background image

Page 1

Instruction Manual

I n s t a l l a t i o n   •   O p e r a t i o n   •   M a i n t e n a n c e

Voltage Regulator

 

hanada technology Co.,Ltd.
Tel: +86 577 86065765
Fax: +86 577 56854565
Email: 

[email protected]

www.hnd-avr.com

Marthon AVR SE350

Summary of Contents for AVR SE350

Page 1: ...age 1 Instruction Manual I nst alla tio n Operation Maintenance Voltage Regulator hanada technology Co Ltd Tel 86 577 86065765 Fax 86 577 56854565 Email sale hnd avr com www hnd avr com Marthon AVR SE350 ...

Page 2: ...SE350 VOLTAGE REGULATOR INSTRUCTION MANUAL ...

Page 3: ...ostat Frequency Compensation Adjustable Roll off frequency 54 61 Hz for 60 Hz 45 51 Hz for 50 Hz Operation Weight6 5 oz Operating Temperature 40 C to 60 C Storage Temperature 65 C to 85 C Power Dissipation 8 watts maximum Size 3 94 L X 2 66 W X 2 20 H Voltage Buildup Internal provisions forautomatic voltage build up from generator residual voltage as low as 10 Vac EMI Suppression Internal Electrom...

Page 4: ... rear face of the voltage regulator EXCITER POWER CIRCUIT Connect the regulator wire F to the generator F or Fl field terminal Connect the regulator wire F to the generator F or F2 field terminal See Figure 2 for typical connection diagram SENSING POWER INPUT CIRCUIT Input power and sensing is achieved through terminals 3 and 4 The voltage input requirement of the SE350 is 190 to 240 Vac See Figur...

Page 5: ... Increasing the stability increases the response time of the generator Conversely decreasing the stability decreases the response time of the generator V HZ ROLL OFF FREQUENCY SELECTION The roll off point is the frequency where the generator voltage starts to decrease This reduces the Kilowatt load to the engine which allows the engine to recover in speed under any load transient condition Use jum...

Page 6: ...t upon connection If it does not build up refer to field flashing section in generator manual Slowly adjust the voltage control until the generator voltage reaches the nominal value If used adjust the remote voltage rheostat to set the generator voltage to the exact value desired Turn the stability adjust counter clockwise until instability is shown on either of the voltmeters mentioned in the PRE...

Page 7: ...s adjust turned down Remote voltage adjust is turned down Defective regulator Check wiring diagram for proper connections Rotate voltages adjust CW until desired voltage is reached Rotate remote voltages adjust CW until desired voltage is reached Replace regulator Output Voltage High Voltages adjust turned too high Remote voltage adjust is turned too high Rotate voltages adjust CCW until desired v...