Summary of Contents for Superlink SC-WBGW256

Page 1: ......

Page 2: ...teway should be treated at an authorized treatment facility for reuse recycling and recovery and not be disposed of in the municipal waste stream Please contact the installer or local authority for more information This symbol printed on the batteries in your gateway is information for end users according to the EU directive 2006 66 EC article 20 annex II Batteries at their end of life should be d...

Page 3: ...Menu screen 19 Basic Configuration Menu screen 20 Air conditioner Cell Configuration screen 21 Air conditioner Cell Configuration File Upload Download screen 23 Network Configuration screen 25 Date and Time Configuration screen 26 Security Configuration screen 28 Authentication Configuration screen 29 Language Configuration screen 30 Pulse count DI status Check screen 31 Web Configuration Menu scr...

Page 4: ...ormed only by qualified specialists WARNING Consult your dealer or a professional contractor to install the unit Improper installation made on your own may cause electric shocks fire or break down of the unit Consult your dealer when moving disassembling or repairing the unit Never modify the unit Improper handling may result in injury electric shocks fire etc Avoid using combustible substances ha...

Page 5: ...use deformation discoloration or break down Do not use benzene paint thinner wipes etc to clean the gateway It could discolor or break down the gateway Wipe it with a piece of cloth which is squeezed tightly after wetting with diluted neutral detergent Finish up the cleaning by wiping with a piece of dry cloth Do not pull or twist the cables of the gateway It could cause break down General precaut...

Page 6: ...r using the included software WGW256Utility Internet Explorer Personal Computer for Control and Monitoring Ethernet 10Base T or 100Base TX connecting with a hub or a cross cable pulse Gateway SC WBGW256 DI1 DI3 P1 P2 P3 P4 P5 P6 P7 P8 P P P P P P P P SUPERLINK NO 1 network 2 SUPERLINK NO 2 network 2 R R R R R R CELL 0 CELL 1 CELL P 1 CELL P 2 CELL Q CELL P Indoor Unit IU 0 Indoor Unit IU 1 Indoor ...

Page 7: ... that hub If an Internet or intranet connection is used If the gateway is connected via the Internet or an intranet office LAN environment please consult with the dealer It is possible for them to arrange for connections on a charged work basis Personal computer initial configuration Configuration in the case of a private Ethernet connection Communication settings TCP IP settings in the monitoring...

Page 8: ...ity Internet Default Level Medium After clicking the Internet tab click the Default Level button Local Intranet Default Level Medium low After clicking the Local Intranet tab click the Default Level button In Privacy Default Level Medium Click the Default button If the privacy setting is set to Medium high or higher the gateway cannot be used so be sure to set the default value to Medium In Connec...

Page 9: ...8 External dimensions Model Name Label Power switch LAN Reset button Power indicator ...

Page 10: ...tion screen Network Configuration screen Date and Time Configuration screen Security Configuration screen Authentication Configuration screen Language Configuration screen Pulse count DI status Check screen WEB Configuration screen Link Configuration screen Web Configuration Menu screen Calendar Configuration screen Master Schedule Configuration screen Calendar Schedule Backup File Upload Download...

Page 11: ...r who performs control monitoring operation with the user ID and password There are differences in authority depending on the user who logs in with the following three categories of authority System Administrator Can operate all screens Control and Monitoring User Cannot operate the Configuration menu Monitoring User Is authorized to use the monitoring screen only and cannot perform any control op...

Page 12: ...e refresh interval can be set to 10 180 seconds See page 33 The characters and icons on the screen might move slightly when the screen is refreshed but this is a characteristic of Internet Explorer Overview Monitor screen Common operations in each screen 1 Displaying a different gateway when multiple gateways are connected Currently the Overview Monitor screen of the gateway on the left end is dis...

Page 13: ...he Buzzer Off button This stops the buzzer sounding on the Overview Monitor computer connected to this gateway Since the volume of buzzer sound is set on the Overview Monitor computer adjust the volume if necessary on the computer When the buzzer sounds while this screen is minimized maximize the screen and then click the Buzzer Off button When the window for another application is in front of the...

Page 14: ...Air conditioner Cell name will cause the previously opened pop up window to close and a new pop up window to open in the same place Individual Monitor screen Operation Status On At least one air conditioner is running in the Air conditioner Cell Off All air conditioners have stopped in the Air conditioner Cell The operation mode of the running air conditioner with the smallest address in the Air c...

Page 15: ...ds depending on the state of the network etc The current setting status is displayed 2 Select control command values from the pull down menus for each control item Select each control command value if necessary The setting range of the set temperature is limited as follows depending on the operation mode On Off On Off Mode Auto Cool Dry Fan Heat Fan Speed Powerful High Medium Low Set Point 16 30 d...

Page 16: ... Click the System Stop button All the air conditioners under this gateway immediately stop and are set to the Remote control Lock mode Then the screen will return to the Overview Monitor screen Even if a system stop command is received from the host computer by BACnet communication or when the contact connected to the system stop input terminal DI1 becomes closed by a fire alarm device etc it will...

Page 17: ...tact connected to the system stop input terminal DI1 is closed the stopped state cannot be released by this screen The system stop condition becomes released when the contact connected to the system stop input terminal DI1 becomes open in the state where two minutes or more has passed since the system stop condition by terminal DI1 was started Even when the system stop condition becomes released t...

Page 18: ...he Load Master button causes the schedule to be loaded from the annual calendar and Master Schedule and displayed on the screen If the Set button is then clicked the Schedule Control is set from the Master Schedule The instructions and display contents in this screen can be copied to another Air conditioner Cell or another date Select the Air conditioner Cell name and corresponding schedule date t...

Page 19: ...n advance can be displayed and edited 3 Select and input each schedule item The following items can be set as schedule items in this screen Time 00 00 23 59 1 minute intervals On Off Blank not specified On Off Mode Blank not specified Auto Heat Cool Fan Dry Fan Speed Blank not specified Powerful High Medium Low Set Point Blank not specified Depending on the operation mode it can be selected within...

Page 20: ...splayed when Configuration Menu is clicked from the menu at the top of the screen The following Configuration menus are available Basic Configuration Menu Web Configuration Menu BACnet Configuration Menu Note The BACnet function setting screen is not used Click the return button to return to the setting menu screen Configuration Menu screen ...

Page 21: ... screen The following Basic Configuration menus are available Air conditioner Cell Configuration Air conditioner Cell Configuration File Upload Download Network Configuration Date and Time Configuration Security Configuration Authentication Configuration Language Configuration Pulse count DI status Check Basic Configuration Menu screen ...

Page 22: ...r conditioners SL Addresses defines them as being in the same group Air conditioner Cell Make sure that the Air condition Cell corresponds to a remote control group An Air conditioner Cell can be defined with only one air conditioner Note The maximum number of air conditioners which can be registered in an Air conditioner Cell is 16 3 Input the Air conditioner Cell names and descriptions You can i...

Page 23: ...KX series and single split PAC series connected by a Superlink adapter Note Wrong settings may cause a significant error in the calculating results for electricity or gas 5 Click the Set button The settings are updated using the revised information Note The meter connection information and meter information WATT GAS and unit quantity per pulse of each air conditioner are set using WGW256Utility so...

Page 24: ...r Cell Configuration CELL_ NO PLACE PLACE_ SHORT SL_LINE SL_ ADDRESS KAKIN_ TYPE ABILITY P1 T1 C1 P8 T8 C8 INTERVAL C000 This room is Cell 000 Room 000 S1 U000 MULTI1 5 6 1 C001 This room is Cell 001 Room 001 S1 U001 MULTI1 7 1 1 C001 This room is Cell 001 Room 001 S1 U002 RUN STOP 7 1 1 C001 This room is Cell 001 Room 001 S1 U004 RUN STOP 14 1 How to interpret the above table Items are as follows...

Page 25: ...gateway turn on the power again and upload the file without 1 In the Basic Configuration Menu screen click Air conditioner Cell Configuration File Upload Download See page 20 Air conditioner Cell Configuration File Upload Download screen To download 2 Select a file format to download 3 Click the Download button Specify the save destination and then save the file CSV PACinfo256 csv file will be sav...

Page 26: ...ill not be able to access the gateway anymore 2 2 If necessary input the Default Gateway IP address Note Consult with the network administrator to determine if a Default Gateway setting is necessary or not 3 Select the Superlink version New or Previous 4 Click the Set button Note The gateway will be rebooted automatically when the Set button is clicked After that the gateway cannot be accessed for...

Page 27: ...ration Menu screen click Date and Time Configuration See page 20 In the initial screen the gateway s current time is set in the time input column Date and Time Configuration screen 2 Select the Time zone Time difference from UTC of the area where the gateway is used Caution Be sure to set the Time zone If the Time zone is not set correctly the gateway s clock will be set to the wrong time For Manu...

Page 28: ...e 5 Click the Set button Note The time is refreshed automatically once every 2 seconds but there is a variance of several seconds The time needed for a refresh screen may take several seconds Leap year processing is also executed automatically A significant change in the time may affect the calculating data The gateway will be rebooted automatically when the Set button is clicked After that the ga...

Page 29: ...actory so any computer with any IP address can access the gateway However if even one IP address is entered in this screen for which access is permitted the gateway can be accessed from only the computer with that address 1 In the Basic Configuration Menu screen click Security Configuration See page 20 2 Input the IP address of the computer for which access is permitted 3 Click the Set button Secu...

Page 30: ...1 In the Basic Configuration Menu screen click Authentication Configuration See page 20 2 Input the User ID and Password of each Authentication See page 10 Input the User ID using 4 16 one byte alphanumeric characters and the Password using 6 16 one byte alphanumeric characters 3 Click the Set button Authentication Configuration screen ...

Page 31: ...se turn off the power of this gateway turn on the power again and upload the file without 1 From the Basic Configuration Menu screen click Language Configuration See page 20 Language Configuration screen To download 2 Select Download language file or Download factory language file 3 Click the Download button The language xml file will be saved To upload 4 Click the Browse button and select the lan...

Page 32: ...Basic Configuration Menu screen click Pulse count DI status Check See page 20 When the Reset button is clicked the display value of the pulse number becomes 0 This screen is a test screen for checking the operation of the terminals and resetting the number of pulses displayed does not affect information calculated internally at all Click the BACK button to return to the Basic Configuration Menu sc...

Page 33: ...cked on the Configuration Menu screen The following Web Configuration menus are available WEB Configuration Link Configuration Calendar Configuration Master Schedule Configuration Calendar Schedule Backup File Upload Download Accounting File Download Accounting Period Time Web Configuration Menu screen ...

Page 34: ... at 30 seconds at the factory Note The maximum delay time from the time the air conditioner s status changes until the change is reflected on the computer screen is virtually decided by this setting If the time set for this interval is short there may be some flickering on the screen from the web browser so it is recommended that the refresh time be set at about 30 seconds 3 When using the alarm b...

Page 35: ...e Gateway Name and IP Address together as a set It is possible to input Linkage Gateway Name with up to 16 one byte characters Enter the IP address using one byte numerals and The order of the text boxes to be inputted corresponds to the display position in the link tab menu Be sure to include the currently logged in gateway The gateway recognizes the input name as its own Link Name when the input...

Page 36: ... of the week Holiday Special Day 1 Special Day 2 Date for setting a special Master Schedule regardless of which day of the week it is When setting individual days one by one select Weekday Holiday Special day 1 or Special day 2 from the pull down menus 4 Click the Set button Note If you jump to the screen for another month without clicking the Set button or if you click the Undo button all the con...

Page 37: ...Configuration See page 32 In the initial screen the Monday of the Air conditioner Cell with the lowest number is displayed in the Air conditioner Cell column on the left side of the screen Master Schedule Configuration screen 2 Select the Air conditioner Cell Name and the Schedule date The display will change to the corresponding Master Schedule Configuration screen 3 Select and input the desired ...

Page 38: ...Master Schedule is changed it has no influence on the current Schedule Control The Master Schedule can be copied to another Master Schedule Select the Air conditioner Cell name and desired schedule date of the destination then click Copy When ALL is selected the settings are copied to all the Air conditioner Cells In some models of air conditioners it is not possible to set and display POWERFUL Ev...

Page 39: ...ad Download screen To download 2 Click the Download button 3 Specify the saving address and save The file schedule256 tgz is saved To upload 4 After clicking the Browse button select the file to upload Note Since a schedule backup file is a binary file special to the gateway the downloaded file cannot be edited and uploaded 5 Click the Upload button Note After the upload of a schedule backup file ...

Page 40: ...r reset manually 1 From the Web Configuration Menu screen click Accounting File Download See page 32 Accounting File Download screen 2 Click the Download button of the Accounting configuration file Download Configure the Air conditioner Cell before the download See page 21 3 Click the Download button of the Accounting data file Download Click the enabled not grayed out Download button The latest d...

Page 41: ...mon to all air conditioners The time period for the in time is configured on this screen The time period other than this configuration is calculated as the out time 1 From the Web Configuration Menu screen click Accounting Period Time See page 32 Accounting Period Time screen 2 Input the time The input ranges are as follows Hour 0 24 24 hour indication Minute 0 59 1 minute intervals 3 Click the Se...

Page 42: ...ore The pop up window cannot be seen After a pop up window opens up to display an individual monitoring screen if you click the Overview Monitor screen window in the background the individual monitoring screen will be hidden Select the pop up window again by clicking the button in the taskbar at the bottom of the screen or select the desired individual monitoring screen from the Overview Monitor s...

Page 43: ...dealer In such cases there will be a fee for relocation Repairs after the free service warranty period Consult your dealer Warranty period is one year from installation It will be charged when repair is required after the period Please consult your dealer Questions For after sales service consult your dealer Dealer Information Please fill in the following information for the after sales service De...

Page 44: ......