Programmable Thermostats

Application

The T8132C Programmable Thermostat provides en-

ergy savings for heating and cooling applications. Separate
programs can be set for weekdays and weekends.

Check Table 1 to make sure the T8132C Thermostat is

compatible with the intended system.

TABLE 1—COMPATIBILITY CHART.

LOCATION

Locate the thermostat about 5 ft (1.5m) above the floor

in an area with good air circulation at average temperature.

Do not mount the thermostat where it may be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air ducts.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall

behind the thermostat.

MOUNT THERMOSTAT MOUNTING PLATE
(FIG. 1)

Position mounting plate on wall. Use spirit level to make

sure mounting plate is level. Use a pencil to mark the two
mounting holes.

Level for appearance only; thermostat functions prop-

erly even when not level. Tighten mounting screws.

Remove mounting plate from wall, and drill 3/16 inch

holes in wall (if drywall) as marked. For firmer material
such as plaster or wood, drill 7/32 inch holes. Gently tap
anchors (provided) into drilled holes until flush with the
wall.

Reposition mounting plate over holes, pulling wires

through wiring opening. Loosely insert two mounting screws
into holes.

Fig. 1—Mounting thermostat mounting plate.

WALL

WIRES THROUGH
WALL OPENING

WALL
ANCHORS (2)

MOUNTING
PLATE

MOUNTING
SCREWS (2)

M1718

WIRING

All wiring must comply with all applicable electrical

codes, ordinances, and regulations. Follow instructions
provided with the controlled equipment.

Run the required number of wires to the thermostat

location (check the appropriate wiring diagram). Refer to
Fig. 3 through 6 for typical wiring diagrams.

In 5-wire installations only, be sure to remove the fac-

tory-installed jumper connecting terminals R and Rc.

System Type

Compatible

With T8131C

Gas—Standing Pilot

Yes

Gas—Electronic Ignition

Yes

Gas-Fired Boilers

Yes

a

Gas—Millivolt

No

Oil-Fired Boilers

Yes

a

Oil-Fired Furnace

Yes

Electric Furnace

Yes

Electric Air Conditioning

Yes

Baseboard Electric  
(120/240 Line Volt)

No

Heat pumps/Multistage Equipment

No

Not compatible with any 120/240 volt circuit.
Not designed for steam or gravity systems.

a

Compatible with 2-wire Honeywell zone valves. Isolating
relay required for 3-wire thermostats for zone valves. Not
compatible with 2-wire White Rodgers no. 1361 Valves.

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to fol-

low instructions can damage product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Make sure installer is a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out product operation.

CAUTION

Disconnect power supply before wiring to pre-
vent electrical shock or equipment damage.

Summary of Contents for T8132C

Page 1: ...L WIRES THROUGH WALL OPENING WALL ANCHORS 2 MOUNTING PLATE MOUNTING SCREWS 2 M1718 WIRING All wiring must comply with all applicable electrical codes ordinances and regulations Follow instructions provided with the controlled equipment Run the required number of wires to the thermostat location check the appropriate wiring diagram Refer to Fig 3 through 6 for typical wiring diagrams In 5 wire inst...

Page 2: ...R VALVE COIL 1 1 Fig 6 3 wire cool only application jumper intact R Rc W Y G B D A C 3 WIRE COOL ONLY JUMPER INTACT L1 HOT L2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 1 JUMPER M848A COOLING CONTACTOR COIL FAN RELAY ADJUST FAN OPERATION SWITCH AS REQUIRED The thermostat fan operation switch labeled FUEL SWITCH see Fig 7 is factory set in the F position This is the c...

Page 3: ... battery door see Fig 8 Install the fresh batteries as shown making sure positive and negative terminals are oriented correctly see Fig 9 Replace battery door Fig 9 Installing position for batteries M1719C REMOVING BATTERY DOOR Fig 8 Removing battery door As the batteries are running low a bAt Lo indicator flashes for one to two months before batteries run out completely Replace the batteries as s...

Page 4: ...ove room temperature After a short delay heating should start and the fan should run immediately if fan operation switch is set in E position Press key until setting is about 10 F 6 C below room temperature The heating equipment should shut off Cooling To avoid possible compressor damage do not operate the cooling system when outside temperature is below 50 F 10 C See compressor manufacturer instr...

Page 5: ...or higher 45 F to 88 F than 88 F 31 C during programming Heating will not come on Check that switch on thermostat is set to HEAT Check the system fuse or circuit breaker and replace or reset if necessary If display is blank or displays bAt Lo install fresh batteries If temperature setting is higher than current temperature and SYSTEM ON indicator is lit see furnace manufacturer instructions Coolin...

Page 6: ...uently The burner on time Readjust according to instructions on page 2 is too short or too long IF THEN The thermostat current setting does Check that the wiring hole in the wall behind the wallplate was not match the display temperature plugged with insulation to prevent drafts that might adversely affect thermostat operation Be aware that it is normal for the current setting and display temperat...