GENERAL DESCRIPTION

 

 

The 

TAU

-

TH

-

01

-

BL

Taurus series detector samples the environmental temperature in the protected area; when the environmental tempera-

ture level or variation rate exceeds a certain degree, a fire alarm message is sent to the control panel.

 

TAU

-

TH

-

01

-

BL

is battery powered and doesn

t need any system cabling installation.

 

LOCATION SELECTION

 

 

Select a location for the detector that conforms to your local applicable safety standards and that is in a good position for sending / receiving 

wireless signals to / from the father 

TAU

-

TRM

-

01

TAU

-

CEM

-

01

 or 

TAU

-

EXM

-

01

 network device.

 

 

Mount  the  detector  as  far  as  possible  from  metal  objects,  metal  doors,  metal  window  openings,  etc.  as  well  as  cable  conductors,  cables 

(especially from computers), otherwise the operating distance may greatly drop.

 

 

The 

TAU

-

TH

-

01

-

BL

must NOT be installed near electronic devices and computer equipment that can interfere with its wireless communication 

quality.

 

TAU

-

TH

-

01

-

BL

 

Hyfire Taurus Heat Detector Black

 

DEPLOYMENT PROCEDURE

 

 

1)

 

Select a location for the detector. See 

LOCATION SELECTION

.

 

2)

 

Unbox the detector from its packaging.

 

3)

 

Detach the detector from its base. See 

INSTALLING / REMOVING THE DETECTOR

.

 

4)

 

Detach the battery cover from the detector. See 

BATTERY COVER

.

 

5.1)

 

a)

 

Link the detector to the system (insulating tab extraction).

 

 

 

See 

LINKING 

-

 WAKE

-

UP 

-

 WITH INSULATING TAB

.

 

 

 

See 

LINKING 

-

 ONE

-

BY

-

ONE 

-

 WITH INSULATING TAB

.

 

--

 or 

-- 

5.2)

 

a)

 

Power up the detector.

 

 

See 

POWERING UP 

-

 FIRST TIME USE 

-

 WITHOUT INSULATING TAB

.

 

 

See 

POWERING UP 

-

 RECOVERY

.

 

 

b)

 

Link the detector to the system (moving the link program switch).

 

 

See 

LINKING 

-

 WAKE

-

UP 

-

 WITHOUT INSULATING TAB

.

 

 

See 

LINKING 

-

 ONE

-

BY

-

ONE 

-

 WITHOUT INSULATING TAB

.

 

6)

 

Reinstall the battery cover on the detector. See 

BATTERY COVER

.

 

7)

 

Detach the identification tag from the base adapter. See 

IDENTIFYING THE DETECTOR

.

 

8)

 

Install the base adapter. See 

FIXING THE ADAPTOR BASE

.

 

9)

 

Install the detector on the base adapter.  See 

INSTALLING / REMOVING THE DETECTOR

.

 

10)

 

Install the identification tag to the base adapter, with all relevant information written / labelled on it. See 

IDENTIFYING THE DETECTOR

.

 

11)

 

Secure the detector to its base with its safety anti

-

tamper screw. See 

INSTALLING THE SAFETY SCREW

.

 

12)

 

Test the detector. See 

TESTING

.

 

It  is  advisable  to  use  the TAU

-

STK

-

01  survey  kit 

to locate a good wireless installation location. 

 

Hyfire Wireless Fire Solutions Ltd 

-

 Unit B12a, Holly Farm Business Park, Honiley, 

 

Warwickshire, CV8 1NP 

-

 United Kingdom

 

www.hyfirewireless.com

 

1)

 

LED indicators

 

2)

 

Battery A

 

3)

 

Battery B

 

4)

 

Link program switch

 

5)

 

Tamper spring (internal)

 

6)

 

Tamper switch (external)

 

7)

 

Battery cover

 

8)

 

Battery cover latch

 

9)

 

Insulating tab

 

10)

 

Wall fixing openings

 

11)

 

Identification tag

 

12)

 

Identification tag lodgement

 

13)

 

Magnet test area

 

14)

 

Base / detector reference marks

 

15)

 

Safety screw

 

1

 

1

 

2

 

3

 

4

 

5

 

Picture 1

 

 

1

 

6

 

7

 

8

 

9

 

10

 

10

 

11

 

13

 

14

 

15

 

12

 

All pictures are for product in black variant. Shown white for illustrative purpose only

 

BATTERY COVER

 

 

Detach the battery cover by pulling and lifting the closing latch.

 

To  reinstall  the  battery  cover,  insert  its  two  hooks  into  their  corresponding 

detector

s recesses; then block it by pressing down the opposite side, until you 

hear the click of the closing latch.

 

 

INSTALLING / REMOVING THE DETECTOR

 

 

Rotate the detector clockwise on its adaptor base to install it.

 

Rotate the detector anti

-

clockwise from its adaptor base to remove it.

 

 

IDENTIFYING THE DETECTOR

 

 

The detector can be visually identified by the detachable tag imprinted with the adaptor base.

 

1)

 

Detach the tag from the base.

 

2)

 

Write / label the relevant identification information on the tag.

 

3)

 

Insert the tag into its lodgement on the side of the adaptor base.

 

 

FIXING THE ADAPTOR BASE

 

 

Fix the base to the wall with suitable screws.

 

 

INSTALLING THE SAFETY SCREW

 

 

Always install the safety blocking screw. 

 

 

LED INDICATORS STATUS MESSAGES

 

 

The two LED indicators communicate to the final user the status of the 

TAU

-

TH

-

01

.

 

POWERING UP AND LINKING 

-

 PRELIMINARY NOTES

 

 

TAU

-

TH

-

01

-

BL

needs to be powered up with the supplied batteries.

 

Linking  is  the  operation  through  which 

TAU

-

TH

-

01

-

BL 

is 

wirelessly  connected

” 

to  a 

TAU

-

TRM

-

01

TAU

-

CEM

-

01

  or 

TAU

-

EXM

-

01

  Taurus 

network device.

 

 

LINKING 

-

 WAKE

-

UP 

-

 WITH INSULATING TAB

 

 

Wake

-

up

” 

linking consists in associating one or more child devices to the Taurus system altogether in a single operation.

 

Wake

-

up  is  performed  either  through  the 

TauREX

  software  or  the 

TAU

-

TRM

-

01

  / 

TAU

-

CEM

-

01

  keyboard

-

screen interface; it  CANNOT  be 

done through 

TAU

-

EXM

-

01

 devices.

 

1)

 

Create the 

virtual model

” 

of the 

TAU

-

TH

-

01

-

BL

either on 

TauREX

 or on the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

2)

 

Pull out the insulating tab.

 

3)

 

Trigger the wake

-

up procedure either from 

TauREX

 or from the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

4)

 

Wait the end of the 

wake

-

up

” 

linking procedure.

 

5)

 

Check on 

TauREX

 or from 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 for linking success. Consult their user manual.

 

 

LINKING 

-

 ONE

-

BY

-

ONE 

-

 WITH INSULATING TAB

 

 

One

-

by

-

one

” 

linking consists in associating one child device at a time to the Taurus system.

 

This operation is performed either through the 

TauREX

 software or the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 keyboard

-

screen interface; it CANNOT 

be done through 

TAU

-

EXM

-

01

 devices.

 

1)

 

Create the 

virtual model

” 

of the 

TAU

-

TH

-

01

-

BL

either on 

TauREX

 or on the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

2)

 

Trigger the linking procedure either from 

TauREX

 or from the 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

.

 

3)

 

Pull out the insulating tab.

 

4)

 

Wait the end of the 

one

-

by

-

one

” 

linking procedure.

 

5)

 

Check on 

TauREX

 or from 

TAU

-

TRM

-

01

 / 

TAU

-

CEM

-

01

 for linking suc-

cess. Consult their user manual.

 

Always install the battery cover, since it is a vital 

part  of  the  tamper  detection  feature.  Make  sure 

the  battery  cover  is  safely  fixed,  blocked  and 

closed.  Make  sure  that  the  internal  tamper  spring  fits 

completely  into  its  battery  cover

s  lodgement.  Check, 

more than once, that the cover

s external tamper switch 

clicks when pressed.

 

When  extracting  the  insulating  tab,  keep  both 

batteries into their lodgements with your thumb, 

since they can be accidentally pulled out too.

 

[email protected]

 

L20

-

TWDT1

-

1400 (vA.1)

 

 

2

 

Check  the  alignment  of  the  raised  reference 

marks on the detector and on the base.

 

Always install the safety blocking screw. 

 

Table 1

 

Please mind that LED signalling burns out battery 

power, therefore reducing batteries lifespan.

 

Device status

 

LEDs indication

 

Power up (DIP on 

ON

”)

 

Blinks red 4 times

 

Power up (DIP opposite 

ON

”) 

 

Blinks green 4 times 

 

Entering wake

-

up mode

 

Blinks alternatively green / red 4 times

 

Link success (one

-

by

-

one)

 

Blinks green 4 times, then the same pattern again

 

Link failure (one

-

by

-

one)

 

Enters wake

-

up mode and signals 

Entering wake

-

up mode

” 

following this failure

 

Link success (wake

-

up)

 

Blinks green 4 times, then same pattern again

 

Link failure (wake

-

up)

 

Blinks green 4 times, then blinks red on once, then blinks alternatively green / red 4 times

 

Normal condition

 

LED off (can be programmed so as to blink green every wireless communication)

 

Alarm activation

 

Blinks red every 2 seconds

 

Battery fault

 

LED off (can be programmed so as to blink amber every 5 seconds)

 

Tamper fault

 

LED off

 

Replaced

 

Blinks amber 2 times

 

Test mode active

 

Blinks green

 