User manual

Technical parameters

Your partner for 

network analysis

D2-MSMT-1

Gateway from Modbus TCP 

to Modbus RTU, serial RS485

multisys

System 

I

 English

Summary of Contents for multisys D2-MSMT-1

Page 1: ...20742_EDEBDA0231 2516 1_EN User manual Technical parameters Your partner for network analysis D2 MSMT 1 Gateway from Modbus TCP to Modbus RTU serial RS485 multisys System I English ...

Page 2: ...resulting from printing errors in or changes to this manual In addition KBR Kompensationsanlagenbau GmbH does not accept any liability for any loss or damage caused by defective devices or devices manipulated by the user Copyright 2016 by KBR Kompensationsanlagenbau GmbH Subject to change ...

Page 3: ...sposal 7 1 6 Overvoltage and lightning protection 7 2 multisys D2 MSMT 1 8 2 1 Interface Modbus RTU serial RS 485 9 2 2 Configuration via the Ethernet interface Telnet 10 2 21 Procedure for IP address 192 168 0 1 or unknown IP 10 2 2 2 Configuration via Telnet 10 2 2 3 Connection diagram 12 3 Technical data 13 3 1 Power supply 13 3 2 Electrical connection 13 3 3 Mechanical data 13 2 4 Standards an...

Page 4: ...he technical details of the device and show how to properly install and start up the device to prevent damage 1 1 User manual This user manual describes the multisys D2 MSMT 1 device version This user manual must be accessible to the user at all times e g in the switch gear cabinet Even if the device is resold to third parties the manual remains an inherent part of the device Although the utmost o...

Page 5: ...en Caution Caution means that minor injuries or damage may occur if suitable safety precautions are not taken Note Note is an important piece of information on the product its operation or the respective part of the operating instructions to which special reference is being made Disclaimer The contents of these operating instructions have been carefully reviewed in terms of the hardware and softwa...

Page 6: ...ad to the destruction of the device For device connection the data given in the connection chart must be complied with see Connection diagram and the connection lines must be voltage free When wiring always ensure that all wiring material used is neither damaged nor defective and that the polarity is correct In order to ensure proper and safe product operation transport store install and assemble ...

Page 7: ...nditions for electronic equipment which you can find at www kbr de The warranty on device properties applies only if the device has been operated in accordance with its intended use 1 5 Disposal Defective outdated or disused devices must be properly disposed of If required we will dispose of the devices for you 1 6 Overvoltage and lightning protection It is recommended to install overvoltage prote...

Page 8: ...he two interfaces RS 485 Modbus serial and Ethernet on the network side are galvanically separated If necessary the RS 485 interface on the Modbus side can be terminated using four DIP switches terminating resistors fitted into multisys The D2 MSMT 1 is equipped with a power LED for supply voltage monitoring It is equipped with its own power supply 85 to 265 V AC DC 2 VA and is suit able for wall ...

Page 9: ...ing RS 485 DIP1 and DIP2 ON DIP3 OFF failsafe activated DIP1 and DIP2 OFF DIP3 ON termination activated DIP1 and DIP2 OFF DIP3 OFF no failsafe no termination DIP4 not assigned Note The failsafe termination can only be activated once per bus segment LED for monitoring power supply RJ 45 Ethernet connection Supply voltage 85 265 V AC DC 2 VA 2 pole multi pin connector 5 mm Connection LED left Activi...

Page 10: ...eInstaller For this purpose download the Lantronix DeviceInstaller software from the Internet and install it you need to install Microsoft NET Framework first After starting DeviceInstaller the connected network is scanned and the Lantronix ports detected are displayed and can then be edited Select the IP address of the multisys D2 MSMT 1 and then establish a Telnet connection After confirming wit...

Page 11: ...le CP2 Not Used CP3 Not Used 4 Advanced Modbus Protocol settings Slave Addr Unit Id Source Modbus TCP header Modbus Serial Broadcasts Disabled Id 0 auto mapped to 1 MB TCP Exception Codes Yes return 00AH and 00BH Char Message Timeout 00050msec 05000msec 7 Security Settings SNMP Enabled SNMP Community Name public Telnet Setup Enabled TFTP Download Enabled Port 77FEh Enabled Web Server Enabled Enhan...

Page 12: ...0 20742_EDEBDA0231 2516 1_EN 12 Connection diagram multisys D2 MSMT 1 LAN L N 1 2 90 91 92 zu weiteren Modbusteilnehmer bzw Leitungsabschluss to other modbus devices and line termination Netz power 2 2 3 Connection diagram ...

Page 13: ...ltage Fusing max 6 A LAN connection 8P8C modular connector RJ 45 BUS connection Connection material For proper operation use shielded twisted pair cables only e g I Y St Y 2x2x0 8 Modbus serial connectors for connection via RS 485 Device Terminal 90 Terminal 91 A Terminal 92 B 3 3 Mechanical data Top hat rail device Housing dimensions 90 x 36 x 61 mm H x W x D Mounting type Wall mounting on DIN ra...

Page 14: ...5 3Z11 Operating temperature 5 C 60 C Humidity 5 95 non condensing Storage temperature 25 C 70 C Electrical safety Standards DIN EN 61010 1 2011 07 Protection class II Overvoltage category III Protection type IP20 in accordance with DIN EN 40050 part 9 1993 05 Electromagnetic compatibility DIN EN 61000 6 3 2011 09 amendment 1 2012 11 DIN EN 61000 6 2 2006 03 amendment 1 2011 03 ...

Page 15: ...V1 00 multisys D2 MSMT Notes 20742_EDEBDA0231 2516 1_EN 15 ...

Page 16: ...20742_EDEBDA0231 2516 1_EN Am Kiefernschlag 7 D 91126 Schwabach Germany T 49 0 9122 6373 0 F 49 0 9122 6373 83 E info kbr de www kbr de KBR Kompensationsanlagenbau GmbH ...