INSTRUCTION GUIDE: ZONESTAT AND SENSORSTAT

IG1603EW    10/12

997-012330-2-R Rev B

Instruction Guide:

IntelliZone2 ZoneStat and SensorStat

ZoneStat Installation Instructions

1. 

Remove the cover from the ZoneStat and attach the 
backplate to the wall making sure the thermostat is level.

2. 

Connect 4 conductor (minimum 18 gauge) wire from the 
ZoneStat to IntelliZone2.

3. 

Zone ID must be set for each Zone (2-6) using the DIP 
switches on the PCB. See the Zone ID Codes illustration 
for configuration options. Zone ID can be confirmed on the 
ZoneStat by pressing the cancel button for 5 seconds.

4. 

Seal the hole in the wall to prevent air leaks and replace the 
front cover.

IntelliZone2 ZoneStat

IntelliZone2 SensorStat

SensorStat Installation Instructions

1. 

Remove the cover from the SensorStat and attach the 
backplate to the wall in one of the two orientations shown 
below.

2. 

Connect 4 conductor (minimum 18 gauge) wire from the 
SensorStat to IntelliZone2.

3. 

Zone ID must be set for each Zone (2-6) using the DIP 
switches on the PCB. See the Zone ID Codes illustration for 
configuration options.

4. 

Seal the hole in the wall to prevent air leaks and replace the 
front cover.

A+

R

C

B-

P14 – Zone 4

A+

R

C

B-

P15 – Zone 5

A+

R

C

B-

Zone 3 Stat

On

3
2  
1

Zone 4 code shown

A+

R

C

B-

Zone 5 Stat

On

3
2  
1

Zone 5 code shown

ZoneStat  

SensorStat

Zone ID must be set for each Zone 2-6. ID can be

confirmed on ZoneStat by pressing cancel button for

5 sec. ID shown on display. See Zone ID Codes.

 

Zone ID must be set for each Zone 2-6. ID cannot be

confirmed on Zone SensorStat. See Zone ID Codes.  

IntelliZone2

Relay Board 

On

3
2  
1

On

3
2  
1

On

3
2  
1

Zone 4

Zone 5

Zone 3

On

3
2  
1

Zone 2

On

3
2  
1

Zone 6

Zone ID Codes

NOTES:

1) Zone ID must be set for each Zone 2-6. ID can be confirmed on ZoneStat
    by pressing cancel button for 5 sec. ID shown on display.
2) Small screw driver can be used to set ID thru protective plastic skin!
3) MasterStat always Zone 1. Zone ID not necessary. 

NOTE:

 The SensorStat must be installed in one of the two orientations

shown above for the most accurate temperature sensing. 

SensorStat Board

UP

SensorStat Installation Orientation

Отзывы: