HL116 Series thermostats are available for individual room temperature control in 

residential, industrial and business premises. Suitable for 2-pipe or 4-pipe Fan Coil configuration.   

HL116 adopt digital control technology with LCD display, It shows the following items: 

working states (cool, heat, auto or ventilation), the room temperature, set-point. There are 

following keys on the panel: Exchange mode (cool, heat, auto or ventilation) “ ”, set-point 

temperature “

S

” and “

T

”; switch: Power On/Off, and Select fan speed (high, medium or low). 

 

 

 

 

 

 

 

 

 

BASIC FEATURES                                                        STATUS DISPLAY 

 Room temperature setting 

 Manual 3-speed changeover 

 Defrost (low temperature protection) 

 Blue Backlight 

 Working Status: Cool 

, Heat 

, Auto 

 and  

Ventilation 

   

 Room temperature display 

 Temperature setting display 

SPECIFICATIONS 

 Sensing element:     NTC 

 Accuracy :                      ± 1

 

 Set-point range:      5  to 35

 

 Display range:              0

50

 

 Operation environment: 0

45

 

 Operating Humidity:  5

95%RH (non-condensing) 

 Power supply:       AC 220V ± 10%, 50/60Hz 

 Switch current rating: Resistive: 2A, Inductive: 1A 

 Rated Power: 

<

 2 W 

 Wirings: Screw-in terminals, each terminal capable of 

accepting 2 x 1.5 mm

2

 or 1 x 2.5 mm

2

 wires 

 Housing: ABS + PC Flame Retardant 

 Dimensions: 86 × 86 × 23.5 mm ( W × H × D ) 

 Hole pitch: 60 mm ( Standard ) 

 Protection Class: IP30 

 Display: LCD 

OPERATION 

"

 On/Off: Slide the switch to “LOW”, “MED” or “HIGH” turn on; Slide the switch to “OFF”, to turn off thermostat and its 

output. 

"

 Setting temperature: Press “

T

” to reduce set-point, press “

S

” to raise set-point, and 1

 changed once. 

"

 Mode Selection:   

HL116DA/DA2/P: When turn on, Press “ ” to change system working in cooling “

”, heating “

” or ventilation “

” 

mode, the related icon will flash, and continuous switch can be performed among three models hereinbefore while “ ” key is 

pressed without release.

 

HL116(A)FCV2: When turn on, Press “ ” to change system working in cooling “

”, heating “

”, Auto “

” or ventilation 

” mode in turn, the related icon will flash, and continuous switch can be performed among four models hereinbefore while 

“ ” key is pressed without release. Thermostat auto switch to cooling or heating mode in accordance with result set point 

compared to environment temperature under AUTO “

” mode (This mode is called AFCV2 mode). 

"

 Fan speed selection: If the switch on panel is slipped to position LOW

MED or HIGH, namely, corresponding Fan 

speed of representation LOW

MED

HIGH symbol is selected. 

MODEL DENOMINATIONS

 

HL116   

DA/DA2: 

Control Motorized Valve (DA: Control 2-wire N.C. FCU valve; DA2: Control 3-wire FCU valve) and 

3-speed fan; When the temperature reaches the set-point, it will close the Motorized Valve with the 

fan still running. 

(A)FCV2:

 Control 4 pipe fan coil units, Control two Motorized Valves and 3-speed fan, when the temperature 

reaches the set-point, it will close the Motorized Valves with the fan still running. 

P:

       Control 3-wire FCU valve (Floating Arithmetic) and 3-speed fan; when the temperature reaches the 

set-point, it will close the Motorized Valve with the fan still running. 