background image

923021011_09_00

4

Page

 

1

 

from

 

4

GENERAL

These  luminaires  are  used  in  places 
where  emergency  luminaires  are  needed. 
Each  luminaire  must  be  permanently 
c o n n e c t e d   t o   m a i n s   p o w e r   s u p p l y.  
Internally,  the  product  consists  of  2 
subsystems,  1  for  each  lamp.  Each 
subsystem  contains  2  batteries  that  are 
c h a r g e d   a n d   d i s c h a r g e d   a n d   a r e  
i n d e p e n d e n t   f r o m   t h e   o t h e r .
Due  to  this,  each  lamp  lights  with  its  own 
b a t t e r i e s   a n d   t h u s   d u r i n g   a   d e e p  
discharge will go OFF at a slightly different 
instance  compared  to  the  other  lamp. 
In  the  event  of  a  power  failure,  the 
luminaire  will  automatically  light  both 
lamps.  When  the  mains  power  supply  is 
restored  the  luminaire  returns  to  normal 
charging operation.

The perimeter of the TEST button contains 
a green charge indicator. When the unit is 
connected  to  the  power  supply  and  the 
batteries  are  also  connected,  the  green 
indicator  blinks  to  show  that  the  batteries 
are  charging  but  are  not  fully  charged. 
When  the  batteries  are  fully  charged  then 
the  indicator  stays  ON  continuously.  On 
every press of the TEST button and for as 
long as the test is conducted, the indicator 

w i l l   b e   O F F.   I f   t h e   b a t t e r i e s   a r e  
disconnected  the  indicator  will  also  be 
turned  OFF.  In  order  to  do  a  complete 
duration  test  please  be  sure  that  the 
indicator is continuously ON. If it is blinking 
it  is  a  sign  of  a  power  failure  and  that  the 
batteries  are  not  fully  charged.  Let  the 
batteries  charge  until  the  indicator  stops 
blinking and then conduct the duration test. 

ΑΤΤΕΝΤΙΟΝ

!!!

1. Operations for installation, maintainance 
or  testing  must  be  done  by  authorized 
personnel only

.

2.  The  device  must  be  connected  to  the 
mains  power  supply  thr

o

u

gh

  a  fuse 

dependent by the total amount of the line’s  
power load.

3. 

It is suggested to check every 6 months 

the  minimum  autononous  duration  by 
disconnecting  the  mains  power  supply

Count the time that  the lamps light and in 
case  of  less  time  than  the  minimum 
autonomous duration the batteries must be 
r e p l a c e d .   I f   t h e   m e a s u r e d   t i m e   i s  
considerably  less  than  the  minimum 
autonomous  duration 

contact  the  installer. 

Congratulations for your selection to buy this product.  

Olympia Electronics -  European manufacturers

.

WATERPROOF POWER LIGHT SERIES, NON MAINTAINED EMERGENCY LUMINAIRE 

GR-21/Η3

TECHNICAL CHARACTERISTICS

220-240V AC/50-60Hz

3 ώρες

24 

ώρες

From overcharge and deep discharge

IP 65

4

x12V/7Ah

  1380lm 

  

2

x55W (halogen

)

38W/ 47VA

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

o

5 to 40  C

Up to 95% 

Electrostatically

 

painted

 

metal plate

3 years 

(1 

year for the lamps and the battery

)

15.

71

 Kgr.

405 x 130 x 500 mm

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT
GUARANTEE 

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Pb)

CHARGING TIME

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

Reviews: