UL 1449 second edition clamping data

Voltage 

L-N 

L-G 

L-L 

N-G 

100-120V 400 400 800 400 

208V  

800 

800 

 

230-277V 800  800  1500 700 

347V 1200 

1000 

2000 

1000 

400-480V   1500 

1500  

600V  

2000 

2000 

 

Liebert Active Tracking Filter System

Technical Specification 

 

Operating Voltage Range

......................................... +/-15% 

 

Fault Current Rating (AIC)

........................................ 200 kAIC 

 Operating 

Frequency 

Range

.................................... 47 – 63 Hz 

 50 

 EMI/RFI Attenuation: 

 

 

Normal Mode .............................................. 10 kHz-500MHz  60 dB 

 

 

Common Mode ........................................... 10 kHz-500MHz   50 dB

 

 Response 

Time

......................................................... <0.5 ns 

 Operating 

Humidity

................................................... 0% to 95% 

 Status 

Indication

....................................................... LEDs, Dry Contacts, Audible Alarm, 

   

 

Surge 

Counter 

 Certifications

............................................................. UL 1449 & 1283, CSA 

 Enclosure 

.................................................................. NEMA 12 standard 

 Warranty 

.................................................................... 10-Years Parts / 5-Years Labor  

 Optional 

Equipment

.................................................. Dual Surge Counter,  

   

Remote 

Monitor 

Panel

 

Dimensional data in inches and shipping weight in pounds 

Model/Configuration 

Dimensions in inches 

Wt 

 

Lbs 

30A Single Phase 

20.0 

16.0 9.0  21.25  10.0 .44  35 

30A Split or Three Phase 

24.0 20.0 9.0  25.25 14.0 .44  60 

60A Single Phase 

20.0 

16.0 9.0  21.25  10.0 .44  35 

60A Split or Three Phase 

24.0 20.0 9.0  25.25 14.0 .44  60 

100A Single Phase 

24.0 

20.0 9.0  25.25  14.0 .44  60 

100A Split or Three Phase 

30.0 24.0 9.0  31.25 18.0 .44  80 

225A Single Phase 

24.0 

20.0 9.0  25.25  14.0 .44  60 

225A Split or Three Phase 

30.0 24.0 9.0  31.25 18.0 .44  80 

400A Split or Three Phase 

48.0 36.0 12.0 49.25 30.0 .44  300 

800A Split or Three Phase 

60.0 

48.0 

12.0 

530 

1200A Split or Three Phase 

60.0 

48.0 

20.0 

750 

2000A Split or Three Phase 

60.0 

48.0 

20.0 

950 

4000A Split or Three Phase 

60.0 

48.0 

20.0 

1300 

Nominal 

Voltage Codes 

120 

120V 

208 

208V 

220 

220V 

230 

230V 

240 

240V 

277 

277V 

480 

480V 

600 

600V 

Source configuration 

1 Phase L-N 2w + gnd 

1 Phase L-L 2w + gnd 

Split Phase 3w + gnd 

3 Phase Wye 4w + gnd 

3 Phase Delta 3w + gnd 

3 Phase Delta Hi-leg 4w+ gnd 

F__ __ __    __    __ __ __ __    -   __ __  

Option Code 

01 

LED, Form C 

Contacts 

03 

LED, Alarm, Dual 

Counters, Form C 

Contacts 

06 

LED, Alarm, Counter, 

Form C Contacts 

Example Part Number:  

F277Y800-03

    = 277/480V, 3-Phase Wye, All Mode, 800 Amp Current Rating  

              LED’s, Alarm & Dual Counters, Form C Contacts 

Current 

Code 

Current 

Rating 

Surge Current Capability  

Per Phase 

30 

30A 100kA 

60 

60A 100kA 

100 

100A 150kA 

225 

225A 150kA 

400 

400A 150kA 

800 

800A 300kA* 

1200 

1200A 300kA* 

2000 

2000A 300kA* 

4000 

4000A 300kA 

* 200kA is available,  

add –200 to part number. 

Job Name____________________________

Model# ______________________________

Date ________________________________

Qty _________________________________

Quote# ______________________________

Life Cycle Surge Testing 

10kA, 20kV, IEEE Cat. C3 

Unit 

Per Mode (L-N/L-G/N-G) 

Per Phase 

100 kA 

12,000/12,000/12,000 

24,000 

150 kA 

12,000/24,000/24,000 

36,000 

200 kA 

24,000/24,000/24,000 

48,000 

300 kA 

24,000/48,000/48,000 

72,000 