background image

Model DSB-2  

Dry Sprinkler Boot  

For Use With TFP Dry Type Sprinklers

Page 1 of 4 

AUGUST 2018 

TFP591

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model DSB-2 Dry Sprinkler 

Boot (Ref. Figure 1) is designed for use 

with TFP Dry Type Sprinklers. When 

properly installed, it will help close the 

air gap created by the clearance hole 

through a wall or ceiling through which 

the dry type sprinkler has penetrated.
The DSB-2 is intended predominately 

for use with clearance holes through 

freezer ceiling structures. In these 

types of installations, due to the greater 

temperature difference between the 

inside and outside of the freezer than 

found with other type installations, the 

potential for the formation of conden-

sation in the sprinkler and subsequent 

ice build-up is increased. If this con-

densation is not controlled, ice build-up 

can occur that might damage the dry 

type sprinkler and/or prevent proper 

operation in a fire situation.
The DSB-2 is intended to help stop the 

air exchange between the inside and 

outside of the freezer (or any other type 

of similar construction) to help prevent 

transfer of moist air into the freezer 

space. The use of the DSB-2 provides 

a quick and efficient means of closing 

the air gap created by the dry type 

sprinkler clearance hole. The DSB-2  

provides the added feature of eliminat-

ing the occurrence of cracking of some 

commonly used sealants, that subse-

quently allows the passage of moist air.

NOTICE

The Model DSB-2 Dry Sprinkler Boot 

described herein must be installed 

and maintained in compliance with 

this document, as well as with the 

applicable standards of the NATIONAL 

FIRE PROTECTION ASSOCIATION, in 

addition to the standards of any other 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

Approvals 

The TYCO Model DSB-2 Dry Sprin-

kler Boot does not require laboratory 

approval to be installed in accordance 

with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION. The use of the DSB-2 does 

not alter any of the applicable labo-

ratory approvals for TFP Dry Type 

Sprinklers.
The 2007 edition of NFPA 13, Section 

8.4.10.2 requires that dry sprinklers  

connected to wet pipe sprinkler 

systems protecting insulated freezer  

structures, the clearance space around 

the sprinkler barrel shall be sealed.

Dry Type Sprinkler Compatibility  

and Technical Data Sheet 

Reference

Series DS-1, Standard Response  

Standard Coverage,  

Pendent, Upright

and HSW  . . . . . . . . . . . . . . . . . . . .TFP500

Series DS-1, Quick Response  

Standard Coverage,  

Pendent, Upright

and HSW  . . . . . . . . . . . . . . . . . . . . TFP510

Series DS-C, Standard Coverage

Concealed Pendent . . . . . . . . . . . . TFP515

Series DS-ECC, Extended Coverage

Concealed Pendent . . . . . . . . . . . . TFP518

Series DS-1, Extended Coverage

Horizontal Sidewall  . . . . . . . . . . . . TFP520

Series DS-2, Standard

Coverage Pendent . . . . . . . . . . . . . TFP530

Series DS-2, Extended

Coverage Pendent . . . . . . . . . . . . . TFP540

Series DS-3, ECOH

Horizontal Sidewall  . . . . . . . . . . . . TFP550

NOTE: Use of the Model DSB-2 Dry 

Sprinkler Boot with non-TFP Dry Type 

Sprinklers will void the warranty. Failure 

may result due to dimensional differ-

ences in the outside diameter of the 

barrel. The DSB-2 has not been tested 

with any non-TFP Dry Type Sprinklers 

with regard to fit or performance.

Physical Characteristics

The Boot is EPDM, the Strap Ties are 

nylon, and the Adhesive is ethyl cyano-

acrylate based. The adhesive is formu-

lated for instant bonding of the Boot to 

metal, plastic, or rubber surfaces.

Design 

Criteria

There are four items to be considered: 

Dry Type Sprinklers, Clearance Hole, 

Exposure Length, and Sprinkler Fitting. 

Dry Type Sprinklers

This Technical Data section provides 

a list of all of the compatible dry type 

sprinklers and their associated techni-

cal data sheets. Refer to the applicable 

technical data sheet for installation and 

maintenance information for the sprin-

kler being utilized.

Summary of Contents for tyco DSB-2

Page 1: ...ION ASSOCIATION in addition to the standards of any other authorities having jurisdiction Failure to do so may impair the performance of these devices The owner is responsible for main taining their fire protection system and devices in proper operating con dition Contact the installing contrac tor or product manufacturer with any questions Technical Data Approvals The TYCO Model DSB 2 Dry Sprin k...

Page 2: ...et pipe sprinkler systems protecting areas subject to freezing temperatures e g sprinkler drops into freezers con sideration must be given to the appro priate length of the sprinkler that will prevent freezing of the water in the con necting pipes due to conduction When the temperature surrounding the wet pipe sprinkler system is maintained at a minimum temperature of 40 F 4 C the following are th...

Page 3: ...hesive contains cyanoacrylate ester Irritation will occur when inhaled This adhesive bonds skin in seconds Contact through clothing may cause burns EYE IRRITANT Always refer to the Material Safety Data Sheet for additional adhesive handling recommendations The Material Safety Data Sheet should be obtained from the adhesive manufacturer via their web site noted on the adhesive con tainer label befo...

Page 4: ... water The use of other cleaning techniques solvents etc may render the adhesive incapable of sealing Step 5 Apply the provided Adhesive to the building structure in a zig zag pattern Refer to Warning regarding the adhesive Step 6 Slide the Boot so that it comes in contact with the building structure and then press the Boot firmly against the building structure to help ensure that the Adhesive is ...

Reviews: