Summary of Contents for CM-E1

Page 1: ...1 ...

Page 2: ...2 Macurco Security Series Detectors ...

Page 3: ...3 CM E1 Carbon Monoxide Detector ...

Page 4: ...o a wall using the supplied rear housing or flush mounts in a 2 x 4 x1 1 2 inch deep single gang switch or handy electrical box Can be Field Tested with Carbon Monoxide Gas 900 square feet coverage The CM E1 is a low voltage detector of Carbon Monoxide The CM E1 is designed for connection to UL Listed Fire Alarm Burglary Control Panels The CM E1 is intended for non hazardous locations such as resi...

Page 5: ...Gas and Vapor Detector and Sensors Tested to UL 2075 using UL 2034 Sensitivity limits for carbon monoxide gas The usual sources of Carbon monoxide are defective heat sources such as furnaces or wood burning stoves and automobiles running in adjoining garages The CM E1 can detect CO from these sources as well as any other sources of CO CM E1 Carbon Monoxide and Hydrocarbon Fuels ...

Page 6: ...s mild effects that are often mistaken for the flu These symptoms include headaches dizziness disorientation nausea and fatigue Carbon monoxide is colorless odorless gas resulting from the incomplete combustion of hydrocarbon fuels Carbon monoxide interferes with blood s ability to carry oxygen to the body s tissues and results in numerous adverse health effects CM E1 Carbon Monoxide and Hydrocarb...

Page 7: ... 1 2 hours life threatening after 3 hours 800 ppm Dizziness headache nausea after 45 minutes unconscious after 1 hour death within 3 hours 1 600 ppm Dizziness headache nausea after 20 minutes death within 2 hours 3 200 ppm Dizziness headache nausea after 10 minutes death within 60 minutes 6 400 ppm Dizziness headache nausea after 1 2 minutes death within 30 minutes 12 800 ppm Instantaneous effects...

Page 8: ... after 60 to 240 minutes 150 ppm of CO after 10 to 50 minutes 400 ppm of CO after 4 to 15 minutes The CM E1 continuously monitors the ambient air at the sensor If the CM E1 measures levels of CO greater than the danger level the RED light will turn on the Alarm Relay will switch to actuate the alarm circuits in the control panel and the buzzer on CM E1 will sound CM E1 Carbon Monoxide and Hydrocar...

Page 9: ... for 4 to 5 seconds Wait for a few seconds The LED should blink Green rapidly and the buzzer should double beep every 15 seconds Pass Press the button once to return to normal mode The CME1 FTG is an 11L 500 ppm Aerosol Carbon Monoxide Field Test Gas This field test gas allows installers to do a Functional Test of the CO sensor The flow rate of the CME1 FTG is 10 LPM providing enough gas to quick ...

Page 10: ...10 GD 2B Combustible Gas Detector ...

Page 11: ...the supplied rear housing or flush mounts in a 2 x 4 x1 1 2 inch deep single gang switch or handy electrical box Can be gas tested by directing gas from an unlit butane cigarette lighter into the detector through the vent holes 900 square feet coverage The GD 2B is a low voltage electronic detector of combustible heating type gases designed for connection to Fire Alarm Burglary Control Panels This...

Page 12: ... switch conducts internal tests and actuates alarm relay Solid State Electronic sensors no maintenance or recalibration Can be self restoring or latching Optional Buzzer Produces repeating loud tone bursts during alarm and chirps if sensor trouble is found Gas boilers furnaces water heaters clothes dryers fireplaces and stoves are usual sources of gas leaks The GD 2B can detect gas from these sour...

Page 13: ...13 GD 2A Combustible Gas Detector ...

Page 14: ...as tested by directing gas from an unlit butane cigarette lighter into the detector near the left hand side through one of the vent holes 900 square feet coverage The GD 2A is a low voltage electronic detector of combustible heating type gases designed for connection to UL Listed Fire Alarm Burglary Control Panels This product is for use in ordinary indoor locations of family living units and offi...

Page 15: ...arm set point 25 LEL Can be self restoring or latching The three part plastic case allows the GD 2A to be either surface mounted or installed over a four inch square or double gang electrical box providing a near flush mount Gas boilers furnaces water heaters clothes dryers fireplaces and stoves are usual sources of gas leaks The GD 2A can detect gas from these sources as well as any other sources...

Page 16: ...in air of 2 2 to 9 5 The rotten egg smell of Propane gas is an odorant called Mercaptan added to aid in leak detection Propane gas is heavier than air and may accumulate in basements crawl spaces ditches or along floors Propane also known as Liquefied Petroleum LP gas is fuel for many homes businesses private and municipal vehicle fleets school buses taxis forklifts and other indoor industrial veh...

Page 17: ...utane and pentane The rotten egg smell of Methane gas is an odorant called Mercaptan added to aid in leak detection Natural Gas and Methane are lighter than air and may accumulate high in a room or building Sources of Methane gas include Landfills from the decomposition of wastes livestock and manure management Natural Gas utilities or Natural Gas powered vehicles and maintenance facilities ...

Page 18: ...18 HD 11 Hydrogen Gas Detector ...

Page 19: ...recting gas from an unlit butane cigarette lighter into the detector near the left side through the vent holes Alarm set point 10 LEL hydrogen gas Can be self restoring or latching The HD 11 is a low voltage electronic detector of Hydrogen gas The HD 11 is designed for connection to Fire Alarm Burglary Control Panels The HD 11 is intended for installation in buildings in non hazardous locations wh...

Page 20: ...rns readily in air over a wide range of concentrations from 4 to 75 by volume Hydrogen gas is lighter than air and may accumulate high in a room or building Sources of Hydrogen include battery charging stations for golf carts forklifts or automobiles battery back up in IT rooms or telecommunication towers and fuel cell or hydrogen powered vehicles and maintenance facilities ...

Page 21: ...ntrations in ventilation ducts Plug in Power Supply PS 12 120VAC to 12VDC transformer CM E1 Adaptor Kit 2 Gang to Single Gang Adaptor Plate Kit CM 15 15A to CM E1 Conversion or GD 2A to GD 2B Conversion CME1 PCA Wire Harness Replacement 6 conductor pigtail cable for use with the CM E1 Carbon Monoxide Detector ...

Page 22: ...22 Macurco Gas Detection Products Any Questions Thank you for your time and attention ...