background image

 

 

 

 

Spec No: 1S6810,    Rev :  0 

 

Release Date: 

6/4/2019      Author: C. Svelnis 

Spec Type: Customer    Product Family: (G) Multipole 

      

 

Page 1 of 2 

Anderson Power Products® 

13 Pratts Junction Road 

Sterling, MA 01564-2305 USA 

Tel: 978-422-3600 

Fax: 978-422-0128 

www.andersonpower.com   

ISO 9001 Certified                                                                                      

1x4 Auxiliary Connector Assembly Instructions

 

 

Four Pole Connector with Single Piece Housing for use in SBE®, SBX® and SBO® 

housings 

 

For installation by a qualified electrician in accordance with national electrical codes and the following 

instruction.  The suitability of this type of termination must be evaluated by the Underwriter’s Laboratories, 

Inc. and the Canadian Standard Association for the end use application. 

 

Assemble contacts to cables according to the equipment manufacturer’s assembly instructions.  The following 

is supplied as a reference. 

 

 

Table A: Recommended Crimp/Assembly Tools 

Tool Type 

Wire Sizes 

Tool Part 

Number 

AWG 

Mm² 

Crimp- Hand tool 

#24-12 awg  

.5 – 4.0 

PM1000G1 

Contact Insertion* 

#24 – 16 awg* 

.5 – 1.5mm²*  PM1002G1 

Contact Extraction 

#24-12 awg  

.5 – 4.0 

PM1003G1 

*

when larger wires are used, the insertion tool is not needed

 

Step 1: 

 

 

Strip cables to dimensions in table below. 

Table B: Cable Stripping Dimensions 

Contact Type 

Dimension "X" 

Notes 

IN 

MM 

Aux. Pin 

0.18 

4.6 

For use when wire insulation OD is 
smaller than crimp barrel ID. 

Aux. Socket 

0.21 

5.3 

Aux. Pin 

0.24 

6.1 

For use when wire insulation OD is 
larger than crimp barrel ID. 

Aux. Socket 

0.28 

7.1 

Please note that instructions are included with each crimp tool for terminating specific contacts.  Use of crimp tools not 
approved by Anderson Power Products can affect UL and CSA approval

.

 

 

Step 2: 

 

 

*Crimp or solder contacts to cable following crimp tool instructions or recommended soldering  
techniques. 

 
 
 
 

Recommended Soldering Techniques 

Use rosin flux solder only.  Wrap cable strands.  Melt solder into well, then heat and insert stripped cable.  
Continue heating well until solder flows into wire, being careful not to over flow onto contact surfaces.  
DO NOT SOLDER DIP CONTACTS.  Cable clamps or cable ties are required for solder

 connections

 

Reviews: