background image

 

 

 

Designing, Manufacturing and Supplying WB Series Electric Isolated Sensor and Digital 

Electrical Transducer since 1989 

 

 

 

USER MANUAL 

WBV415S01 AC voltage transducer 

TRUE RMS

 

 

   

 

 

www.wb-my.com

[email protected]

Technical Service: 86 816 2778271 

Quality Complain: 86 816 2278273 

Fax Line: 86 816 2281934 

 
 
 
 

ISO9001 ISO14000 ISO18000 

Certified 

 

Quality Warranty 

Any quality problem found in WB series products, we offer 

Three years free charge of repair the products, and six months guaranteed free charge of change and return the 

products. 

 

 

 

 

 
 

Summary of Contents for WBV415S01

Page 1: ...ucer TRUE RMS www wb my com wblch wbdz cn Technical Service 86 816 2778271 Quality Complain 86 816 2278273 Fax Line 86 816 2281934 ISO9001 ISO14000 ISO18000 Certified Quality Warranty Any quality problem found in WB series products we offer Three years free charge of repair the products and six months guaranteed free charge of change and return the products ...

Page 2: ... The operating manual for the equipment gives instructions for its installation commissioning and operation However the manual cannot cover all conceivable circumstances or include detailed information on all topics In the event of questions or specific problem do not take any action without proper authorization Contact the appropriate WB technical sales office and request the necessary informatio...

Page 3: ...t or electric circuit The product has certain advantages of total galvanic isolation between input and output high accuracy low drifting by temperature and wide temperature bearable range etc Function realization schematic drawing In 4 6 5 3 Mianyang Weibo Electronics Co Limited No 7 Road 2 of Xianren Road Youxian District Mianyang City P R China Tel 86 816 2971265 Fax 86 816 2281934 www wb my com...

Page 4: ...nput 9 Responding Time 300mS 10 Over Load Capacity 2 times of nominal input continuous 11 Maximum Load 5mA 12 Static Current 20mA 13 Auxiliary Power 12VDC or 24VDC optional 14 Isolation Voltage 2500Vdc for 1 minute 15 Output Ripple 40mV root mean square value output load is 250Ohm 16 Drifting by Temperature 200 10 6 17 Case Protection and Material IP20 Flame Retarded ABS Conform to UL94V 0 18 Mean...

Page 5: ... 10mV and multiple converters can share with one set auxiliary power together 3 Basic testing method for accuracy 1 According to the terminal definition table to connect the testing circuit 2 The testing must to be done by under the following conditions Auxiliary power 24V 1 ripple 5mV Ambient temperature 25 2 Relative humidity RH 45 75 Accuracy for Signal Power Source instrument 0 05 Signal Power...

Page 6: ...p and fall of the product 4 If the product has been using under the environment with strong magnetic field interference please pay attention to the shield of input wire and the output signal wire should be as short as possible For product intensive installation the space between each product should not be smaller than 10mm 5 Only use identified terminals 6 There is no lightening strike prevention ...

Reviews: