background image

Page

 1

 from

 6

923293003_09_006

GENERAL

o

This  device  is  used  indoors 

(

ta  40 C

)

  in 

places  where  emergency  luminaires  are 
needed.  Each  device  must  be  permanently 
connected to mains power supply

.

 In normal 

operation the battery is charging. In case  of 
a  mains  power  supply  failure,  the  device 
enters emergency mode and the illumination 
LED  turns  on.  When  the    mains    power   
supply is restored the device turns to normal 
operation.

Battery Charging

Battery Cut-off

To install the luminaire follow the installation 
instructions 

ο

n page 3.

INSTALLATION

The 

battery 

charging 

is 

completely 

controlled

In  this  case,  is

 

achieved  the 

perfect  battery maintenance 

as well as the 

elongation  of  its  duration

When  the  battery 

has  completely  charged

it  charges  with  a 

maintenance current.

The device in this operation when the mains 
power  supply  fails

 

and  battery  has  lost  its 

energy

During  this  operation  the  device 

enters the idle state

 

and battery consumption 

is  negligible,  in  order  to  be  protected  from 
deep discharge.

This  test  can  be  done  by  pushing  the  test 
button.  The  light  source  and  the  emergency 
circuit of the device is monitored. The manual 
test can be conducted only if the main power 
supply  and  the  battery  is  connected.  During 
this test period all indication LEDs are OFF. 

Automatic Autonomous Test

Manual

 Test

Automatic Operational Test

The Automatic Autonomous Test is conducted 
and measures the device’s back up operation 
and  emergency  duration.  The  BATTERY 
FAULT  LED  blinks  during    the  measurement, 
indicating this process to the user. This test is 
conducted  automatically  every  six  months

In 

order  to  be  performed,  the  mains  power 
supply  and  the  battery  should  be  connected 
and  fully  charged

If  the  battery  is  not  fully 

charged

the  test  is  postponed

 

until  the 

battery  is    completely  charged.  If  during  this 
test,  the  autonomy  is  less  than  the  nominal 
then  the  battery  fault  led  turned  on 
continuously  and  the  battery  must  be 
replaced. 

This  test  includes  all  the  operations  that 
provide  the  manual  test  and  is  conducted 
automatically  every  15  days.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery should be connected.        

SELF TESTING N

ON

-M

AINTAINED

 EMERGENCY CEILING MOUNTED 

LUMINAIRE

S

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT

GUARANTEE

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY (NiMh)

CHARGE TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

220-240V AC / 50-60Hz

1

.5

 hour

24 hours

Deep discharge and overcharge protection

IP40

4.8V/1.2Ah

  300lm 

  1 white

 

power LED

o

5 to 40  C

Up to 95% 

ABS/PC

3 years

 (1 

year for the battery

)

439gr.

Ø125 x 63 mm

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

Charge, lamp fault, battery fault

TEST button

4.3W / 4.7 VA

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 5)

Olympia Electronics - European manufacturer

Thank you for your trust in our products  

3 hours

  150lm 

 GR-29

0

/M

 GR-291/M

 GR-292/M

 GR-293/M

Reviews: