background image

 

 

GFH45-IOM  Rev. 0  12/18 

 

 

Printed in USA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enidine / Conoflow 

105 Commerce Way 
Westminster, SC  29693 
Tel:  (864) 647-9521 
Fax: (864) 647-7993 

 

 

 

 
 

 

INSTRUCTION AND MAINTENANCE MANUAL 

GFH45 PRESSURE REGULATOR 

 

CAUTION:  These instructions should be read 
carefully prior to installation, use or 
maintenance. 

 

GENERAL PRODUCT OVERVIEW 
 

Conoflow’s GFH45 Series Airpak®, Filter-Regulator is 
used to provide clean, accurate air to instruments, 
valves, positioners, transducers and other pneumatic 
control devices. This unit’s design provides high flow 
capability, durable materials of construction and bubble 
tight shut-off. 
 
The GFH45 Regulator has a maximum supply pressure 
capability of 300 PSIG (2.07 MPa) with control output 
settings of 0-25, 0-60 and 0-125 PSIG (0-172, 0-414 and 
0-862 kPa). This brass filter regulator boasts a high flow 
delivery rate and excellent droop characteristic. 
 
This regulator is offered with ¼” NPT inlet and outlet 
ports, two outlet gauge ports, and brass construction.  A 
handwheel or wrench knob adjustments are standard. 
 

CAUTION:  

Maximum Supply Pressure is 300 

PSIG (2.07 MPa)

 

 

WARNING: This product is not recommended 
for use with flammable liquids or gasses.

 

 
 
 
 
 
 
 

 
 
 
 
MATERIALS OF CONSTRUCTION 

Nozzle Assembly: Brass with Buna N Soft Seat 
Range Spring: Zinc Plated Carbon Steel 
Diaphragm Assembly: see CED Code 
Bowl: Brass 
Body: Brass 
Bonnet: Brass 

 
SPECIFICATIONS 

Maximum Supply Pressure:

 

300 psig (2.07 MPa) 

Outlet pressure ranges are determined by the last 
character in the regulator model number. 

C

” 

25 psig (172 kPa) 

F

” 

60 psig (414 kPa) 

G

” 

125 psig (862 kPa) 

Proof Pressure:

 

150% of maximum operating 

Burst Pressure:

 

400% of maximum operating 

 
Flow Capacity:

  

20 scfm (see flow chart) 

Temperature Range:

   -20 °F to 165 °F 

 

 

 

 (-29 °C to 74 °C) 

Sensitivity:                   

0.02 psi (0.14 kPa) 

Connections:

   

¼” NPT Inlet and Outlet Ports,  

   Two-¼” 

NPT 

Gauge 

Ports 

 

(90° from Outlet Port) 

Weight:

 

 

3.4 lb (1.55 kg)  

 

REGULATOR CLEANING 

The GFH45 pressure regulator is cleaned to ITT 
Conoflow specification ES8A 01 1 when option B is 
selected in position 6 of the model number. 

WARNING 

Conoflow’s products are designed and 
manufactured using materials and 
workmanship required to meet all applicable 
standards.  The use of these products 
should be confined to services specified 
and/or recommended in the Conoflow 
catalogs, instructions, or by Conoflow 
application engineers. 

 

To avoid personal injury or equipment 
damage resulting from misuse or 
misapplication of a product, it is necessary 
to select the proper materials of 
construction and pressure-temperature 
ratings which are consistent with 
performance requirements. 

Summary of Contents for GFH45

Page 1: ...STRUCTION Nozzle Assembly Brass with Buna N Soft Seat Range Spring Zinc Plated Carbon Steel Diaphragm Assembly see CED Code Bowl Brass Body Brass Bonnet Brass SPECIFICATIONS Maximum Supply Pressure 300 psig 2 07 MPa Outlet pressure ranges are determined by the last character in the regulator model number C 25 psig 172 kPa F 60 psig 414 kPa G 125 psig 862 kPa Proof Pressure 150 of maximum operating...

Page 2: ... factory plugged outlet gauge ports WARNING If the supply line is connected to the outlet port regulator damage or unexpected flow through the regulator could occur Prior to applying inlet pressure double check the connections and assure the wrench knob or hand wheel is backed out sufficiently to unload the range spring in the bonnet Carefully apply inlet pressure and check the supply connection f...

Page 3: ...leed No Relief Character 10 Gauge Selections X No Gauge standard Character 11 Filter Bowl Option 1 Standard Bowl Size NOTE Materials of construction and cleaning specifications are the user s responsibility Character 12 Control Ranges C 25 psig 172 kPa F 60 psig 414 kPa G 125 psig 862 kPa OPERATION IN SERVICE Open upstream controls to provide the regulator supply pressure To increase the output se...

Page 4: ...kage Repair Disassemble Inspect regulator body where bowl o ring contacts Inspect bowl where o ring contacts Replace o ring Symptom External leakage Potential Cause Draincock leakage Repair Tighten draincock by turning handle clockwise Symptom Outlet pressure cannot be adjusted to maximum control range Potential Causes 1 Control knob positive stop adjustment 2 Flow induced droop Repair 1 Adjust po...

Page 5: ...r 9 Remove the dripwell by pulling downward away from the body 10 Remove the filter 11 To remove the plug spring and valve plug unscrew the retainer then grip the plug spring and pull downward away from the body The plug and plug spring should slide out of the body together ASSEMBLY 1 Replace worn or damaged components with new components 2 Clean and inspect components for reuse Sealing surfaces m...

Page 6: ...or Model Number and Item Description This will permit positive identification and rapid handling of order 2 Spare parts kit standard configuration only a G6385516 for the 0 25 60 psi 172 414 kPa models b G6385517 for the 0 125 psi 862 kPa model 3 For other model configurations or non CED codeable models consult factory for correct part number ...

Reviews: