background image

NOTE! To the installer: Please make sure you provide 
this manual to the owner of the pumping equip ment or to 
the responsible party who maintains the system.

Part # 5625-359-1

Item # E-03-359   04/09

PULTRUDED RAIL SYSTEM

Summary of Contents for PULTRUDED RAIL SYSTEM

Page 1: ...To the installer Please make sure you provide this manual to the owner of the pumping equip ment or to the responsible party who maintains the system Part 5625 359 1 Item E 03 359 04 09 PULTRUDED RAIL SYSTEM ...

Page 2: ...nge should release easily Step 2 Attach supplied chain leg to achieve a three point lift Test the balance of the pump by adjusting the location of the shackle in reference to individual chain links The pump must be level to function properly WARNING If the sealing flange end of pump is raised above the horizontal the guide rail may be damaged upon lowering the pump Ensure pump is horizontal before...

Page 3: ...vertical discharge piping modules to elbow using bolts nuts lock washers and gasket NOTE When increasing the pipe size at the discharge elbow an eccentric flanged reducer coupling may be required to avoid interference with the guide rail See Installation Data Install remainder of the sump discharge piping This typically includes a vertical run of piping appropriately sized and configured to mate w...

Page 4: ...ate Guide Rail Bracing Sump depths of 9 6 and greater require intermediate guide rail bracing The braces mount on the vertical discharge pipes with U bolts which are sized according to the discharge pipe size The number of guide rail braces required are as follows Sump Depths 9 6 to 18 0 1 guide rail brace required 18 6 to 27 0 2 guide rail braces required 27 6 to 30 0 3 guide rail braces required...

Page 5: ... the pump or bottom of the basin Shorten cords to suit the installation See Bulletin Q 701 for the Installation and Service Manual on the electrical Control Panel system 11B Control Panel Mounted Remote from Basin If the Control Panel is remotely located instead of on the mounting stand at the basin install coupling through basin wall Screw protective bushing from inside basin into coupling all fu...

Page 6: ...clogged Amperage higher than name plate will indicate this 2 Pump rotation may be wrong Reversing any two line leads on three phase pumps will reverse the rotation 3 Discharge plug valve may be closed 4 Plugging anywhere from impeller to sealing flange This is evident if no water runs out of sealing flange after raising the pump Pull the pump from the basin to find the clog 5 Plugging beyond the s...

Page 7: ...LTRUDED RAIL I BEAM HYDRAULIC SEALING FLANGE ASSEMBLY WITH BUNA DIAPHRAGM right hand to suspend the float the pump should continue to run The pump should stop when raising the left hand to suspend the float If this procedure does not cause the pump to operate as described either order new 3900 mercury float switches or replace alternator relay PULTRUDED RAIL SYSTEM ...

Page 8: ...XCEEDING 9 6 HYDROMATIC 3900 SUBMERSIBLE LEVEL SWITCHES HYDROMATIC NON CLOG SUBMERSIBLE PUMP HOPPER BOTTOM RECOMMENDED DISCH ELBOW FRP GUIDE RAIL LIFTING CHAIN VENT PIPING DEPTH OF WELL FT IN INFLUENT PIPE INV EL CONTROL POWER CABLES CONTROL CABLE MOUNTING BRACKET E G F SUMP SUMP SUMP MIN WATER LEVEL GRADE ELEV ELEV D C SIMPLEX 3 THROUGH 6 PUMPS ...

Page 9: ... EXCEEDING 9 6 HYDROMATIC 3900 SUBMERSIBLE LEVEL SWITCHES HYDROMATIC NON CLOG SUBMERSIBLE PUMP HOPPER BOTTOM RECOMMENDED DISCH ELBOW FRP GUIDE RAIL LIFTING CHAIN VENT PIPING DEPTH OF WELL FT IN INFLUENT PIPE INV EL CONTROL POWER CABLES CONTROL CABLE MOUNTING BRACKET H F G E SUMP SUMP SUMP SUMP MIN WATER LEVEL GRADE ELEV ELEV DUPLEX 3 THROUGH 6 PUMPS ...

Page 10: ...ons provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other than for what it is designed and man...

Page 11: ......

Page 12: ...___________________________ D Incoming line voltage _________________________ Actual _____________________________ E Voltage to pumps ____________________________ Actual _____________________________ F Type of junction box _____________________________ Manufacturer _______________________ G Are floats installed in wet well _______________________________________________________ H Are floats set to...

Reviews: