FSI-751 Plug-in Intelligent Ionization Sensor  

Installation and Maintenance Instructions

GENERAL DESCRIPTION

Model FSI-751 is an intelligent sensor that uses a state-of-the-art ionization sensing chamber. This sensor is designed to provide open area protection and 

is intended for use with compatible control panels only. 
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (Part 

No. RA400Z).
Notifier panels offer different feature sets across different models. As a result, certain features of the FSI-751 may be available on some control panels, but 

not on others. The sensor will support either FlashScan™ or CLIP (Classic Loop Interface Protocol) mode. The possible features available in the FSI-751, 

if supported by the control unit include:
1.  The panel controls the LED operation on the sensor. Operational modes are RED blink, RED continuous, GREEN blink, and off.
2.  The remote output may be synchronized to the LED operation or controlled independent of the LEDs.
Please refer to the operation manual for the UL listed control unit for specific operation of the FSI-751.

SPECIFICATIONS

Operating Voltage Range:             

 

15 to  32 VDC

Max. Avg. Standby Current:   

300µA @ 24 VDC (one communication every 5 sec. with LED blink  enabled)

Max.  Alarm Current (LED on):  

6.5 mA @ 24  VDC

Operating Humidity Range:     

10% to 93% Relative Humidity, noncondensing

Operating Temperature Range 

0° to 49°C (32° to 120°F)

Height:                     

 

 

 

1.7 inches (43 mm) installed in B710LP Base

Diameter: 

 

 

 

6.1 inches (155 mm) installed in B710LP Base

 

 

 

 

4.1 inches (104 mm) installed in B501 Base

Weight:                     

 

 

 

3.6 oz. (102 g)

WARNING

Disconnect loop power before installing sensors.
Before installing the sensor, please refer to the 

System Smoke Detector Application Guide

.

 This manual includes detailed information on sensor spacing, 

placement, zoning, and special applications. Copies of this manual are available from Notifier. 
1. Sensor Installation
    a. Set the address on the sensor per job drawings.
    NOTE: Some panels support extended addressing. In order to set
    the sensor above address 99 on compatible systems, carefully remove the stop
    on the upper rotary switch with thumb or finger as shown in Figure 2.
    b. Insert the sensor into the base and rotate it clockwise until it drops into place.
    c. Continue to rotate the sensor until it locks into the base.

CAUTION

Dust covers are an effective way to limit the entry of dust into smoke detector sensing chambers. However, they may not completely prevent airborne 

dust particles from entering the detector. Therefore, Notifier recommends the removal of detectors before beginning construction or other dust producing 

activity. 
Be sure to remove dust covers from any sensors that were left in place during construction as part of returning the system to se  

  

2.Tamper-Resistance
    Model FSI-751 includes a tamper-resistant capability that prevents its removal from the bracket without the use of a tool. Refer to the base manual for 

details on making use of this capability.

3. After all sensors have been installed, apply power to the system.
4. See Figure 3. Test the sensor by positioning a test magnet (M02-04) against the sensor plastic in the magnet test area. The alarm level should be rec-

ognized at the panel and the LED controlled by communication command from the panel.

N500-57-00 

 

 

 

 

 

       1 

 

 

 

 

I56-1249-04R

 

 

 

 

 

Notifier 12 Clintonville Rd, Northford, CT 06472-1653, (203) 484-7161           

3

2

1

3

2

1

3

2

1

+

-

-

+

U.L. LISTED COM

P

A

TIBLE

CONTROL

 P

ANEL

CLASS A OPTIONAL WIRING

REMOTE ANNUNCIATOR

+

-

CAUTION: Do not loop wire under terminal 1 or 2.

Break wire run to provide supervision of connections.

WIRING GUIDE

Refer to the installation instructions for the plug-in base 
being used. As indicated in Figure 1, terminals for power, 
ground, and the optional RA400Z Remote Annunciator 
are included in the base. Base Models B710LP (shown 
in Figure 1) and B501 are electrically identical.
NOTE: All wiring must conform to all applicable codes, 
ordinances, regulations and to the control panel    spec-
ifications.
NOTE: Verify that all sensor bases are installed and that 
polarity of the wiring is correct at each base.