background image

Prior to installation, read the entire instructions

WARNING 

Risk of fire or electric shock. 

LED Retrofit Kit installation requires 
knowledge of luminaires electrical systems. 
If not qualified, do not attempt installation. 
Contact a qualified electrician.

WARNING 

Risk of fire or electric shock. 

Install this kit only in the luminaires that 
have the construction features and 
dimensions shown in the photographs 
and/or drawings and where the input 
rating of the retrofit kit does not exceed 
the input rating of the luminaire.

WARNING 

To prevent wiring damage or 

abrasion, do not expose wiring to edges of 
sheet metal or other sharp objects.

Installation Instructions LED-8929***-HAZ

& LED-8929***C-HAZ

Make all electrical connection according to 
national and local codes.

Installers should not disconnect existing wires 
from lampholder terminals to make new 
connections at lampholder terminals.  Instead 
installers should cut existing lampholder lead 
away from the lampholder and make new 
electrical connections to lampholder lead 
wires by employing applicable connectors.

This retrofit kit is accepted as a component of 
a luminaire where the suitability of the 
combination shall be determined by 
authorities having jurisdiction.

Luminaire Fittings Reference Table

Luminaire 

Fitting

Page Number

GE Lighting Filtr-

Gard®

2

Crouse-Hinds 

Champ® VMV 

4

Appleton 

Mercmaster® III 

6

Appleton 

Mercmaster® II 

8

WARNING 

Do not make or alter any open 

holes in an enclosure of wiring or electrical 
components during kit installation.

1

Included with the kit:
1. LED lamp
2. Label for modified luminaire
3. Instructions
4. Wire connectors (2)

Input Rating:
Voltage: 120-277 VAC or 347VAC for C-HAZ
Frequency: 50/60Hz
Wattage: 24W

Summary of Contents for LED-8929***-HAZ Series

Page 1: ...and local codes Installers should not disconnect existing wires from lampholder terminals to make new connections at lampholder terminals Instead installers should cut existing lampholder lead away from the lampholder and make new electrical connections to lampholder lead wires by employing applicable connectors This retrofit kit is accepted as a component of a luminaire where the suitability of t...

Page 2: ...D 8929M HAZ 2 1 Disconnect electrical power to the luminaire at the supply source CAUTION Risk of burn allow luminaire and lamp to cool before proceeding 3 Allow the ballast cover to hinge open and disconnect the quick disconnect between the cover and housing by pulling the two black plastic connectors apart 4 Cut the black and white wires from the quick disconnect to the ballast circuitry leaving...

Page 3: ...D 8929 HAZ LED 8929 C HAZ Quick disconnect 3 Lamp Installation 8 Remove the optical assembly covering the lamp such as guards globes or reflectors by un threading 9 Remove old lamp 10 Firmly tighten LED lamp enough to depress the center contact of the lamp holder 11 Replace the optical assembly by threading into the ballast housing 12 Apply the silver adhesive label over the current label on the l...

Page 4: ...te The luminaire does not need to be removed from the mounting surface prior to modification Retrofit Kit Selection Table Ballast Housing Retrofit Kit VMVS050 VMVM070 VMVM100 LED 8929E HAZ LED 8929E C HAZ All Others LED 8929M HAZ LED 8929M C HAZ Champ is a register trademark of Eaton s Crouse Hinds 4 1 Disconnect electrical power to the luminaire at the supply source CAUTION Risk of burn allow lum...

Page 5: ...l assembly by threading into the ballast housing 13 Apply the silver adhesive label over the current label on the luminaire which specifies the replacement lamp and where it will be visible during re lamping 14 Re connect electrical power to the luminaire at the supply source Example Globe and Guard 5 Remove the wire connectors from the lamp holder wires 6 Using the included wire connectors connec...

Page 6: ...n Retrofit Kit Selection Table Ballast Housing Retrofit Kit MLBG MLBR LED 8929E HAZ LED 8929E C HAZ KPB KPBR LED 8929M HAZ LED 8929M C HAZ Mercmaster is a registered trademark of Appleton Grp LLC 6 1 Disconnect electrical power to the luminaire at the supply source CAUTION Risk of burn allow luminaire and lamp to cool before proceeding 3 Allow the ballast cover to hinge open 4 Remove the wire conn...

Page 7: ...lamp and where it will be visible during re lamping 14 Re connect electrical power to the luminaire at the supply source Example Globe and Guard 5 Remove the wire connectors wire nuts from the lamp holder wires These wires might be bundled together with other wires so carefully trace the wires from the lamp holder Discard the additional white wire if any 6 Using the included wire connectors wire n...

Page 8: ...emoved from the mounting surface prior to modification Retrofit Kit Selection Table Ballast Housing Retrofit Kit LPB 4 height housing only LED 8929M HAZ LED 8929M C HAZ Mercmaster is a registered trademark of Appleton Grp LLC 8 1 Disconnect electrical power to the luminaire at the supply source CAUTION Risk of burn allow luminaire and lamp to cool before proceeding 3 Allow the ballast cover to hin...

Page 9: ...ple Globe and Guard Wire connectors Wire nuts Ballast Bracket Lamp holder wires 5 Locate the wire tie and cut it separate the wiring from the bundle Remove the wire connectors wire nuts from the lamp holder wires Discard the additional white wire if any The lamp holder wires are black and white and come from under the ballast on the hinge side of the ballast housing The ballast is under the bracke...

Page 10: ...SSEMENT Ne percez et ne modifiez aucun trou ouvert dans un boîtier de composants de câblage ou de composants électriques pendant l installation de la ensemble AVERTISSEMENT Pour éviter l endommagement ou l abrasion du câblage ne l exposez pas aux bords tranchants des feuilles de métal ou à d autres objets tranchants Effectuez toutes les connexions électriques conformément aux codes nationaux et lo...

Page 11: ...difié 1 Débrancher l alimentation électrique du luminaire à la source d alimentation ATTENTION Risque de brûlure laisser refroidir le luminaire et la lampe avant de continuer Câblage 2 Ouvrir le luminaire en desserrant la vis qui maintient le boîtier du ballast et couvrir 3 Laisser le couvercle du ballast s ouvrir et déconnecter le débranchement rapide entre le couvercle et le boîtier en tirant su...

Page 12: ...st et le couvercle en serrant la vis Installation de la lampe 8 Retirez l ensemble optique recouvrant la lampe tel que les protections les globes ou les réflecteurs en les dévissant 9 Enlever la vielle lampe 10 Serrer fermement la lampe LED suffisamment pour appuyer sur le contact central du supporte de lampe 11 Remplacez l ensemble optique en le vissant dans le boîtier du ballast 12 Appliquer l é...

Page 13: ...ier de luminaire ballast HID Crouse Hinds Champ VMV homologué UL pour utilisation dans les zones dangereux de Classe I Division 2 Groupes A B C et D Tableau de sélection du ensemble de conversion Outils nécessaires 1 Tournevis à fente ou une clé pour ouvrir la couverture Remarque L appareil n a pas besoin d être retiré de la surface du mur avant d être modifié 1 Débrancher l alimentation électriqu...

Page 14: ...charnière du couvercle Fermer et fixer le boîtier du ballast et le couvercle en serrant la vis Installation de la lampe 9 Retirez l ensemble optique recouvrant la lampe tel que les protections les globes ou les réflecteurs en les dévissant 10 Enlever la vielle lampe 11 Serrer fermement la lampe LED suffisamment pour appuyer sur le contact central du supporte de lampe 12 Remplacez l ensemble optiqu...

Page 15: ...n Grp LLC 15 3 Laisser le couvercle de ballast s ouvrir 4 Retirez les connecteurs de câble des câbles entrants câbles qui fournissent l alimentation du système de conduit au circuit de ballast Si le luminaire est équipé d un fusible et d un porte fusible installé sur la hotte de montage le fil d entrée raccordé au fusible devra être déconnecté pour éviter le fusible Jetez tous les fusibles Veillez...

Page 16: ...e lampe 7 Terminer les câbles non utilisés des étapes 4 et 5 avec les connecteurs de fils enlevés à chaque étape 8 Placer l axe de charnière du boîtier du ballast sur la charnière du couvercle Fermer et fixer le boîtier du ballast et le couvercle en serrant la vis Exemple Globe et Garde Installation de la lampe 9 Retirez l ensemble optique recouvrant la lampe tel que les protections les globes ou ...

Page 17: ...UL pour utilisation dans les zones dangereux de Classe I Division 2 Groupes A B C et D Tableau de sélection du ensemble de conversion Outils nécessaires 1 Tournevis à fente 2 Clé à molette Remarque L appareil n a pas besoin d être retiré de la surface du mur avant d être modifié Câblage 1 Débrancher l alimentation électrique du luminaire à la source d alimentation ATTENTION Risque de brûlure laiss...

Page 18: ...t la lampe LED suffisamment pour appuyer sur le contact central du supporte de lampe 12 Remplacez l ensemble optique en le vissant dans le boîtier du ballast 13 Appliquer l étiquette adhésive argent sur l étiquette actuelle sur le luminaire qui spécifie la lampe de remplacement et où il sera visible lors de la re lampe 14 Connectez l alimentation électrique au luminaire à la source d alimentation ...