manualshive.com logo in svg
background image

ZFR1831 Pro Series Wireless Router

Installation Guide

Introduction

The ZFR1831 Wireless Router (ZFR1831) is a component of the ZFR183x Pro Series Wireless Field Bus

System which provides BACnet IP connectivity to compatible Johnson Control Field Controllers, VAV

Controllers, Thermostats and Sensors over a wireless mesh network. The ZFR1831 can be used as a

wireless Network Coordinator, a Field Controller Router or Stand-alone Repeater.

Applications

Important: 

Where failure or malfunction of an ZFR1831 or loss of communications due to

wireless interference could lead to personal injury or property damage to the controlled

equipment or other property, additional precautions must be designed into the control

system. Incorporate and maintain other devices, such as supervisory or alarm systems or

safety or limit controls, intended to warn of or protect against failure or malfunction of a

ZFR1831.

Important: 

The WRG1830/ZFR183x Series Wireless Field Bus System is not designed or

intended for use in mission-critical or life/safety applications.

North American emissions compliance

United States

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two

conditions:

1.  This device may not cause harmful interference, and
2.  This device must accept any interference received, including interference that may cause

undesired operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by the party responsible for compliance could

void the user’s authority to operate the equipment.

Canada

Industry Canada Statement(s)

This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to

the following two conditions:

1.  This device may not cause interference, and
2.  This device must accept any interference, including interference that may cause undesired

operation of the device.

(barcode for factory use only)

ZFR1831

Johnson Controls - CONFIDENTIAL

*241146100004-*

Part No. 24-11461-00004 Rev —
2020-05-22
11.0 Alpha

Содержание ZFR1831 Pro Series

Страница 1: ...nt The WRG1830 ZFR183x Series Wireless Field Bus System is not designed or intended for use in mission critical or life safety applications North American emissions compliance United States Compliance Statement Part 15 19 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must ac...

Страница 2: ...uct warranty Important The modular phone jack and screw terminal connections cannot be used simultaneously Location Considerations Follow these guidelines when locating an ZFR1831 within an ZFR183x Pro Series Wireless Field Bus system The ZFR1831 wireless router can be installed on wall wall box conduit or ceiling grid Do not mount inside metal enclosures or on surfaces that can block RF signals L...

Страница 3: ...es for an WRG1830 ZFR183x Series system and for estimating the number of ZFR1831 Routers needed as repeaters for extending wireless transmission range refer to the applicable WRG1830 ZFR183x Series Wireless Field Bus System Technical Bulletin Parts included Verify that the following parts shipped with the ZFR Pro Router ZFR1831 Wireless Router 3m 10ft wiring cable ZFR1831 Pro Series Wireless Insta...

Страница 4: ...Figure 2 ZFR1831 Router conduit installation mounting view ZFR1831 Pro Series Wireless Router Installation Guide 4 Johnson Controls CONFIDENTIAL ...

Страница 5: ...s to transmit a message to the coordinator In a well designed system the layout design should minimize the required hops based on the recommended transmission ranges and should typically be kept below five Information on determining the numbers of hops being used is covered in the WRG1830 Wireless Gateway Users Guide LIT 12013550 The WRZ sensors list a lower line of sight range because they transm...

Страница 6: ...und the ZFR1831 to promote good ventilation LED visibility and ease of service Important Do not connect supply power to the ZFR1831 before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the ZFR1831 Important Use copper conductors only Make all wiring in accordance with local national and regional regulations The Z...

Страница 7: ...d Controller via RJ12 Figure 5 RJ12 pin out on the controller Note See MS TP Communications Bus Technical Bulletin LIT 12011034 for more information 7 ZFR1831 Pro Series Wireless Router Installation Guide Johnson Controls CONFIDENTIAL ...

Страница 8: ...or ceiling grid 2 Connect a 15VDC to 24 VAC source to the wireless router s screw terminal pin connectors Figure 7 ZFR1831 wired as Stand alone Repeater Using as a coordinator connected to WRG 1 Follow the mounting instructions above for mounting to either wall wall box conduit or ceiling grid ZFR1831 Pro Series Wireless Router Installation Guide 8 Johnson Controls CONFIDENTIAL ...

Страница 9: ... and adjustments Selecting a PAN OFFSET for a Wireless Network When selecting a PAN OFFSET for a wireless network keep these points in mind All devices within one wireless mesh network must be set to the same PAN setting Select PAN settings that are unique for the site The AREA rotary switch should be set to 0 Figure 9 ZFR1831 Router Rotary Switches 9 ZFR1831 Pro Series Wireless Router Installatio...

Страница 10: ...r Controller and Repeater Product code number ZFR1831 0 Wireless Field Bus Router Power supply input 15VDC with cable connected to field controller or 24 VAC nominal 20 VAC minimum 30 VAC maximum 50 60 Hz power supply Class 2 Addressing Rotary Switches Field Adjustable Wireless band Direct Sequence Spread Spectrum 2 4 GHz ISM Bands Transmission power 100 mW Maximum selectable Transmission range 75...

Страница 11: ...egulations for Low Power Unlicensed Transmitters Transmitter Identification ZFR1831 FCC OEJ ZFRRADIO Canada CAN CSA E60730 1 15 Canadian Standard For Automatic electrical controls for Household and Similar use Part 1 General requirements Energy Management Equipment Industry Canada IC Compliant to Canadian ICES 003 Class B Limits Industry Canada IC RSS 210 Transmitter Identification ZFR1831 279A ZF...

Страница 12: ...Johnson Controls CONFIDENTIAL www johnsoncontrols com ...

Отзывы: