Operating instructions 

Ultrasonic flow rate sensor

SU8200

704855 / 00 

 

  07 / 2010

UK

Summary of Contents for efector 300 SU8200

Page 1: ...Operating instructions Ultrasonic flow rate sensor SU8200 704855 00 07 2010 UK ...

Page 2: ...nu 14 9 Parameter setting 15 9 1 General parameter setting 15 9 2 Settings for volumetric flow monitoring 17 9 2 1 Settings for limit value monitoring with OUT1 17 9 2 2 Settings for limit value monitoring with OUT2 17 9 3 Settings for temperature monitoring 17 9 3 1 Settings for limit value monitoring with OUT2 17 9 4 User settings optional 18 9 4 1 Determine the standard unit of measurement for ...

Page 3: ...tion set up operation and mainte nance of the unit must be carried out by qualified personnel authorised by the plant operator In all applications test the compatibility of the product materials 12 Techni cal data with the media to be measured For the scope of validity cULus 6 Electrical connection 9 4 9 Selection of the medium to be monitored 19 9 5 Service functions 19 9 5 1 Reading the min max ...

Page 4: ...ture limit value 9 4 1 4 2 Volumetric flow monitoring The flow rate is monitored by an ultrasonic meter the measured signals by the electronics 2 switching signals for volumetric flow limit values can be provided output 1 and output 2 For the switching functions 4 4 4 3 Monitoring of temperatures A switching signal for temperature limit values can be provided on output 2 For the switching function...

Page 5: ...he final value of the measuring range VMR the fol lowing processes are carried out The start up delay is activated Output 1 switches as programmed ON for NO function OFF for NC function Output 2 switches when the flow is evaluated SEL2 FLOW as pro grammed ON for NO function OFF for NC function dSt only has an effect on the switching signals for volumetric flow monitoring After the activation of th...

Page 6: ... output becomes active 2 dSt elapsed Q reached SP output remains active 3 Q below SP but above rP output remains active 4 Q below rP output is reset 5 Q reaches again 0 5 of VMR dSt starts output becomes active 6 dSt elapsed Q has not reached SP output is reset 7 Q reaches SP output becomes active ...

Page 7: ... active 7 dSt elapsed Q has not reached good range output is reset 8 Q reaches good range output becomes active 4 6 Customer specific calibration CGA This calibration changes the slope of the curve of measured values It influences the display and the outputs A operating value for display and output signals Q volumetric flow MEW final value of the measuring range V0 curve of measured values without...

Page 8: ...he unit so that the measuring pipe is always completely filled Arrange for inlet and outlet pipe lengths Disturbances caused by bends valves reductions etc are compensated for It applies in particular no shut off and control devices are allowed directly in front of the unit S disturbance D pipe diameter F flow direction Install in front of or in a rising pipe F flow direction ...

Page 9: ...lation locations Directly in front of a falling pipe In a falling pipe FF flow direction At the highest point of the pipe system Directly in front of the spout of a pipe F flow direction On the suction side of a pump F flow direction ...

Page 10: ...adapters for NPT pipes brass 2 seals Order no E40156 2 adapters forg NPT pipes brass 2 seals 1 Screw the adapter B into the pipe A 2 Place the seals C and install the unit according to the marked flow direction 3 Screw the adapter B with the threads D until it is hand tight 4 Tighten the two adapters in opposite direction tightening torque 30 Nm After installation air bubbles in the system can aff...

Page 11: ...ly to EN50178 SELV PELV For the scope of validity cULus The device shall be supplied from an isolating transformer having a secondary Listed fuse rated as noted in the following table Overcurrent protection Control circuit wire size Maximum protective device rating Ampere AWG mm2 26 0 13 1 24 0 20 2 22 0 32 3 20 0 52 5 18 0 82 7 16 1 3 10 Disconnect power connect the unit as follows Pin1 Ub Pin3 U...

Page 12: ...rature in F LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits Indication of the current volumetric flow can be changed temporarily to indicate the current temperature 10 2 Indication of the parameters and parameter values 10 Mode Enter pushbutton Selection of the parameters and acknowledgement of the parameter values 11 Set pushbutton Setting of the parameter ...

Page 13: ...13 UK 8 Menu 8 1 Menu structure Mode Enter Set ...

