background image

KE2 WiFi 

Service Tool

(pn 20906)

KE2 LDA  (pn 21253)

Application:

  Designed for small to mid-sized racks - eliminates overly 

complicated controls that are designed for larger systems.

 Easily applied to new or existing installations. 

 Supports up to 5 stages of loading with onboard relays. 

 On racks with compressors all of equal HP, will automatically 

equalize runtime 

 Racks with compressors of varying HP, it maintains consis-

tent suction pressure.

  Master View webpages, allows technicians to quickly and 

easily assess the system’s operation & Review historical per-

formance using onboard data logging.

 Works as a stand-alone rack controller or in conjunction with 

KE2 Evaporator Efficiency controllers. 

 Can limit the amount of defrost load, as dictated by the site’s 

electrical requirements.

The KE2 Compressor Sequencer is new to KE2 Therm’s refrigeration con-

trols suite. Designed for small to mid-sized racks, The KE2 Compressor 

Sequencer brings the controller’s features in line with the job’s require-

ments. It eliminates the necessity of using overly complicated controls 

designed for larger systems. 
The KE2 Compressor Sequencer replaces aging rack controllers or can 

retrofit racks with existing mechanical controls. 
The controller supports up to 5 stages of loading through its onboard 

relays. Each relay can be configured as the rack’s: Fixed Speed Compres-

sor, Compressor Unloader, Digital Scroll Compressor, Master Liquid Line 

Solenoid, or Hot Gas Defrost Relay. 
When applied to racks with compressors all of equal horse power, the 

controller will automatically equalize the runtime of each compressor. 

Compressors can also be of various HP. When more than one HP is se-

lected the controller will use the stage with the smallest capacity, to 

maintain consistent suction pressure.
The KE2 Compressor Sequencer includes KE2 Therm’s Master View web-

pages, allowing technicians to quickly and easily assess the system’s 

operation, and review historical performance through onboard data 

logging.
The compressor sequencer works as a stand-alone rack controller or in 

conjunction with KE2 Evaporator Efficiency controllers. When applied 

with the KE2 Evaporator Efficiency controllers the KE2 Compressor Se-

quencer can limit the amount of defrost load, as dictated by the site’s 

electrical requirements.

Part Numbers 

-  Controllers & Accessories

Part Number Description

 

KE2 Compressor Sequencer

21246

Controller only

 

Pressure Transducers

20201

Pressure Transducer – 0 to 150 psia, 10 ft. leads

20202

Pressure Transducer – 0 to 500 psig, 10 ft. leads

Temperature Sensors

21230

High temp for discharge at condenser inlet, 15 ft.

20199

Standard for all other temp inputs, 10 ft. 

(black)

Solid State Relay

21304

Solid State Relay for Compressor Sequencer (used to control 

5th compressor stage or digital scroll

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Q.2.43

April 2018

KE2 Compressor 

Sequencer 

pn 21710

Quick Start Guide

This reference should remain on site with the installed KE2 Compressor Sequencer

Parts List 

- Included 

The following are included in the KE2  Compressor 

Sequencer kit 21710:

(1) KE2 Compressor Sequencer 120/208-240 VAC 

controller

(1) high voltage safety shield
(1) 15’ high-temperature sensor 
(1) 0-150 psia pressure transducer with 10ft. lead
(1) 0-500 psig pressure transducer with 10ft. lead
(1) 10 ft. temperature sensor for suction temperature 
(4) 90 degree quick disconnects
 
(4) self-tapping screws
(2) course thread screws  (1) fine thread machine screw with lock washer
(4) wire ties 
(rated for high & low temp)
(1) 5-position pluggable connector  
(4) 3-position pluggable connectors (for power in, transducer  & 3A relay)
(9) 2-position pluggable connectors (for sensors & digital input, analog output)
(1) 120 Voltage jumper
(1) 208-240V Voltage jumper 
(already installed on controller)

Other Supplies 

-  Not Included

The KE2 Compressor Sequencer installation requires standard truck stock items.  

A list of items is provided.

 Conduit to go between the controller and the electrical panel

 (2) Conduit connectors (straight or elbow as required)

  High voltage wires matched to the number of compressors, liquid line so-

lenoid (if used), and the controller

 Wire labeling (numbers, colors, etc.)

 Additional wire ties

 18 gauge twisted shielded pair (if extending sensor wires)

Before you begin:

NOTE: 

After the controller is wired, the KE2 Compressor Sequencer is 

setup using the controller’s onboard webpage. 

To access the webpage on the controller you will need a laptop and 

Ethernet cable, or a mobile device and either the KE2 LDA communica-

tion device, or the KE2 WiFi Service Tool. (See page 3)

Summary of Contents for 21710

Page 1: ...KE2 Compressor Se quencer can limit the amount of defrost load as dictated by the site s electrical requirements Part Numbers Controllers Accessories Part Number Description KE2 Compressor Sequencer 2...

Page 2: ...SH 0 150 psia pressure transducer for suction header T1 Suction 50 to 150 F Tempera ture sensor for suction header T2 Air Optional 50 to 150 F tempera ture sensor for space temperature Allows floating...

Page 3: ...ntroller wired and ready Superheat 0 0 F Suct Pressure 96 2 F Suct Temp 87 7 F Computer Tablet or Smart Phone Option A Option B Option C NOTE Computer requires Static IP See bulletin Q 5 11 This will...

Page 4: ...Superheat Superheat as calculated by the controller T1 Suction Temp Suction temperature as measured by the controller Saturation temp Saturation temperature as calculated by the controller Only one of...

Page 5: ...nloader for Cmp 3 Unloader for Cmp 4 Disabled Only one digital compressor Digital Comp ON OFF requires a solid state relay Comp HP per relay labels the HP of each compressor 0 1 to 50 HP None Defrost...

Page 6: ...Max Disch Pres Turns system of when exceeded 100 to 500 psig 450 psig Min Suction SH The lowest acceptable superheat Turns system off when exceeded 5 to 50 F 2 8 to 27 8K 15 F 8 3K Max Suction SH The...

Page 7: ...aximumDischarge Pressure Delay All stages will be turned off The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the Settings page...

Page 8: ...luminated The controller will scroll High Superheat across the front panel High Discharge Pressure If the discharge pressure is above the Max Disch Pres Maximum Discharge Pressure for longer than the...

Page 9: ...e superheat reading is main taining above the Min Safety Suction Superheat the alarm will be cleared The controller will send a notification to the email address or phone number provided in the Addres...

Page 10: ...r to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll the controller requires the user to assign a relay output for each compressor stage av...

Page 11: ...be sent If multiple digital inputs are selected for compressor module any compressor module input will control in manner described above Compressor Module If the Digital Input receives an Inactive si...

Page 12: ...ENTER for 3 seconds to save change To change settings To save setting changes To move through controller menus To return to Main Menu Indicator lights Red light critical alarm system is not running Am...

Page 13: ...splays number of users currently viewing this specific controller s webpage System alarms and messages are displayed DESCRIPTION Displays real time system information and shows the interaction of mult...

Page 14: ...tions Customer information is displayed Use to customize the User Name and Password from the default setting The KE2 Smart Access Settings are provided by KE2 Therm and are only needed when using KE2...

Page 15: ...d must be provided The default User Name ke2admin The default Password ke2admin For security reasons the User Name and Password should be changed from the default Once you are logged in go to the Sett...

Page 16: ...ld also be changed Network settings may be changed to match customer s environment IP address is Enabled or Disabled Enabled if selected IP is Dynamic Disabled if selected IP is Static Prevents unauth...

Page 17: ...Comp 5 Relay 2 5 Dropdown Options All Relay Options the same as Relay 1 except the list of Unloaders for the compressor never includes the active compressor R 404A R 507 R 407A R 407C R 422A R 422D R...

Page 18: ...p to 49 members All mem bers must be in the same network i e a router divides a network The SiteView may be organized by logging into the controller Air Electric Hot Gas DESCRIPTION SiteView provides...

Page 19: ...le Date and Time are pulled from the connected computer 5 460 Day Capacity Load and Suction Pressure are displayed when moving the mouse over the data Days ago DESCRIPTION The Graphing Snapshot shows...

Page 20: ...ile the KE2 Compressor Sequencer s free connectiv ity is still available KE2 Therm recognizes that some customers prefer the simplicity and convenience of KE2 Smart Access to enjoy the benefits of the...