2

 

A

min

 = Required minimum room area, in m²

m

c

  = Refrigerant charge in appliance, in 

LFL

  = Lower fl ammability limit (0.307 

/m³)

h

0

 = 

 

Installation height of the appliance (1.8 m for wall mounted)

SF

 = 

 

Safety factor with a value of 0.75

**  

The required minimum room area, 

A

min

, shall also be governed by 

the safety factor margin formula below :

** not less than safety
 factor 

margin

(*)  If holder at the rear of chassis need 

to be used to prop up the unit, this 
distance shall be 65 mm or more.

 

Carry out insulation after 
checking for gas leaks and 
secure with vinyl tape.

 Vinyl tape

Remote control holder

Remote control holder fi xing screws

Remote control

Insulation of piping connections

Attaching the remote control holder to the wall

INDOOR UNIT

CONNECT THE CABLE TO THE INDOOR UNIT

2

The power supply cord, indoor and outdoor unit connection cable can be connected without removing the front grille.

Install the indoor unit on the installing holder that mounted on 
the wall.

Open the front panel and grille door by loosening the screw.

Cable connection to the power supply through Isolating Devices 
(Disconnecting means).

 

Connect the approved polychloroprene sheathed 

power 

supply cord

 3 x 2.5 mm² (2.25 ~ 2.5HP), type designation 

60245 IEC 57 or heavier cord to the terminal board, and 
connect the other end of the cable to Isolating Devices 
(Disconnecting means).

 

Do not use joint power supply cord. Replace the wire if the 
existing wire (from concealed wiring, or otherwise) is too short.

 

In unavoidable case, joining of power supply cord between 
isolating devices and terminal board of air conditioner shall be 
done socket and plug rated 16 A (2.25HP) or 20 A (2.5HP).
Wiring work to both socket and plug must follow to national 
wiring standard.

Bind all the 

power supply cord

 lead 

wire with tape and route the power 
supply cord via the left side escapement.

Connection cable

 between indoor 

unit and outdoor unit shall be approved 
polychloroprene sheathed 4 x 2.5 mm² 
(2.25 ~ 2.5HP) fl exible cord, type 
designation 60245 IEC 57 or heavier 
cord.

Bind all the indoor and outdoor 

Connection cable

 with tape and route 

the connection cable via the right side 
escapement.

Remove the tapes and connect the 
power supply cord and connection cable 
between indoor unit and outdoor unit 
according to the diagram below.

Recommended 
length (mm)

a

b

c

d

e

f

g

30

30

60

45

40

35

55

 WARNING

This equipment 
must be properly 
earthed.

Recommended 

length (mm) 

refer table below

Terminals on the outdoor unit

S1 2

3

1

2

3

Colour of wires (connection cable)

Terminals on the indoor unit

L

1

N

S1 2

3

OR

L

1

N

S1 2

3

(Power supply cord)

Connection for multi 
inverter model (Outdoor 
power supply)

Terminals on the isolating devices 
(Disconnecting means)

(L) (N)

Tape

Power 
supply 
cord

Connection cable

Tape

INSTALL THE INDOOR UNIT 

1

For indoor unit installation, please scan the matrix two-dimensional (2D) barcode and refer to the detailed manuals.

Note:

 

Isolating Devices (Disconnecting means) should have 
minimum 3.0 mm contact gap.

 

Ensure the colour of wires of outdoor unit and the terminal 
Nos. are the same to the indoor’s respectively.

 

Earth wire shall be Yellow/Green (Y/G) in colour and 
longer than other AC wires as shown in the fi gure for the 
electrical safety in case of the slipping out of the cord 
from the anchorage.

Secure fi rmly the power supply cord and connecting cable onto 
the control board with the holder.
Do not overtighten holder screw, as this may damage the holder.

Close grille door by tighten with screw and close the front panel.

a

b

c

4

d

e

f

g

6

S1

1

S1

1

Isolating Devices

Outdoor Unit

Terminal Board

Panel

Panel

Flip the panel down 

until ‘click’ sound before 

connect indoor and outdoor 

connection cable

Holder

Holder

Flip the 

panel down

Earth 

Wire 

longer 

than 

others 

AC wires 

for safety 

reason

Right escapement

Left escapement

Power supply 

cord

Indoor & outdoor 
connection cable

Earth Wire 

longer than 

others AC 

wires for 

safety reason

 Do not joint wires.

Use complete wire without joining.

Use approved socket and plug with earth pin.

Wire connection in this area must follow to national wiring rules.

WIRE STRIPPING, CONNECTING REQUIREMENT

5 mm or more

Indoor/outdoor 
connection 
terminal board

(gap between wires)

No loose 
strand when 
inserted

10 ± 1 mm

Wire stripping

ACCEPT

Conductor 

fully inserted

PROHIBITED

Conductor 

over inserted

PROHIBITED

Conductor not 

fully inserted

 

CAUTION

Do not connect power supply to indoor 
and outdoor unit at the same time.
Risk of fi re if wrong connection of power 
supply.

WARNING

RISK OF FIRE

JOINING OF WIRES 
MAY CAUSE 
OVERHEATING AND 
FIRE.

1.  Please cut using pipe cutter and then remove the burrs.
2.  Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping 

end down to avoid the metal powder entering the pipe.

3.  Please make flare after inserting the flare nut onto the copper pipes.

When properly fl ared, the internal surface of the 
fl are will evenly shine and be of even thickness. 
Since the fl are part comes into contact with the 
connections, carefully check the fl are fi nish.

 Improper  fl aring 

Inclined Surface 

damaged

Cracked Uneven 

thickness

1.  To cut

2.  To remove burrs

3.  To fl are

Bar

Red arrow mark

Handle

Core

Yoke

Clamp handle

Bar

0 – 0.5 mm

Copper pipe

Reamer

Point down

Pipe

 

Do not overtighten, overtightening may cause gas leakage.

Piping size

Torque

6.35 mm (1/4")

[18 N•m (1.8 

f•m)]

9.52 mm (3/8")

[42 N•m (4.3 

f•m)]

12.7 mm (1/2")

[55 N•m (5.6 

f•m)]

15.88 mm (5/8")

[65 N•m (6.6 

f•m)]

19.05 mm (3/4")

[100 N•m (10.2 

f•m)]

Connecting The Piping to Outdoor Multi

Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. 
Make flare after inserting the flare nut (locate at valve) onto the copper pipe. Align center 
of piping to valve and then tighten with torque wrench to the specified torque as stated 
in the table.

* For Gas side piping please refer table and diagram below

Outdoor Multi Combination Model 

Pipe size (refer 

to diagram)

CS-TZ60***

CU-3Z68***,
CU-4Z68***,
CU-4Z80***,
CU-5Z90***

(CZ-MA2PA)

CS-TZ71***

CU-4Z80***,
CU-5Z90***

(CZ-MA2PA) &

(CZ-MA3PA)

Connecting The Piping to Outdoor

Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge.
Make fl are after inserting the fl are nut (locate at valve) onto the copper pipe. 
Align center of piping to valve and then tighten with torque wrench to the 
specifi ed torque as stated in the table.

Connecting The Piping to Indoor

For connection joint of all models

Please make flare after inserting flare nut (locate at 
joint portion of tube assembly) onto the copper pipe. 
(In case of using long piping)

Connect the piping

 

Align the center of piping and suffi ciently tighten 
the fl are nut with fi ngers.

 

Further tighten the fl are nut with torque wrench in 
specifi ed torque as stated in the table.

Torque wrench

Spanner or 
Wrench

Additional Precautions For R32 Models when connecting by fl aring at indoor side

Ensure to do the re-fl aring of pipes before connecting to units to avoid leaking.

Seal suffi ciently the fl are nut (both gas and liquid sides) with neutral cure (Alkoxy type) & ammonia-free 
silicone sealant and insulation material to avoid the gas leak caused by freezing.

Neutral cure (Alkoxy type) & ammonia-free silicone sealant is only to be applied after pressure testing 
and cleaning up by following instructions of sealant, only to the outside of the connection. The aim is to 
prevent moisture from entering the connection joint and possible occurrence of freezing. Curing sealant 
will take some time. Make sure sealant will not peel off when wrapping the insulation.

Apply neutral cure 

(Alkoxy type) and ammonia-free 

silicone sealant along the 

circumference

Hall Union

Hall Union

Connection pipe 

(female side)

Pipe size expander

(CZ-MA2PA)

Auxiliary pipe

(male side)

(Indoor)

Auxiliary pipe

(male side)

(Outdoor)

Flare Nut

Hall Union

Hall Union

Connection pipe 

(female side)

Pipe size expander

(CZ-MA2PA)

Auxiliary pipe

(male side)

(Indoor)

Auxiliary pipe

(male side)

(Outdoor)

Flare Nut

Gas side

Connection pipe

(female side)

Auxiliary pipe

(male side)

Flare Nut

Hall Union

Liquid side

Cutting and Flaring The Piping

CONNECT THE PIPING

3

Required tools for Installation Works

1  Phillips screw driver
2 Level 

gauge

3  Electric drill, hole core drill (ø70 mm)
4  Hexagonal wrench (4 mm)
5 Spanner
6 Pipe 

cutter

7 Reamer
8 Knife
9  Gas leak detector
10 Measuring tape
11 Thermometer

12 Megameter
13 Multimeter
14 Torque wrench

18 N•m (1.8 k

g

f•m)

42 N•m (4.3 k

g

f•m)

55 N•m (5.6 k

g

f•m)

65 N•m (6.6 k

g

f•m)

100 N•m (10.2 k

g

f•m)

15 Vacuum pump
16 Gauge manifold

 

Please scan the above matrix two-dimensional (2D) barcode and read thoroughly for the detailed instruction.
Panasonic will not be responsible for any accident or damage due to improper installation in anyway not described in the detailed manuals. Malfunction caused by incorrect 
installation is also not covered by product warranty.

 WARNING

Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Any unfi t method or using incompatible material may cause product 
damage, burst and serious injury.
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit on veranda of a high rise building, child may climb up to outdoor unit and cross over the handrail 
causing an accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or 
over current will cause electrical shock or fi re.

Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.

Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury. 

Do not sit or step on the unit, you may fall down accidentally. 

Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing.    

   

When installing or relocating air conditioner, do not let any substance other than the specifi ed refrigerant, eg. air etc mix into refrigeration cycle (piping). Mixing of air etc. will cause abnormal 
high pressure in refrigeration cycle and result in explosion, injury etc.

Do not pierce or burn as the appliance is pressurized. Do not expose the appliance to heat, fl ame, sparks, or other sources of ignition.
Else, it may explode and cause injury or death.

Do not add or replace refrigerant other than specifi ed type. It may cause product damage, burst and injury etc.

 

For R32/R410A model, use piping, fl are nut and tools which is specifi ed for R32/R410A refrigerant. Using of existing (R22) piping, fl are nut and tools may cause abnormally high 
pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
For R32 and R410A, the same fl are nut on the outdoor unit side and pipe can be used.

 

Since the working pressure for R32/R410A is higher than that of refrigerant R22 model, replacing conventional piping and fl are nuts on the outdoor unit side are recommended.

 

If reuse piping is unavoidable, refer to instruction “IN CASE OF REUSING EXISTING REFRIGERANT PIPING”

 

Thickness of copper pipes used with R32/R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.

 

It is desirable that the amount of residual oil less than 40 m

g

/10 m.

Engage authorized dealer or specialist for installation. If installation done by the user is incorrect, it will cause water leakage, electrical shock or fi re.

For refrigeration system work, install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fi re.

Use the attached accessories parts and specifi ed parts for installation. Otherwise, it will cause the set to fall, water leakage, fi re or electrical shock.

Install at a strong and fi rm location which is able to withstand weight of the set. If the strength is not enough or installation is not properly done, the set will drop and cause injury.

For electrical work, follow the national regulation, legislation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough 
or defect found in the electrical work, it will cause electrical shock or fi re.

Do not use joint cable for indoor / outdoor connection cable. Use the specifi ed indoor/outdoor connection cable, refer to instruction 

CONNECT THE CABLE TO THE INDOOR UNIT

 and connect 

tightly for indoor/outdoor connection. Clamp the cable so that no external force will have impact on the terminal. If connection or fi xing is not perfect, it will cause heat up or fi re at the connection.

Wire routing must be properly arranged so that control board cover is fi xed properly. If control board cover is not fi xed perfectly, it will cause fi re or electrical shock.

This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD), with sensitivity of 30 mA at 0.1 sec or less. 
Otherwise, it may cause electrical shock and fi re in case of equipment breakdown or insulation breakdown.

During installation, install the refrigerant piping properly before running the compressor. Operation of compressor without fi xing refrigeration piping and valves at opened position will cause 
suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.
During pump down operation, stop the compressor before removing the refrigeration piping. Removal of refrigeration piping while compressor is operating and valves are opened will cause 
suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.

Tighten the fl are nut with torque wrench according to specifi ed method. If the fl are nut is over-tightened, after a long period, the fl are may break and cause refrigerant gas leakage.

After completion of installation, confi rm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant contacts with fi re.

Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when the refrigerant contacts with fi re.

Be aware that refrigerants may not contain an odour.

This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone.
Otherwise, it may cause electrical shock in case of equipment breakdown or insulation breakdown.

 CAUTION

Do not install the unit in a place where leakage of fl ammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fi re.

Prevent liquid or vapor from entering sumps or sewers since vapor is heavier than air and may form suffocating atmospheres.

Do not release refrigerant during piping work for installation, re-installation and during repairing refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite.

Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

Do not touch the sharp aluminium fi n, sharp parts may cause injury. 

Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture.

Select an installation location which is easy for maintenance.
Incorrect installation, service or repair of this air conditioner may increase the risk of rupture and this may result in loss damage or injury and/or property.
Power supply connection to the room air conditioner.
Use power supply cord 3 x 2.5 mm² (2.25 ~ 2.5HP) type designation 60245 IEC 57 or heavier cord.
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
1)  Power supply connection to the receptacle using power plug. 

Use an approved 16 A (2.25HP), 20 A (2.5HP) power plug with earth pin for the connection to the socket.

2)  Power supply connection to a circuit breaker for the permanent connection. 

Use an approved 16 A (2.25HP), 20 A (2.5HP) circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact gap.

Installation work.
It may need two people to carry out the installation work.

Keep any required ventilation openings clear of obstruction.

A

min

 = 

m

c

 / (

SF x 

LFL

 x 

h

0

)

The higher value shall be taken when determining 
the room area.

OR

OR

OR

Pipe size reducer

(CZ-MA3PA)

https://eu.datanavi.ac.smartcloud.panasonic.com/documents/index.htm?model=TZ60ZKE

QR code for 

Web Manual

Summary of Contents for TZ71ZKE Series

Page 1: ...ble For Gas side piping please refer table and diagram below Outdoor Multi Combination Model Pipe size refer to diagram CS TZ60 CU 3Z68 CU 4Z68 CU 4Z80 CU 5Z90 CZ MA2PA CS TZ71 CU 4Z80 CU 5Z90 CZ MA2P...

Page 2: ...o contrario podr a estallar y provocar lesiones o la muerte Consulte PRECAUCIONES PARA EL USO DEL REFRIGERANTE R32 en el manual de instalaci n de la unidad exterior para conocer m s precauciones a las...

Page 3: ...trico in funzionamento In caso contrario potrebbe esplodere e causare lesioni o morte Fare riferimento a PRECAUZIONI PER L USO DEL REFRIGERANTE R32 nel manuale per l installazione dell unit esterna pe...

Page 4: ...lopend een ontstekingsbron in gebruik is Houd het apparaat verwijderd van open vuur werkende gastoestellen of een werkende elektrische verwarmer Anders zou het kunnen exploderen en verwondingen of ove...

Page 5: ...ente Manter afastado de chamas vivas quaisquer aparelhos de g s operacionais ou qualquer aquecedor el trico operacional Caso contr rio pode explodir e provocar les es ou morte Consultar a sec o PRECAU...

Page 6: ...4 x 2 5 2 2 25 2 5HP 60245 IEC 57 6 7 a b c d e f g 30 30 60 45 40 35 55 S1 2 3 1 2 3 L 1 N S1 2 3 L 1 N S1 2 3 L N 1 2D 3 0 8 9 a b c 4 d e f g 6 S1 1 S1 1 5 p 10 1 1 2 3 1 2 3 0 0 5 6 35 1 4 18 1 8...

Page 7: ...l gaz en fonctionnement ou tout chauffage lectrique en fonctionnement Sinon il peut exploser et provoquer des blessures ou la mort R f rez vous au paragraphe PR CAUTIONS POUR L UTILISATION DU R FRIG R...

Page 8: ...te in einem gut bel fteten Raum mit einer Innenfl che gr er als Amin m siehe Tabelle A aufbewahrt installiert und betrieben werden in der es keine kontinuierlich in Betrieb befindliche Z ndquelle gibt...

Page 9: ...opreza na koje morate obratiti pa nju Primjenjivi komplet cijevi Veli ina cijevi Plin Teku ina CZ 3F5 7BP 9 52 mm 3 8 6 35 mm 1 4 CZ 4F5 7 10BP 12 7 mm 1 2 6 35 mm 1 4 CZ 52F5 7 10BP 15 88 mm 5 8 6 35...

Page 10: ...kan ayg ttan veya al an herhangi bir elektrikli s t c dan uzak durun Aksi takdirde patlayabilir ve yaralanma ya da l me neden olabilir Dikkat edilmesi gereken di er nlemler i in d nite kurulum k lavuz...

Page 11: ...30 60 45 40 35 55 mm S1 2 3 1 2 3 K L 1 N S1 2 3 L 1 N S1 2 3 L N 1 2D 3 0 mm Y G AC 8 9 a b c 4 d e f g 6 S1 1 S1 1 AC AC 5mm 10 1 mm 1 2 3 1 2 3 0 0 5 mm 6 35 mm 1 4 18 N m 1 8 f m 9 52 mm 3 8 42 N...

Page 12: ...n db t Sada p slu n ho potrub Velikost potrub Plyn Kapalina CZ 3F5 7BP 9 52 mm 3 8 6 35 mm 1 4 CZ 4F5 7 10BP 12 7 mm 1 2 6 35 mm 1 4 CZ 52F5 7 10BP 15 88 mm 5 8 6 35 mm 1 4 Redukce velikosti potrub CZ...

Page 13: ...buchu czego wynikiem mog by obra enia cia a lub mier Informacje na temat innych rodk w ostro no ci na kt re nale y zwr ci uwag znajduj si w RODKI OSTRO NO CI PODCZAS STOSOWANIA CZYNNIKA CH ODNICZEGO R...

Page 14: ...v bbi betartand vint zked sekkel kapcsolatosan tekintse meg AZ R32 ES H T K ZEG HASZN LAT RAVONATKOZ VINT ZKED SEK c m r szt a k lt ri egys g beszerel si k zik nyv ben Alkalmazhat cs k szlet Cs vezet...

Page 15: ...hn a sp sobi zranenie alebo smr al ie bezpe nostn opatrenia ktor m je potrebn venova pozornos n jdete v asti BEZPE NOSTN OPATRENIA PRI POU VAN CHLADIVA R32 v n vode na in tal ciu vonkaj ej jednotky Po...

Page 16: ...evati glejte PREVIDNOSTNI UKREPI PRI UPORABI HLADIVA R32 v priro niku za vgradnjo zunanje enote Komplet ustreznih cevi Velikost cevi Plin Teko ina CZ 3F5 7BP 9 52 mm 3 8 6 35 mm 1 4 CZ 4F5 7 10BP 12 7...

Page 17: ...mai mari de Amin m a se vedea Tabelul A i n care nu exist nicio surs de aprindere cu func ionare continu A nu l sa n apropierea surselor de flac r deschis aparatelor cu func ionare pe gaz pornite sau...

Reviews: