background image

Product Specification Sheet

page 1

11/02 (Rev. 0)

L

IQUI

-

TECT®

 410

Point Leak Detection Sensor

Description 

The Liqui-tect 410 

(LT410) provides a 

single-point detection 

of leaks. The point 

detection sensor has 

two gold-plated 

sensing probes to 

prevent corrosion 

resistance and to 

provide accurate 

readings. The LT410 

constantly monitors 

points for leaks, 

internal faults and power failures and warns of any 

abnormal conditions. Mounting brackets allow for 

sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under 

a raised computer floor or air conditioning drip pans. 

Two independent outputs provide added flexibility 

with the capacity to signal both a local alarm panel 

and a remote building management system or external 

equipment, such as motorized water shut-off valves.
The LT410 is also ideally suited for the following:

Placement on Subfloor 

Under Cooling Support Equipment 

Specifications  

Dimensions-Top, Front & Side Views

Wiring Interconnections 

Ordering Information 

Applications

Locations

• Glycol, Chilled 

Water Cooling

• Humidification 

Feed Water Piping

• Condensate Pumps 

and Drains

• Unit and Ceiling 

Auxiliary Drip Pans

• Overhead Piping 

Troughs

• Large-Scale Network Control 

Centers

• Data Centers
• Server Rooms - Closets
• Unattended Remote Shelters
• Mechanical Equipment Rooms
• Sensitive Areas With 

Overhead Piping

• Industrial Process Control 

Rooms

* Output connections to external alarm monitoring panels

such as the Liebert contact closure alarm panels

Leak detection 

zone (directly 

beneath unit)

To a Liebert

environmental

unit and

an optional*

monitoring

panel

To external 

power 

supply or 

directly 

from 

unit

LT410

Liqui-tect 410 Sensor

Power requirements

24 VAC 100 mA, 50/60 Hz, 3 VA (max.)

Dimensions

W x D x H

6.35" x 2.25" x 4.46"

(161.2 mm x 57.2 mm x 113.2 mm)

Weight (assembled)

2.0 lbs (0.9 kg)

Metal enclosure

NEMA 1, IP 30

Environmental Conditions

Operating temperature

50°F to 104°F (10°C to 40°C)

Operating humidity

10% to 95% relative humidity

(non-condensing)

Operating altitude

0 to 10,000 ft (0 to 3,048 m)

Output Relays

Contact rating

2 Form-C; 3 A rating at 24 VAC

Agency Listings

UL

UL916

C-UL

C22.2, No. 205-M1983

CE

Yes

FCC Compliance

47 CFR, Part 15

Red Wires

Orange Wires

Yellow Wires

24 V, AC/DC

@0.10A, 50-60Hz, DC

Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

Product 

Number

Quantity

Description

LT410

Point Leak Detection Sensor

5.85"

(148.5mm)

TOP VIEW

Form-C relay 

outputs & 

power wiring 

connection

4.46"

(113.2mm)

FRONT VIEW

Adjustable 

probe height

0.0–0.5"

(0.0–12.7mm)

2.25"

(57.2mm)

SIDE VIEW

6.35"

(161.2mm)

Shipping weight: 2 Ibs (0.9 kg)

Mounting holes: #8 screws

Po

w

er

Po

w

er

1-

N

O

1-

N

C

1-

C

O

M

2-

N

O

2-

N

C

2-

C

O

M

Gold-plated 

probes

Height adjustable

0-0.5" (0-12.7mm)

Reviews: