background image

The light source contained in this luminary shall only be replaced by the manufacturer, or his 

agent, or a similar qualified person.

NOTE! The light source is non-user replaceable.

NOTE!!

  The  installer  should  fill  in,  on  the  specification 

label, the letter 

G

 if the luminaire is used as a safety sign.

(*)

 Maintained operation: The luminaire lights its illumination source, when it is powered by the mains 

power supply or not. 
Non Maintained operation: The luminaire lights its illumination source, only in  power supply’s failure.

ADDRESS OPERATION

For  address  operations  refer  to  the  installation 
manual of the panel. Please see manual of CBS 
panel  GR-8600  for  maximum  number  of 
luminaries that can be interconnected. 

GENERAL

1.  Operations  for  installation,  maintainance  or 
testing  must  be  done  by  authorized  personnel 
only.
2.  The  device,  must  be  connected 

only

  to  the 

GR-8600 panel via its ADR line.
3.  The  user  must  set  the  address  before 
installation.  To  address  the  device  see  on  page 
3.

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

923753002_09_002

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specifications see page 1)

Operation  temperature range
Relative humidity

Construction materials
External dimensions
Typical weight
Guarantee

Mains voltage
Maximum power consumption

Degrees of cover protection
Produced in accordance with 

Light source intensity 

18-30V DC

o

-30 to 50 C

up to 95% 

3 years 

IP 54

200lm 

2.5W

ABS/PC, PC

551 gr.

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547

Page 1 from 3

LED MODULE CHARACTERISTICS

Olympia Electronics S.A

45 °C max. across the board

Manufacturer

Model Number
Voltage Range

Connections

Nominal Power

Temperature (tc)

NOTE: 

LED= Light Emitting Diode

LABELING EXPLANATION:
Z: 

Central supply  

1: 

Maintained

 (*)

C:

 Including inhibiting mode

G: 

Internally illuminated safety sign

12-14V DC

2.4W

2505195

“BAU LIGHT” SERIES ADDRESSABLE LUMINARIES FOR GR-8600 CBS

GR-750/CBS/24V/ADR/HP/LL GR-751/CBS/24V/ADR/LP/LL GR-752/CBS/24V/ADR/HP/HL GR-753/CBS/24V/ADR/LP/HL

1.5W

350lm 

Viewing distance

*15m, **17m

15m 

15m 

358 x 85 x 88 mm

358 x 125 x 88 mm

358 x 85 x 88 mm

358 x 125 x 88 mm

579 gr.

579 gr.

551 gr.

12-13.5V DC

1.1W

Non-reversible connection between main pcb and led module

35 °C max. across the board

Z 1 C

*15m, **17m

GR-750/CBS/24V/ADR/HP/LL GR-751/CBS/24V/ADR/LP/LL GR-752/CBS/24V/ADR/HP/HL GR-753/CBS/24V/ADR/LP/HL

*

15m: When the luminary is installed on a wall.

**17m: When luminary is installed on the ceiling.

Reviews: