manualshive.com logo in svg
background image

DIS1710 Local Controller Display Installation

Instructions

Applications

The DIS1710 Local Controller Display is a stand-

alone display module designed for installation on

the front panel of an enclosure. The DIS1710 display

can connect to the Network Control Engine (NCE),

Field Equipment Controller (FEC), or Advanced

Application Field Equipment (FAC) models that do

not have integral displays. The display provides a

local user interface for the application running in

the controller. Use the Controller Configuration Tool

(CCT) tool to configure the display.

North American emissions
compliance

United States

This equipment has been tested and found to

comply with the limits for a Class A digital device

pursuant to Part 15 of the FCC Rules. These limits

are designed to provide reasonable protection

against harmful interference when this equipment

is operated in a commercial environment. This

equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications.

Operation of this equipment in a residential area

may cause harmful interference, in which case the

users will be required to correct the interference at

their own expense.

Canada

This Class (A) digital apparatus meets all the

requirements of the Canadian Interference-Causing

Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte

toutes les exigences du Règlement sur le matériel

brouilleur du Canada.

Installation

Observe these guidelines when installing the

DIS1710 display:
• Transport the display in the original container to

minimize vibration and shock damage to the unit.

• Verify that all parts were shipped with the display.

• Do not drop the display or subject it to physical

shock.

Parts included

• One DIS1710 Local Controller Display
• One communication cable
• One O-ring
• One installation instructions sheet

Materials and special tools needed

• Power saw for cutting a hole into the panel to hold

the display, if no hole is provided

• Small Phillips-head screwdriver

*24102409J*

Part No.  24-10240-9 Rev. J

2019-10-18

(barcode for factory use only)

MS-DIS1710-0

Содержание DIS1710

Страница 1: ...ed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulati...

Страница 2: ...nel Door with Cutout for display Mounting Location considerations The display is mounted onto the front panel door of an enclosure Mounting dimensions and physical features Refer to the following illustrations for the mounting dimensions and physical features of the display Figure 1 DIS1710 Mounting Dimensions mm in Figure 2 DIS1710 physical features Preparing the panel The display is mounted onto...

Страница 3: ... 4 Insert the display into the front access hole on the panel door Hold in place 5 Carefully insert the back plate to the other side of the access hole inside of the panel door and secure it to the cutout by hand tightening the two thumbscrews You may need to tilt the back plate to slide it onto the two bottom retaining tabs Figure 4 Attaching the display into panel cutout 6 Using the screwdriver ...

Страница 4: ...een the SA Bus connector on the back of the display and the SA Bus jack on the front of the controller Figure 6 The coiled cable is 91 cm 3 ft in length and can be stretched to a maximum length of 152 cm 5 ft Figure 6 Connecting the SA bus cable If the SA Bus jack on the controller is in use you can wire the display s communication cable to the SA Bus terminal block Splice one end of the communica...

Страница 5: ...not require commissioning Cable connection between the DIS1710 Local Controller Display and a commissioned field controller allows for immediate display function Ensure that the communication cable is connected between the display and the controller For more information on commissioning refer to the Controller Tool Help LIT 12011147 Troubleshooting Refer to the DIS1710 Local Controller Display Tec...

Страница 6: ...CN PAZX UL 916 Energy Management Equipment FCC Compliant to CFR47 Part 15 Subpart B Class A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive Compliance Australia and New Zea...