Page 14: ...inimum value memory for volumetric flow CGA Customer specific calibration of the curve of measured values CAr Calibration reset FOU1 Behaviour of output 1 in case of an internal fault FOU2 Behaviour of output 2 in case of an internal fault dSt Start up delay dAP Measured value damping damping constant in seconds diS Update rate and orientation of the display UniF Standard unit of measurement for v...

Page 15: ...m eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be reduced let the display move to the maximum setting value Then the cycle starts again at the minimum setting value 3 Acknowledgement of the parameter value Press Mode Enter briefly The parameter is display...

Page 16: ...ss Mode Enter Set for 10 s Loc is displayed During operation Loc is briefly displayed if you try to change parameter values Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Time out If during parameter setting no pushbutton is pressed for 15 s the unit exits the param eter setting mode The parameter value is not changed For medium temperatures over 50 C 122 F some parts of t...

Page 17: ...switching function Hno hysteresis function normally open Hnc hysteresis function normally closed Fno window function normally open Fnc window function normally closed Select SP2 and set the value at which the output switches Select rP2 and set the value at which the output switches back 9 3 Settings for temperature monitoring 9 3 1 Settings for limit value monitoring with OUT2 Select SEL2 and set ...

Page 18: ...rd3 display as for d1 d2 d3 rotated by 180 OFF the display is switched off in the operating mode 9 4 4 Customer specific calibration of the curve of measured values Select CGA and set the value between 60 and 140 100 factory preset 9 4 5 Calibration reset Select CAr Press Set and keep it pressed until is displayed Press Mode Enter briefly Value is reset CGA 100 9 4 6 Setting the start up delay Sel...

Page 19: ... HI or LO Press Set and keep it pressed until is displayed Press Mode Enter briefly It makes sense to delete the memories as soon as the unit works under normal operating conditions for the first time 9 5 2 Reset all parameters to the factory setting Select rES then press Set and keep it pressed until is dis played Press Mode Enter briefly The factory setting is listed at the end of the instructio...

Page 20: ...for NC function Hnc Fnc 10 1 Read the set parameters Press Mode Enter briefly to scroll the parameters Press Set briefly when the requested parameter is displayed The unit displays the corresponding parameter value After about 15 s it again displays the parameter then it returns to the Run mode 10 2 Changing the display unit in the Run mode Press Set briefly in the Run mode to move from one displa...

Page 21: ...s Set briefly The latest measured values are displayed IOE Flow sensor faulty Loc Setting pushbuttons locked parameter change rejected VMR final value of the measuring range 10 4 General operating conditions Avoid deposits accumulated gas and air in the pipe system Greater amounts of accumulated gas and air in the medium or unit generally lead to the display SEnS For medium temperatures over 50 C ...

Page 22: ...22 11 Scale drawing 1 Display 2 Connector electrical connection 3 Marking direction of flow ...

Page 23: ...h gpm gph Measuring range 0 0 100 0 0 00 6 00 0 00 26 42 0 1585 Resolution 0 2 0 01 0 02 1 Display range 0 0 120 0 0 00 7 20 0 00 31 70 0 1902 Maximum permissible flow rate 110 0 6 60 31 70 1902 Response time ms 250 dAP 0 Damping flow signal dAP s 0 0 1 0 Start up delay s 0 50 Accuracy water 3 MV 0 2 MVR glycol solutions 35 5 MV 0 5 MVR oils viscosity 68 mm s at 40 C 5 MV 0 5 MVR Repeatability VMR...

Page 24: ...r film polyamide Protection IP 67 III Insulation resistance MΩ 100 500 V DC Shock resistance g 20 DIN IEC 68 2 27 11ms Vibration resistance g 5 DIN IEC 68 2 6 55 2000 Hz EMC IEC 1000 4 2 ESD 4 8 KV IEC 1000 4 3 HF radiated 10 V m IEC 1000 4 4 Burst 2 KV IEC 1000 4 5 Surge 0 5 1 KV IEC 1000 4 6 HF conducted 10 V 1 to EN50178 SELV PELV MV measured value VMR final value of the measuring range 12 1 Se...

Page 25: ...ing User setting SP1 20 0 rP1 10 0 OU1 Hno OU2 Hno SP2 FLOW 80 0 rP2 FLOW 60 0 SP2 TEMP 62 0 rP2 TEMP 44 0 CGA 100 FOU1 OFF FOU2 OFF dSt 0 0 P n PnP dAP 0 6 rTo OFF diS d2 UniT Lmin UniF C SEL2 FLOW MEDI H2O More information at www ifm com ...