background image

1

Outdoor Lifestyles  •  ODMEZG-36 Installation Manual  •  4601-901  Rev. B  •  10/17

Models:

Installation Manual

Installation and Appliance Setup

INSTALLER:  Leave this manual with party responsible for use and operation.

OWNER:  Retain this manual for future reference.

NOTICE: DO NOT

 discard this manual!

In the Commonwealth of Massachusetts installation must be 

performed by a licensed plumber or gas fitter.

See Table of Contents for location of additional Commonwealth 

of Massachusetts requirements.

This appliance may be installed as an OEM 

installation in manufactured home (USA 

only) or mobile home and must be installed 

in accordance with the manufacturer’s 

instructions and the 

Manufactured Home 

Construction and Safety Standard,

 

Title 24 

CFR, Part 3280 

in the United States, or the 

Standard for Installation in Mobile Homes, 

CAN/CSA Z240 MH Series,

 in Canada.

This appliance is only for use with the type(s) 

of  gas  indicated  on  the  rating  plate.  This 

appliance is not convertible for use with other 

gases, unless a certified kit is used.

• 

DO NOT

 store or use gasoline or other flam

-

mable vapors and liquids in the vicinity of this 

or any other appliance.

•  What to do if you smell gas   

DO NOT

 try to light any appliance.

DO NOT

 touch any electrical switch. 

DO 

NOT

 use any phone in your building.

-  Leave the building immediately.

-  Immediately call your gas supplier from 

a neighbor’s phone. Follow the gas sup

-

plier’s instructions.

-  If you cannot reach your gas supplier, call 

the fire department.

•  Installation and service must be performed 

by a qualified installer, service agency, or the 

gas supplier.

WARNING: 

FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly 

could result in serious injury, death, or 

property damage. 

DANGER

HOT GLASS 

WILL 

CAUSE BURNS.

DO NOT TOUCH 

GLASS 

UNTIL COOLED.

NEVER 

ALLOW CHILDREN

 TO TOUCH GLASS

.

A  barrier  designed  to  reduce  the  risk  of 

burns from the hot viewing glass is provided 

with this appliance and shall be installed for 

the  protection  of  children  and  other  at-risk 

individuals.

ODMEZG-36

MEZZANINE

SERIES

CERTIFIED

S

AFETY

 

B

ARRIER

Summary of Contents for ODMEZG-36

Page 1: ... plate This appliance is not convertible for use with other gases unless a certified kit is used DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Leave the building immediately Immediately call your ...

Page 2: ...ion A Securing and Leveling the Appliance 13 B Installing Non Combustible Facing Material 14 C Installation Instructions for Outdoor Side 15 5 Termination Location and Vent Information A Vent Termination Minimum Clearances 17 B Chimney Diagram 18 C How to use the Vent Graph 19 D Vertical Horizontal Termination Configurations 20 E Below Grade Installations 21 F Vertical thru the roof Applicatons 22...

Page 3: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Gas Section 9 Pg 42 Proper appliance for fuel type Was a conversion performed Leak check performed and inlet pressure verified ed Verified proper air shutter setting for installation type ___________________________ ___________________________ ___________________________ ___________________________ ______________________...

Page 4: ...liance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this product must be pro tected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations s...

Page 5: ... gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage instal...

Page 6: ...ly the media must be installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal lation Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or sub...

Page 7: ...t Dimension Diagrams Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Figure 3 6 Location Inches Millimeters G 6 5 8 168 H 1 1 2 38 I 9 1 8 232 J 24 5 8 625 K 19 1 8 486 L 20 1 8 511 Location Inches Millimeters A 49 1 8 1248 B 41 1 2 1029 C 23 5 8 524 D 29 5 8 753 E 50 3 4 1289 F 37 3 4 959 Appliance Dimensions Table ...

Page 8: ...y to ensure safe installation Failure to follow instructions exactly can create a fire hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING 68 1727 mm Minimum Ce...

Page 9: ...esign preference Figure 3 5 Appliance Locations It is important to follow the framing and finishing instruc tions step by step to ensure proper placement of fireplace in the surrounding framing finishing materials 51 3 4 Refer to Section 10 for hearth mantel and wall projection information 18 1 8 51 3 4 18 1 8 Mantel Clearances NOTE The combustible area above the facing must not protrude more than...

Page 10: ... A B D HEADER DEPTH HEADER DEPTH APPLIANCE MAY BE INSTALLED OFF OF FLOOR Adjust framing dimensions for interior and exterior sheathing such as sheetrock and drywall Header depth not to exceed 3 1 2 inches If appliance is installed off of floor maintain required clearances to combustibles Construct platform in accordance with local building codes Clearances to Combustibles Follow these instructions...

Page 11: ...you MUST check local building codes to determine the requirements to these steps Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home Additional...

Page 12: ...immed from the floor appropriately to maintain 1 4 in minimum space between the floor hearth and hearth refractory The base of the fireplace may sit on a combustible sur face The area in front of the fireplace must be protected by a noncombustible hearth extension unless the fire place is raised a minimum of three inches above the com bustible floor or hearth See Figures 3 7 and 3 8 Figure 3 8 Non...

Page 13: ... secure the appliance see below Nailing tabs are provided to secure the appliance to the framing members Bend out the two nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing See Figure 4 1 Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims underneath the appliance Secure the app...

Page 14: ...the side of the fireplace See Figures 3 2 3 4 for framing and clearance details Figure 4 2 Nailing Tabs Interior Side Figure 4 3 Nailing Tabs Exterior Outdoor Side NAILING TAB SHIPPING FLANGE NAILING TAB 1 IN STANDOFF Optional Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance Figure 4 4 Install Non Combustible Facing Material B Install...

Page 15: ... used beyond 3 from the top of the flashing must be approved to a minimum of 225 F continuous exposure Special care should be taken when choosing building materials for weatherproofing i e building wraps sealant tapes liquid sealants rubberized flashings etc All sealant materials or building wraps installed within 3 of the top of the fireplace flashing must be approved to a minimum temperature of ...

Page 16: ...flashing by 3 in Metal Flashing Top of Fireplace 3 4 in Overlap from flashing Figure 4 6 Seal this seam with caulk both sides Seal along bottom edge with caulk Facing material must overlap face by at least 3 4 in Facing must NOT extend beyond this edge NOTE Seal along bottom edge and boundary of facing material with caulk Figure 4 7 ...

Page 17: ...SCHARGE OPENING 5 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe could cause overheating and fire WARNING Figure 5 2 Staggered Termination Caps Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using decor...

Page 18: ...MITTED C J B D B F B A E V V V V V V M H or i V G X V H A V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 term...

Page 19: ...ottom of the graph 3 Select the indicated dimension and position the fire place in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4 m the horizontal run to the face of the outer wall must not exceed 16 4 9 m Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system 40 38 36 34 32 30 28 26 24...

Page 20: ... finished outside wall The maximum number of 90 elbows per side wall installation is three 3 A minimum of 12 305 mm is required before a 90 elbow If a 90 elbow is fitted directly after 12 305 mm vertical section mounted to the top of the fireplace the maximum horizontal vent run before the termination or a vertical rise is 36 914 mm Figure 5 5 Maximum Three 3 90 Elbows Per Installation 3 x 90 Elbo...

Page 21: ...ace of the exterior wall See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 12 1 Establish vent hole through the wall 2 Remove soil to a depth of approximately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel Figure 5 9 3 Install vent system 4 Ensure...

Page 22: ...al plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1x45 elbows 8 5 2 6 m 2x45 elbows 7 2 1 m A minimum of an 12 3 6 m vertical rise is required Two sets of 45 elbows offsets may be used within the vertical sections From 0 to a maximum of 8 2 5 m of vent pipe can be used between elbows Figure 5 12 The maximum angular variation allo...

Page 23: ...lowed between two 45º elbows See Figure 5 13 Figure 5 14 shows the vertical and horizontal offsets for DVP elbows Figure 5 13 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A...

Page 24: ...uring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe See Section 11 A for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 5 15 Vertical terminations are measure...

Page 25: ...rizontal Run NOTICE Failure to follow these instructions will void the warranty WARNING This fireplace must be vented to the outside The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent system require a minimum of 3 clearances ...

Page 26: ...0 17 Figure 5 19 Vertical Vent Maximum Note If installing a vertical vent termination off the top of the appliance the optional exhaust restrictor may be needed V V 3 ft Min 1m 40 ft Max 13 3 m Top Vent Vertical Termination No Elbows Note Use DVP Series components only ...

Page 27: ...RNING Risk of Fire DO NOT attach elbow directly to the appliance The ODMEZG 36 requires a minimum of 12 inches of vertical venting before attaching any elbow to the appliance ODMEZG 36 V1 V2 Minimum H1 H2 Maximum 1 ft 309 mm 3 ft 2 7 m 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 6 ft 2 8 m 4 ft 1 2 m 12 ft 3 6 m 5 ft 1 5 m 15 ft 4 5 m V1 V2 H1 H2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum ...

Page 28: ...1 H2 V2 V1 WARNING Risk of Fire DO NOT attach elbow directly to the appliance The ODMEZG 36 requires a minimum of 12 inches of vertical venting before attaching any elbow to the appliance ODMEZG 36 V1 V2 Minimum H1 H2 Maximum 1 ft 309 mm 3 ft 2 7 m 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 6 ft 2 8 m 4 ft 1 2 m 12 ft 3 6 m 5 ft 1 5 m 15 ft 4 5 m V1 V2 H1 H2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum ...

Page 29: ...ermination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by non com bustible materials such as concrete a hole with diameter one inch greater than the pipe is acceptable Note Do not pack the gap with insulation Whenever a non combustible wall is penetrated the wall shield firestop is only required on one side and no heat shield is necessary Figure 6 1 Horizontal V...

Page 30: ... NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating ATTIC ABOVE A PIPE DVP A 10 in 254 mm A INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materials or insulation to...

Page 31: ...ating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Required Commercial Multi family Multi level exceeding two stories or High Rise Applications All outer pipe joints must be sealed with high temperature silicone 300º F minimum continuous exposure rating in cluding the slip section that connects directly to the hori zontal termination cap Apply a bea...

Page 32: ... slip section elbow and cap outer flues shall be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 7 6 120º Figure 7 7 Securing Vertical Pipe Sections 120º Figure 7 8 Securing Horizontal Pipe Sections C Secure The Vent Sections Verti...

Page 33: ...17 D Disassemble Vent Sections Rotate either section see Figure 7 9 so the seams on both pipe sections are aligned as shown in Figure 7 10 Pull carefully to separate the pieces of pipe Figure 7 10 Align and Disassemble Vent Sections Figure 7 9 Rotate Seams for Disassembly ...

Page 34: ...F TO LOWEST DISCHARGE OPENING Figure 7 13 Install Bolt into Brackets NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 7 12 Caulk the overlap seam of any exposed pipe sections that are located abov...

Page 35: ...nation cap shown in Figure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 15 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall th...

Page 36: ...seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 4 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For ce...

Page 37: ...Risk of Shock Replace damaged wire with type 105 C rated wire Wire must have high temperature insulation Accessories Requirements This appliance may be used with a wall switch wall mounted thermostat and or a remote control Wiring for optional Hearth Home Technologies approved accessories should be done now to avoid reconstruction Follow instructions that come with those accessories Figure 8 1 Bot...

Page 38: ...or Explosion DO NOT wire IFT controlled appliance junction box to a switched circuit Incor rect wiring will override IFT safety lockout Refer to Figure 8 3 or 8 4 IFT Wiring Diagram This appliance is equipped with an Intellifire Touch control valve which operates on a 6 volt 1 5AMP system Plug the 6 volt transformer plug into the appliance junction box to supply power to the unit OR install 4 AA c...

Page 39: ...JUNCTION BOX 110 120 VAC RF MODULE ADAPTER I S 6 PIN RED BLK ORANGE PILOT GREEN MAIN IFT RC400 REMOTE CONTROL RED BLK BRN BRN JUMPER WIRE LIGHTING HARNESS WIRE HARNESS LIGHT JOIN INCANDESANT LIGHTING BRN ACCESSORY CABLE POWER VENT OPTIONAL Figure 8 4 IntelliFire Touch Wiring Diagram withPower Vent ...

Page 40: ...onnected to the 1 2 in 13 mm control valve inlet If substituting for these components please consult local codes for compliance Fire Risk Explosion Hazard High pressure will damage valve Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig WARNI...

Page 41: ...k of Fire or Explosion Gas build up dur ing line purge could ignite Purge should be performed by qualified service technician Ensure adequate ventilation Ensure there are no ignition sources such as sparks or open flames E High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction...

Page 42: ...ical vent run Adjust air shutter for longer vertical runs See Figure 9 4 Refer to Gas Service Access instructions in Section 9 C to access the air shutter Loosen the Philips screw Air Shutter Settings NG Propane ODMEZG 36 1 4 IN No Cap Twist shutter to adjust Shutter may be open for longer horizontal vent runs Do not close the air shutter more than 1 16 in for NG or 1 4 in for propane Tighten the ...

Page 43: ... in a Vertical Tube Furnace at 750 ºC WARNING Risk of Fire Maintain specified air space clearances to combustibles Inadequate air space could cause overheating and fire NOTICE The maximum finishing material not only includes the decorative finish materials marble tile slate etc but also the thin set lath and adhesive used to attach the decorative finish material Finishing Materials This section di...

Page 44: ...f Sheetrock Cracking DO Use all purpose joint compound Use eggshell paint 100 acrylic latex paint gloss or semi gloss To Avoid Sheetrock Cracking DO NOT Use a quick set or light weight joint compound Use flat paint In extreme cases lab tests have shown yellow pigments fading out of paints over time due to heat Vent run and installation location will have an effect on wall temperature and fading If...

Page 45: ... levers Cam Levers FP2433 lift glass Figure 10 4 Remove Glass Frame DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS Un panneau vitré chaud peut causer des brûlures Laissez refroidir le panneau vitré avant d y toucher Ne laisser jamais les enfants toucher le panneau vitré A barrier designed to reduce the risk of burns from the hot viewing glass ...

Page 46: ...ight Bulbs Pilot is Located in Center Figure 10 6 Stone and Glass Placement D Glass Only Placement NOTE Three 3 bags of glass are supplied with the fireplaces It is not necessary to use the entire 3rd bag of glass provided Too much glass can cut off the proper amount of air the burner needs to burn clean This may cause sooting 1 Spread glass evenly in one layer over the entire floor and burner It ...

Page 47: ...RIER INSTALLATION INSTRUCTIONS 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 10 7 with the corre sponding slots on the firebox Figure 10 8 3 Slide the screen down into the slots until it fits secure ly in place NOTICE It is the responsibility of the installer to ensure the barrier is affixed to the fireplace at the time of instal la...

Page 48: ...ipe see chart Effective Height Length 4 7 8 in 276 mm 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop 13 mm Finished Height 19 3 4 in 502 mm UNIV AS2 Attic Insulation Shield Tab 1 in 25 4 mm 20 3 4 in 527 mm 14 IN 356 MM 14 IN 356 MM 20 IN 508 MM 12 IN 305 MM DVP RDS ROOF DECK INSULATION SHIELD 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support Pipe Effective...

Page 49: ... Effective Length Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effecti...

Page 50: ...4 in 337 mm RF12 Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield 12 IN 305 mm 7 IN 178 mm 4 15 16 IN A A A 1 2 IN 13 mm 7 ...

Page 51: ...4 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap DVP TB1 Basement Vent Cap 12 in 305 mm 1 1 2 in 38 mm 7 3 8 in 187 mm 14 in 356 mm 17 3 4 in 451 mm 6 in 152 mm 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS 10 7 8 in 276 mm 10 1 2 in ...

Page 52: ...IN 813 mm MIN 35 IN 889 mm MAX Note Use only approved termination caps with the PVI SLP See instructions included with PVI SLP kit Figure 11 5 PVI SLP Vent Components 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm SLP LPC SLP Low Profile Cap 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Basemen...

Page 53: ...to order Note The PVLP SLP requires a PVLP CK be installed on this appliance The PVLP CK is ordered separately from the PVLP SLP Contact your dealer to order Figure 11 6 PVLP SLP Vent Components PVLP HS Heat Shield 14 IN 356 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 ...

Page 54: ...LP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 15...

Page 55: ...trol with child protection lockout feature Keep remote controls out of reach of children Contact your dealer if you have questions Printed in U S A Copyright 2016 Outdoor Lifestyles a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www outdoorlifestylesproducts com Please contact your Outdoor Lifestyles dealer with any questions or concerns For the location of your near...

Reviews: