background image

VisionPRO® IAQ

Equipment Interface Module

Installation 

Guide

® U.S. Registered Trademark. US Patent No. 6,208,263; 6,373,376; 

6,448,901; 7,012,927 and other patents pending. 

Copyright © 2011 Honeywell International Inc. 

All rights reserved.

69-1823EFS-05

English: 

Page 1

 • Français: 

Page 6

 • Español: 

Página 11

For up to 4 Heat/2 Cool systems with Honeywell THM5421C or equivalent.

System Types

CAUTION: ELECTRICAL HAZARD. 

Can cause electrical shock or equipment damage. 

Disconnect power before beginning installation.

MERCURY NOTICE: 

If this product is replacing a control that contains mercury in a 

sealed tube, do not place the old control in the trash. Contact your local waste manage-

ment authority for instructions regarding recycling and proper disposal.

Must be installed by a trained, experienced technician

Read these instructions carefully. Failure to follow these instructions  

can damage the product or cause a hazardous condition.

•  Gas, oil, or electric heat with air 

conditioning 

•  Warm air, hot water, high-

efficiency furnaces, heat pumps, 
steam, gravity

•  Heat only
•  Heat only with fan
•  Cool only

Summary of Contents for thm5421c

Page 1: ...ipment damage Disconnect power before beginning installation MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste manage ment authority for instructions regarding recycling and proper disposal Must be installed by a trained experienced technician Read these instructions carefully Failure to f...

Page 2: ...ng pages CAUTION This product may be damaged if mounted inside HVAC equipment Install only on the outside of HVAC equipment LED Restore power and check LED LED blinks rapidly Normal information transfer LED blinks once Incoming message to EIM LED blinks continuously Wiring problem Check wiring to terminals 1 2 3 LED always off Wiring problem Check wiring to terminals 1 2 3 LED always on EIM may ne...

Page 3: ...R RC RH 24 VAC H1 U M2 D1 H M2 V1 N T2 OR POWERED HUMIDIFIER Typical hookup of powered humidifier M23488 FACTORY INSTALLED JUMPER BETWEEN R RC AND RH 1 2 3 C R RC RH COMMUNICATION TERMINALS COMMUNICATION LED W1 W2 W3 Y Y2 G 24 VAC O B AUX AUX2 Y Y2 G 1 2 3 CONV HP CHANGEOVER AUX 1 HEAT 3 AUX 2 HEAT 4 COMP 1 COMP 2 FAN RELAY WIRE TO TERMINALS ON THERMOSTAT 1 1 Typical hookup of heat pump system wit...

Page 4: ...peed M23494 1 2 3 C R RC RH 24 VAC H1 U M2 D1 H M2 V1 N T2 OR POWERED VENTILATOR Typical hookup of powered ventilation M23495 1 2 3 C R RC RH 24 VAC H1 U M2 D1 H M2 V1 N T2 OR FRESH AIR DAMPER DH90 BLUE GREEN YELLOW RED WHITE FIELD INSTALLED JUMPER BETWEEN DHM 1 AND VNT 1 Hookup of Honeywell DH90 with fresh air intake for ventilation M23492 1 2 3 C R RC RH 24 VAC H1 U M2 D1 H M2 V1 N T2 OR POWERED...

Page 5: ...midity 5 to 90 non condensing Physical Dimensions 7 9 16 H x 4 35 64 W x 1 21 64 D 185 mm H x 116 mm W x 34 mm D Electrical Ratings Terminal Voltage 50 60Hz Running Current W Heating 20 30 Vac 0 02 1 0 A W2 Heating 20 30 Vac 0 02 1 0 A W3 Heating 20 30 Vac 0 02 1 0 A Y Cooling 20 30 Vac 0 02 1 0 A Y2 Cooling 20 30 Vac 0 02 1 0 A Aux Auxiliary Heat 20 30 Vac 0 02 1 0 A Aux2 Auxiliary Heat 20 30 Vac...

Page 6: ... et autres brevets en instance Copyright 2011 Honeywell International Inc Tous droits réservés MISE EN GARDE RISQUE ÉLECTRIQUE Peut provoquer des secousses électriques ou endommager le matériel Coupez l alimentation avant d entreprendre l installation AVIS CONCERNANT LE MERCURE Si ce produit remplace un dispositif de régula tion contenant une ampoule de mercure ne placez pas ce dernier dans les or...

Page 7: ...ur éviter des dommages n installez pas ce produit à l intérieur d équipement de la HVAC Installez seulement sur l extérieur de l équipement de la HVAC LED Reconstituerez l énergie électrique vérifiez l opération La lumière clignote rapidement Transfert de l information normal Clignotements de lumière une fois Message entrant à EIM La lumière clignote sans interruption Problème de câblage Vérifiez ...

Page 8: ...V1 N T2 OU HUMIDIFICATEUR ALIMENTÉ Raccordement type d un humidificateur alimenté MF23488 CAVALIER INSTALLÉ À L USINE ENTRE R RC ET RH 1 2 3 C R RC RH BORNES DE COMMUNICATION VOYANT DE COMMUNICATION W1 W2 W3 Y Y2 G 24 VCA O B AUX AUX2 Y Y2 G 1 2 3 CONV HP COMMUTATION CHAUD FROID AUX 1 CHAUFFAGE 3 AUX 2 CHAUFFAGE 4 COMP 1 COMP 2 RELAIS DE VENTILATEUR FIL VERS LES BORNES DU THERMOSTAT 1 1 Raccordeme...

Page 9: ...C R RC RH 24 VCA H1 U M2 D1 H M2 V1 N T2 OU VENTILATEUR ALIMENTÉ Raccordement type d un ventilateur alimenté MF23495 1 2 3 C R RC RH 24 VCA H1 U M2 D1 H M2 V1 N T2 OU REGISTRE D AIR FRAIS DH90 BLEU VERT JAUNE ROUGE BLANC CAVALIER INSTALLÉ À L USINE ENTRE DHM1 ET VNT1 Raccordement d un DH90 de Honeywell avec apport d air neuf pour la ventilation MF23492 1 2 3 C R RC RH 24 VCA H1 U M2 D1 H M2 V1 N T...

Page 10: ...e fonctionnement 5 à 90 sin condensación Dimensions 7 9 16 H x 4 35 64 L x 1 21 64 Ép 185 mm H x 116 mm L x 34 mm Ép Caractéristiques électriques Borne Tension 50 60Hz Courant W Chauffage 20 30 Vca 0 02 1 0 A W2 Chauffage 20 30 Vca 0 02 1 0 A W3 Chauffage 20 30 Vca 0 02 1 0 A Y Climatisation 20 30 Vca 0 02 1 0 A Y2 Climatisation 20 30 Vca 0 02 1 0 A Aux Chauffage aux 20 30 Vca 0 02 1 0 A Aux2 Chau...

Page 11: ... 448 901 7 012 927 y otras patentes pendientes Copyright 2011 Honeywell International Inc Todos los derechos reservados PRECAUCIÓN PELIGRO ELÉCTRICO Puede causar descarga eléctrica o daño del equipo Desconecte la alimentación de energía antes de iniciar la instalación AVISO DE MERCURIO Si este producto reemplaza a un control que contiene mer curio en un tubo sellado no arroje el control viejo a la...

Page 12: ...te producto dentro del equipo de la HVAC Instale solamente en el exterior del equipo de la HVAC LED Reactivaron corriente eléctrica y verifique la operación La luz centelleo rápidamente Transmisión informativa normal Centelleos de la luz una vez Mensaje entrante a EIM La luz centelleo continuamente Problema del cableado Compruebe el cableado a los terminales 1 2 3 Luz siempre apagado Problema del ...

Page 13: ...H M2 V1 N T2 O HUMIDIFICADOR CON ENERGÍA Conexión típica de humidificador con energía MS23488 PUENTE INSTALADO EN FÁBRICA ENTRE R RC Y RH 1 2 3 C R RC RH TERMINALES DE COMUNICACIÓN LED DE COMUNICACIÓN W1 W2 W3 Y Y2 G 24 VCA O B AUX AUX2 Y Y2 G 1 2 3 CONV HP CONVERSIÓN AUX 1 CALEFACCIÓN 3 AUX 2 CALEFACCIÓN 4 RELÉ DE REFRIG 4 RELÉ DE REFRIG 5 RELÉ DEL VENTILADOR CABLE A TERMINALES EN EL TERMOSTATO 1...

Page 14: ...4 VCA H1 U M2 D1 H M2 V1 N T2 O VENTILADOR CON ENERGÍA Conexión típica de ventilación con energía MS23495 1 2 3 C R RC RH 24 VCA H1 U M2 D1 H M2 V1 N T2 O HUMIDIFICADOR DE AIRE FRESCO DH90 AZUL VERDE AMARILLO ROJO BLANCO PUENTE INSTALADO EN CAMPO ENTRE DHM 1 Y VNT 1 Conexión del modelo DH90 Honeywell con entrada de aire fresco para ventilación MS23492 1 2 3 C R RC RH 24 VCA H1 U M2 D1 H M2 V1 N T2...

Page 15: ...namiento 5 a 90 sin condensación Dimensiones físicas 7 9 16 H x 4 35 64 A x 1 21 64 P 185 mm H x 116 mm A x 34 mm P Regímenes eléctricos Terminal Tensión 50 60Hz Corriente W Calefacción 20 30 VCA 0 02 1 0 A W2 Calefacción 20 30 VCA 0 02 1 0 A W3 Calefacción 20 30 VCA 0 02 1 0 A Y Refrigeración 20 30 VCA 0 02 1 0 A Y2 Refrigeración 20 30 VCA 0 02 1 0 A Aux Calefacción aux 20 30 VCA 0 02 1 0 A Aux2 ...

Page 16: ...onal Inc 69 1823EFS 05 M S Rev 03 11 Need Help For assistance with this product please visit http yourhome honeywell com or call Honeywell Customer Care toll free at 1 800 468 1502 Besoin d aide Pour obtenir de l aide et apprendre à faire fonctionner votre produit Honeywell veuillez consulter le site Web http yourhome honeywell com ou vous adresser aux Services à la clientèle de Honeywell en compo...

Reviews: