background image

NSW

 02 9644 7144    

QLD

 07 3252 5366    

VIC

 03 9544 2211   

WA

 08 9349 2972

ASD 533

Aspirating Smoke Detector

As of production version 200619 and FW version 01.08.xx

The ASD 533 aspirating smoke detector has the task of continu-

ously taking air samples via a sampling pipe tube network from a 

monitored area and feeding the samples to a smoke sensor.
The ASD 533 consists of the detector housing and a sampling pipe 

tube network. The sampling pipe has several sampling holes 

whose size is such that each hole extracts the same amount of air. 

The sampling pipe may be I-, U-, T-, H-, or E-shaped. The sam-

pling pipe is symmetrically designed in principle. Asymmetrical 

sampling pipe tube networks can also be implemented using the 

“ASD PipeFlow” calculation software.

Fig. 1 ASD 533

__________________________________________________________________________________________________________________  

Description

Integrated in the detector housing is a high-performance fan which, 

in conjunction with the sampling pipe, ensures an uninterrupted air 

supply to the detector housing. Airflow monitoring detects any pipe 

blockages and pipe breakages in the sampling pipe.
The  ASD 533 aspirating smoke detector is part of the ASD 535 

product range and is available in a version for 1 sampling tube and 

1 smoke sensor without smoke level indicator. The exact designa-

tion for the aspirating smoke detector is therefore 

ASD 533-1

. The 

present document will however refer in principle to the product des-

ignation 

ASD 533

The  ASD 533 uses the 

SSD 533

smoke sensor, which has an 

alarm sensitivity of 0.02%/m to 10%/m.
The  ASD 533 aspirating smoke detector has four slots for addi-

tional modules. The following modules can be fitted:

XLM 35

SecuriLine eXtended Module;

SLM 35

SecuriLine Module;

RIM 35

Relay Interface Module with 5 relays (max. 2 

units);

MCM 35

Memory Card Module

The ASD 533 can be connected to a higher level FACP via poten-

tial-free change-over contacts.
Fitting an 

XLM 35

or 

SLM 35

means that the ASD 533 can be ide-

ally connected to the SecuriFire and Integral fire alarm systems via 

the addressable loop (with SLM also to the SecuriPro).
The 

RIM 35

is available as a further installation option. This mod-

ule enables the availability of all three pre-signal levels as well as 

the states “smoke sensor dirty” and “LS-Ü blockage” as relay con-

tacts. The relays are also freely programmable via the 

„ASD Config” configuration software.
The 

MCM 35

is used for storing operating data.

The ASD 533 aspirating smoke detector can be used for:

Equipment monitoring

: EDP systems, electrical distributors,

switch cabinets, etc.

Space surveillance

: EDP rooms, ultra-clean rooms, warehou-

ses, hollow floors, protection of cultural assets, transformer sta-

tions, prison cells, etc.

The ASD 533 is also deployed in areas where conventional point 

detectors are normally used. Local regulations and provisions must 

be observed from case to case.
The response behaviour of the ASD 533 has been tested in com-

pliance with EN 54-20, Class A, B and C.

When setting up ASD 533 fire alarm systems, it is impor-

tant to take note of and observe the information and 

specifications in the “

Technical description ASD 533

”. 

This includes among others:

General

Section 1

Planning

Section 4

Mounting

Section 5

Installation

Section 6

Commissioning

Section 7

Opening the detector housing

To actuate the 

rotary snap locks

use a Phillips screw-

driver (at least No. 5) to 

press down firmly

towards the 

housing base and then 

turn

90°. The position of the lock 

slit shows the current status:

angled approx. 45° toward detector housing corner = 

closed;

angled approx. 45° toward detector housing edge = 

open.

In either position the rotary snap locks 

must

snap into 

place.
The 

housing cover

(control unit) is connected to the 

main board by a 

ribbon cable

. Make sure the ribbon ca-

ble is not damage when the housing cover is lifted off.

Summary of Contents for ASD 533

Page 1: ... 35 Memory Card Module The ASD 533 can be connected to a higher level FACP via poten tial free change over contacts Fitting an XLM 35 or SLM 35 means that the ASD 533 can be ide ally connected to the SecuriFire and Integral fire alarm systems via the addressable loop with SLM also to the SecuriPro The RIM 35 is available as a further installation option This mod ule enables the availability of all...

Page 2: ...allation of the ASD release the two lock clamps however it should be left inside its protective packaging until the definitive commissioning The definitive installation is carried out as de scribed below see Fig 3 Always leave the smoke sensor inside its protective packaging until it is ready to be installed definitively in the detector housing Depending on the circumstances e g long period of tim...

Page 3: ...manently assigned parameters Normative system limits according to EN 54 20 Class A to C positions A11 to C31 Non normative system limits positions W01 to W44 Configurable positions for settings after using ASD PipeFlow and or ASD Config or SecuriPro SecuriFire or Integral FACP SLM 35 XLM 35 X01 to X03 The parameters are saved at the factory with values for compliance with EN 54 20 Changing the par...

Page 4: ...ior consultation with the manufacturer The airflow monitoring values stored under those switch positions are not tested in accordance with EN For more information on using the table of system limits please refer to the Technical description T 140 287 Sec 4 4 4 3 and 4 4 4 4 Table of system limits for planning without ASD PipeFlow calculation Compliant with EN 54 20 Class A highly sensitive Shape S...

Page 5: ... 5 3 0 7 0 11 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 2 5 4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 U T shaped sampling pipes Number of sam pling holes per sampling branch Hole diameter in mm for the sampling hole number as of ASD 1 2 3 4 5 6 7 8 1 5 0 2 4 0 5 0 3 4 0 4 0 5 0 4 4 0 4 0 4 0 5 0 5 4 0 4 0 4 5 5 0 6 5 6 3 0 3 0 3 5 3 5 4 0 6 5 7 2 5 3 0 3 0 3 5 3 5 4 0 6 5 8 2 5 2 5 3 0 3 0 ...

Page 6: ... 5 60 5 X01 X03 Soiling threshold of Al 75 65 100 5 X01 X03 Dust latching On On Off X01 X03 Soiling latching On On Off X01 X03 Smoke sensor fault delay 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü pipe blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity applies to A01 to C31 20 1 70 1 X01 X03 LS Ü value averaging number 20 1 30 1 X01 X03 LS Ü delay a...

Page 7: ...al 1 s 1 120 s MCM smoke peak value memory Off Off On Carry out new initial reset On Off Smoke sensor mode of operation smoke sensor I SSD DMB SSD DMB or OEM inputs individual or in combination Switched off Isolate smoke sensor smoke sensor I Normal operation Isolate normal operation Filter monitoring smoke sensor I Off Off On Filter service life 6 months 1 24 months Read out operation time months...

Page 8: ... b21 Displays the new set ting Initial reset Measure Display Procedure remarks Before carrying out an initial reset i e after switching on the ASD 533 make sure you observe a waiting time of at least 5 min 1 Press the UP key flashing C31 or others Displays the default setting or the installa tion specific switch position 2 Press the UP key several times until dis play shows U in succession A to U ...

Page 9: ...200006 01 XX SecuriLine eXtended line module XLM 35 11 2200003 01 XX SecuriLine module SLM 35 4000286 0101 Relay interface module RIM 35 4000287 0101 Memory card module MCM 35 4000285 0101 SD memory card industrial version 11 4000007 01 XX USB cable 4 5 m 4301248 Main board AMB 33 1 11 2200004 01 XX BCB 35 without smoke level indicator 4301220 0101 Aspirating fan unit AFU 35 complete 4000299 Airfl...

Page 10: ... C Sampling pipe temperature range 20 60 C Max permissible temperature fluctuation in detector housing and sampling pipe operation 20 C Max permissible storage temperature for detector housing without condensation 20 70 C Ambient pressure difference between detector housing and sampling pipe sampling holes must be identical Humidity ambient condition for detector housing transient without condensa...

Reviews: